Generator Size Calculator

Size a generator from your appliance list: total running watts, the biggest motor's starting surge and a safety margin, as running and starting watts.

Generator Size Calculator

Total simultaneous running watts
2,000
The combined running watts of every load in your list: the steady power the generator must deliver once everything is on.
Largest additional starting surge (W)
1,500
Minimum starting watts needed
3,500
Safety-margin running watts
2,400
Safety-margin starting watts
4,200
Your generator: running check
Not checked (enter the generator's rating to compare)
Your generator: starting check
Not checked (enter the generator's rating to compare)

Background.

A generator can run the lights, the router and the television without strain and still stall the moment the refrigerator's compressor switches on. Motors take a brief rush of power to get turning, often two or three times what they draw once running, and that moment, not the steady load, is what trips undersized generators. Sizing one means checking two numbers: the running watts of everything you want on at once, and the extra kick needed when a motor starts.

The example list here is a typical outage kit: a refrigerator at 700 running watts, a sump pump at 800, 300 watts of lights, a 50-watt router and a 150-watt television. Together they draw 2,000 watts once running. The refrigerator needs 2,200 watts for a moment to start, 1,500 more than it runs at; the sump pump needs 1,200 extra. On the assumption that only one motor starts at a time, the worst moment is the refrigerator starting while everything else is already on, which calls for 2,000 + 1,500 = 3,500 watts. A 20% margin turns those into 2,400 running watts and 4,200 starting watts, the two figures to hold against a generator's specification.

Generators are sold on exactly that pair. The running rating (sometimes called rated or continuous watts) is what the machine can deliver hour after hour; the starting rating (surge or peak watts) is what it can deliver for a few seconds. Both have to clear your figures. Since the one-motor-at-a-time assumption only holds if you make it hold, the usual practice is to start the largest motor first and switch other loads on one by one after it.

None of this makes a generator safe to run. Portable generators produce carbon monoxide, a gas you cannot see or smell, and FEMA, the CDC and the Consumer Product Safety Commission all warn that running one indoors or in a garage can kill. Placement, connection to the house and fuel storage come before any wattage question.

What is generator size calculator?

Running watts are the steady power an appliance draws once it is operating. Starting watts, also called surge watts, are the higher power some appliances need for a moment as they start: anything with an electric motor or compressor, such as refrigerators, freezers, pumps, air conditioners and many power tools. Lights, electronics and heating elements start at about the same power they run at, but heating is the quiet budget-breaker: a common 1,500-watt space heater has no surge to speak of, yet on its own it draws three-quarters of the example list's 2,000 running watts. Generator sizing compares the total of your simultaneous running loads, and that total plus the largest single starting surge, with the generator's running and starting ratings. A safety margin on top keeps the machine from working at its exact limit.

How to use this calculator.

  1. Decide which appliances have to run together during an outage. The list should be the set you will power at the same time, not everything in the house.
  2. Edit the load list. Each appliance is one entry written as {"name":"freezer","runningWatts":500,"startingWatts":1500}, with entries separated by commas inside the square brackets. Every entry counts toward the total unless it carries "simultaneous":false, which leaves that appliance out; deleting the entry does the same.
  3. Take running watts from the appliance label or manual, and starting watts from the manual or manufacturer. For appliances without a motor, such as lights and electronics, make starting watts equal to running watts; starting watts can never be lower.
  4. Keep the 20% safety margin or change it. A larger margin buys headroom for uncertain labels and future additions, at the cost of a bigger, heavier generator.
  5. Check a generator by comparing its running rating with the safety-margin running watts and its starting rating with the safety-margin starting watts; both must be at least as large. Or enter the generator's two ratings in the optional fields and the pass-or-short lines at the bottom of the results make the comparison for you.
  6. Before buying, check the outlets as well as the watts: the generator needs the 240-volt or high-current outlet your transfer equipment or largest appliance uses, and enough 120-volt outlets to spread the rest.

The formula.

W = ( ΣRᵢ + Sₘₐₓ ) × (1 + m)

The calculation has three steps. First it adds the running watts of every entry: ΣR = R₁ + R₂ + … + Rₙ. That is the load the generator carries once everything is on. Second, for each entry it finds the extra starting surge, Sᵢ = startingᵢ − runningᵢ, which is zero for loads that start at their running power, and keeps the largest, Sₘₐₓ. The minimum starting requirement is ΣR + Sₘₐₓ: every other load already running while the hungriest motor starts.

Third, both figures are scaled by the safety margin m: recommended running watts = ΣR × (1 + m), and recommended starting watts = (ΣR + Sₘₐₓ) × (1 + m). With m at 20% the multiplier is 1.2.

Adding only the largest surge is the central assumption. A starting surge lasts only a moment, so two motors overlap only if they happen to start at the same instant. That can happen: when a generator is switched on with everything already plugged in, or when a refrigerator and a freezer happen to cycle together. If it could happen with your loads, combine the motors that might coincide into one entry whose running watts are the sum of their running watts and whose starting watts are the sum of their starting watts. Their surges then add up instead of only the larger counting. Where one motor's surge dwarfs the rest, as a central air conditioner's often does, a soft-start kit fitted to the compressor lowers its inrush; enter the reduced starting figure the kit maker quotes and the starting requirement falls with it.

The arithmetic works in watts and ignores voltage. A 240-volt load such as a well pump needs a generator with a 240-volt output and a suitable connection, whatever the wattage says, and the margin does not account for generators losing output in high heat or at altitude, for which manufacturers publish their own derating.

A worked example.

Example

The default list holds five loads. Their running watts add up as 700 + 800 + 300 + 50 + 150 = 2,000 W, the total simultaneous running load. Next come the extra starting surges. The refrigerator starts at 2,200 W against 700 W running, a surge of 2,200 − 700 = 1,500 W. The sump pump starts at 2,000 W against 800 W, a surge of 1,200 W. The lights, router and television start at their running power, so their surge is zero. The largest surge is the refrigerator's 1,500 W, and the minimum starting requirement is 2,000 + 1,500 = 3,500 W. With the 20% margin, the running figure becomes 2,000 × 1.2 = 2,400 W and the starting figure 3,500 × 1.2 = 4,200 W. A generator rated at least 2,400 running and 4,200 starting watts covers this list, provided the refrigerator and the pump never start together. Notice which figure sets the size: the starting requirement is 1.75 times the running load, so a machine chosen on running watts alone would be the one that stalls. If they might, combining them into one entry of 1,500 running and 4,200 starting watts raises the requirement to 4,700 W, or 5,640 W with the margin, a noticeably larger machine for the same five appliances.

safety Margin Percent20

Frequently asked questions.

Where do I find starting watts if the label only gives running watts?
Look in the owner's manual or the manufacturer's specification first. Motor nameplates often list LRA, locked-rotor amps, the current the motor draws at the instant of starting; multiplying LRA by the supply voltage gives a rough, usually generous estimate of the starting demand. Failing that, the example's refrigerator and sump pump start at about three and two and a half times their running watts.
My appliance lists amps, not watts. How do I convert?
Multiply the amps by the supply voltage. A device drawing 6.5 amps at 120 volts uses about 6.5 × 120 = 780 watts. For heaters and incandescent lamps that is exact. For motors the product is volt-amperes, which runs a little above true watts, so using it errs on the generous side, which is the safe direction when sizing a generator.
Why does it add only the largest starting surge?
Because motors draw their surge only for a moment, so the worst case under normal use is one motor starting while everything else is already running. The assumption holds when you control the order: start the largest motor first, then switch on the rest one at a time. Plugging everything in before starting the generator breaks the assumption, because every motor tries to start at once.
How do I account for two motors that might start together?
Merge them into a single entry. Give it running watts equal to the sum of their running watts and starting watts equal to the sum of their starting watts, so its surge is the two surges added. In the example, a combined refrigerator-and-pump entry of 1,500 running and 4,200 starting watts raises the minimum starting requirement from 3,500 W to 4,700 W.
Is a 20% safety margin enough?
It is a planning choice, not a rule. A margin covers labels that understate real draw, ageing appliances, generators losing output in hot weather or at altitude, and the extra lamp someone plugs in later. Too little leaves you running at the limit; too much buys a heavier, louder machine. With 20%, the steady load uses about 83% of the recommended running rating.
Does an inverter generator change the sizing?
The comparison is the same: its running rating must cover the running figure and its surge rating the starting figure. Inverter generators produce a steadier, cleaner output that suits electronics, and many vary engine speed with the load, which makes them quieter at light loads. They tend to be smaller, so check their starting rating carefully against any motor loads.
Can a portable generator run a 240-volt well pump?
Only if it has a 240-volt output and the pump is connected through suitable transfer equipment. On a typical 120/240-volt portable generator the 120-volt outlets draw from two halves of the output, each able to supply roughly half the total, so piling every 120-volt load onto one half can overload it while the total looks fine. Spread loads across both.
Can I plug the generator into a wall socket to power the house?
No. Feeding power back through a household outlet, known as backfeeding, can send electricity out along the utility lines and electrocute line workers or neighbours, and it can damage the generator and your wiring when grid power returns. Connecting a generator to house circuits needs a transfer switch or approved interlock, installed by a licensed electrician.
Where should the generator sit while it runs?
Outdoors, well away from the house. Federal safety guidance says never to run one inside a home, garage, basement, crawlspace or shed, even with doors or windows open, and the Consumer Product Safety Commission advises at least 20 feet from the house with the exhaust pointed away from doors, windows and vents. Fit battery-powered carbon monoxide alarms inside.
Does this work for a permanently installed standby generator?
It helps you draw up the load list, but a standby system is sized and installed by a qualified electrician or installer. Those units often feed whole panels through an automatic transfer switch, run on natural gas or propane, and need a load calculation and permits under local electrical code. Your running and starting totals are a useful starting point for that conversation.

How this page was produced

Published by
Quanta Calculator
Primary sources
5 cited below
Method
W = ( ΣRᵢ + Sₘₐₓ ) × (1 + m)
Published
Last verified

Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.