Audited 05 Aug 2026·Last updated 28 Oct 2026·3 citations·Tier 2·0 uses

Eui Calculator

Work out a building's site EUI in kBtu/ft² per year from twelve months of electricity (kWh), natural gas (therms) and gross floor area.

Eui Calculator

kWh
therms
ft2
Site energy use intensity
42.0607
Annual site energy divided by gross floor area, in kBtu per square foot per year.
Annual site energy
841,214.1633kBtu

Background.

A utility bill tells you how much energy a building bought, but not whether that is a lot. A large hospital and a small dental office will never use similar amounts, and electricity arrives in kilowatt-hours while gas arrives in therms, so even the two bills for one building cannot simply be added together. Energy use intensity deals with both problems at once: convert every fuel to the same unit, add them, and divide by floor area.

In the United States the convention, set by the EPA's ENERGY STAR Portfolio Manager, is thousands of British thermal units per square foot per year, written kBtu/ft². A kilowatt-hour is 3.412 kBtu and a therm is 100 kBtu by definition, so one therm of gas holds as much energy as about 29.3 kWh. In the worked example below, 100,000 kWh beside 5,000 therms looks like a 20-to-1 split on paper, yet gas supplies about 59% of the energy.

The figure produced here is site EUI: energy counted at the meter, exactly as the bills record it. It is the number facility managers track year over year, and the one to check when you want to know whether a lighting retrofit or a new boiler made a difference in the same building.

Three things are left out on purpose. Fuels other than electricity and natural gas, such as fuel oil, propane or district steam, have no input, so a building that burns them will read low. Source energy, which adds the losses at power plants and on the grid, is not computed. And there is no weather normalization, so a harsh winter pushes gas use and the EUI up without anything having changed inside the building.

What is eui calculator?

Site energy use intensity is a building's total annual energy consumption, as measured at its own meters, divided by its gross floor area. Here the total is electricity plus natural gas, both expressed in kBtu, so the result is kBtu per square foot per year. Gross floor area in the ENERGY STAR sense is the whole enclosed area of every floor, measured to the outside surfaces of the exterior walls, corridors, stairwells and plant rooms included. Parking areas are not counted in it.

How to use this calculator.

  1. Add up twelve consecutive months of electricity from the bills and enter the total in Annual electricity use. Use the kWh consumption line, not the kW demand figure that some commercial bills also show.
  2. Do the same for gas in Annual natural gas use. If the utility bills in CCF (hundreds of cubic feet), multiply by the therm factor printed on the bill to get therms before entering it.
  3. Enter Gross floor area in square feet, measured to the outside of the walls and including every floor, but leaving out parking. If you only have square metres, multiply by 10.764.
  4. Compare the site EUI first with the same building's earlier years. Set it against other buildings only when they share a use type and a similar climate.

The formula.

Site EUI=(electricity kWh*3.412141633 + gas therms*100)/gross ft2

Site EUI = (E × 3.412141633 + G × 100) ÷ A, where E is annual electricity in kWh, G is annual natural gas in therms and A is gross floor area in square feet. The 3.412141633 is the number of kBtu in one kilowatt-hour: a kWh is 3,600 kJ and a Btu is about 1.055 kJ. The 100 follows from the therm being defined as 100,000 Btu. The bracketed sum is the annual site energy, reported on its own in kBtu, and dividing by area turns it into an intensity. Because the result is a ratio, the floor area matters as much as the bills: entering 10% too little area makes the EUI about 11% too high. Neither fuel is weighted for how it was generated or delivered, which is what separates site EUI from source EUI.

A worked example.

Example

Take a 20,000 ft² office that used 100,000 kWh of electricity and 5,000 therms of gas over a year. Electricity first: 100,000 × 3.412141633 = 341,214.1633 kBtu. Gas next: 5,000 × 100 = 500,000 kBtu. Together that is 841,214.1633 kBtu of annual site energy. Dividing by the floor area, 841,214.1633 ÷ 20,000 = 42.0607 kBtu/ft² per year. Gas provides about 59% of that energy, even though its bill shows a number one-twentieth the size of the electricity figure. The denominator deserves the same care as the meters: had the owner entered 18,000 ft², say rentable area instead of gross, the same bills would give 46.73 kBtu/ft², an apparent 11% decline in performance that comes from the floor area alone.

gross Floor Area Sq Ft20,000
annual Fuel Therms5,000
annual Electricity Kwh100,000

Frequently asked questions.

What counts as a good EUI for my building?
It depends mostly on what the building does and where it stands. Hospitals, restaurants and buildings that run around the clock carry high EUIs because of their hours and process loads, while warehouses and self-storage run low. Portfolio Manager compares each building with national survey data for its own property type, which is the only fair yardstick.
What is the difference between site EUI and source EUI?
Site EUI counts energy at the building's meters. Source EUI traces it back to raw fuel by adding what was lost producing and delivering it. Grid electricity loses a great deal at power plants, so it weighs close to three times more in source terms, while piped gas changes little. ENERGY STAR scores are based on source energy; this page reports site energy only.
My gas bill is in CCF, not therms. What do I enter?
Convert first. A CCF is a hundred cubic feet of gas, a volume, while a therm is a fixed quantity of energy, 100,000 Btu. Utilities print a therm factor or heat-content figure on the bill, usually a little above 1, and CCF multiplied by that factor gives therms. Entering CCF unconverted typically understates gas by a few percent.
Why did our EUI rise this year when nothing changed in the building?
Weather is the usual cause. A colder winter drives up heating gas and a hotter summer drives up cooling electricity, and site EUI takes the bills as they come. Portfolio Manager also reports a weather-normalized figure for this reason. After weather, look at occupancy, longer operating hours or new equipment such as a tenant's server room.
We also burn fuel oil or buy district steam. Can those be included?
Not directly: the page has inputs only for electricity and natural gas, so any other fuel is ignored and the EUI comes out low. You could convert another fuel to equivalent therms using its own heat content and add it to the gas figure, but Portfolio Manager handles mixed fuels properly and also applies source factors to each.
Does a lower EUI always mean a more efficient building?
Only among comparable buildings and conditions. Shorter hours or empty floors lower the EUI without any efficiency gain. Replacing a gas boiler with an electric heat pump lowers site EUI genuinely, because the heat pump moves more heat than the electricity it uses, but it also shifts the mix toward electricity, which counts for more in source terms.

How this page was produced

Published by
Quanta Calculator
Primary sources
3 cited below
Method
Site EUI=(electricity kWh*3.412141633 + gas therms*100)/gross ft2