Valve Flow Coefficient Calculator
Valve Cv calculator: Cv = Q√(SG/ΔP) sizes a control valve from flow, allowable pressure drop, and specific gravity — the US screening formula.
Valve Flow Coefficient Calculator
Background.
Control-valve catalogues rate every valve with one number: Cv, the flow coefficient, defined as the US gallons per minute of 60 °F water the wide-open valve passes with a 1 psi pressure drop across it. Sizing a valve starts by asking the question in reverse — given the flow my process needs and the pressure drop I can spend, what Cv must the valve offer? — and the basic liquid relation answers it: Cv = Q·√(SG/ΔP).
The formula is the orifice square-root law in customary dress. Flow through a restriction rises with the square root of pressure drop — push four times harder and only twice the flow emerges — and with the inverse square root of the liquid's density, entering here as specific gravity relative to water. Water at SG = 1 reduces the definition to its calibration case; a light hydrocarbon at 0.7 needs about 16% less Cv for the same duty, brine at 1.2 about 10% more.
The number returned is the required coefficient, and its role is valve selection with margin: the valve chosen should offer more than the required Cv when wide open, leaving travel in reserve for control, without being oversized so grossly that it operates nearly shut, where control is poor and wear concentrates. Comparing the required Cv against the ratings of candidate valves is the screening step of every specification.
Screening is the operative word. The full sizing standard (ISA-75.01 / IEC 60534) layers on corrections this basic relation omits: viscous liquids, flashing and cavitation when the drop is large against the liquid's vapour pressure, choked flow, pipe-reducer effects, and gas service's entirely different equations. The scope note beside the result keeps that boundary explicit — this page ranks candidates and catches order-of-magnitude errors; the standard signs off the purchase.
What is valve flow coefficient calculator?
Cv is the US valve flow coefficient: the flow of 60 °F water, in US gallons per minute, that passes through a valve at a stated opening when 1 psi is dropped across it. It condenses a valve's geometry — seat size, plug shape, passage tortuosity — into a single hydraulic capacity, letting dissimilar valves be compared directly. For nonflashing turbulent liquid service the required coefficient follows Cv = Q√(SG/ΔP). The metric sibling Kv (m³/h of water at 1 bar) converts as Kv = 0.865·Cv. Because Cv belongs to a particular opening, a control valve's datasheet usually lists a table of Cv against travel rather than a single figure; the catalogue headline is the wide-open value, and a valve throttling in service is working somewhere down that table.
How to use this calculator.
- Enter the target flow in US gallons per minute — convert from m³/h by multiplying by 4.403, or from litres per minute by dividing by 3.785.
- Enter the pressure drop the valve is allowed to absorb at that flow, in psi: not the pump's full head, but the share allocated to the valve — commonly a third or so of the system's dynamic losses, so the valve retains authority. From bar, multiply by 14.504.
- Enter the liquid's specific gravity against water: 1.0 for water, ≈0.85 for diesel-range oils, ≈1.15 for a 20% sodium chloride brine.
- Size for the hardest case the valve will meet — the maximum flow together with the smallest drop available at that flow — then shortlist valves whose wide-open rating exceeds that Cv with room to spare for control.
- Before purchase, hand the shortlist to the full ISA/IEC sizing calculation — mandatory when the liquid is viscous, near its vapour pressure (cavitation and flashing), or when the drop is a large fraction of inlet pressure.
The formula.
For turbulent liquid flow through a fixed restriction, Bernoulli plus a discharge coefficient gives Q ∝ A√(ΔP/ρ): flow rises with the root of the driving pressure and falls with the root of density. Cv packages the proportionality in customary units — defining it as gpm of water per √psi makes the constant exactly 1 for the calibration fluid, and any other liquid enters through its density ratio, SG. Rearranged for capacity, Q = Cv√(ΔP/SG); rearranged for selection, Cv = Q√(SG/ΔP). The square root shapes practice: halving the allowed drop forces a 41% larger Cv, and pressure drop measurements taken at one flow scale to another as (Q₂/Q₁)²: a valve dropping 4 psi at 20 gpm will drop (30 ÷ 20)² × 4 = 9 psi at 30 gpm. The law's boundaries are physical — laminar (viscous) flow bends the exponent away from ½, and once the internal pressure dips to the liquid's vapour pressure, bubbles form (cavitation) or persist (flashing) and flow chokes: more ΔP then buys no more Q, which the bare formula cannot see.
The Kv conversion is nothing more than units. Kv uses cubic metres per hour and bar where Cv uses US gallons per minute and psi, so Cv ÷ Kv = 4.403 ÷ √14.504 ≈ 1.156, which is the same statement as Kv = 0.865·Cv. Specific gravity, being a ratio, is identical in both systems.
The formula also assumes the valve sits in a pipe of its own size. When a smaller valve is fitted between reducers, the reducers take part of the drop and the assembly passes less than the valve's catalogue Cv suggests; the full standard handles this with a piping geometry factor, which this screening relation leaves out. Fittings elsewhere in the line belong to the system's losses, not the valve's.
A worked example.
A control valve must pass 20 US gallons per minute of water (specific gravity 1.0) while dropping 4 psi across the valve. What Cv does that require? The liquid sizing relation is Cv = Q × √(SG/ΔP). The square root term is √(1/4) = 0.5, so Cv = 20 × 0.5 = 10 exactly — the valve must flow 10 gpm of water at a 1 psi drop. The square root is the part intuition gets wrong: to halve the pressure drop at the same flow you need √2 ≈ 1.41 times the Cv, not twice. And because SG sits inside the root, even a notably heavy liquid like a 1.2-SG brine only raises the required Cv by a factor of √1.2 ≈ 1.095, about 9.5%. The same relation works from metric process data once the units are converted. A duty of 10 m³/h of oil at SG 0.85 with 0.5 bar available is 44.03 gpm and 7.252 psi, so Cv = 44.03 × √(0.85 ÷ 7.252) = 15.07. Working in Kv instead gives 10 × √(0.85 ÷ 0.5) = 13.04, and 13.04 ÷ 0.865 lands on the same 15.07. This is the screening number for shortlisting valve sizes; the manufacturer's full method then checks choking, viscosity and cavitation before anything is ordered.
Frequently asked questions.
What does a Cv of 10 physically mean?
Why does required Cv shrink when I allow a larger pressure drop?
Which flow and pressure drop should I size for?
How does specific gravity enter, and what about viscous liquids?
Does the liquid's temperature matter?
What are cavitation and flashing, and why can't this formula see them?
Can I size a gas or steam valve with this formula?
What Cv does a control valve have when it is only part open?
My flow data is in litres or imperial gallons. What should I watch for?
How do Cv and the metric Kv relate?
References& sources.
- [1]Emerson, Control Valve Handbook, 6th ed.
- [2]Swagelok, Valve Sizing Technical Bulletin.
- [3]BIPM, The International System of Units (SI Brochure), 9th ed., version 3.01, coherent derived units and quantity equations.
- [4]NIST Special Publication 811, Guide for the Use of the International System of Units, 2008 edition.
- [5]ISA, Control Valve Sizing Equations, ANSI/ISA-75.01.01 (bibliographic standard).
How this page was produced
- Published by
- Quanta Calculator
- Overseen by
- Daniel, Quanta Calculator Researcher
- Primary sources
- 5 cited below
- Method
- Cv = Q(gpm) sqrt(SG / DeltaP(psi))
- Published
- Last verified
Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.
In this category
Embed
Quanta Pro
Paid features are coming later.
- All 1560 calculators remain free
- No billing is enabled