Solar Battery Sizing Calculator

Size a home or off-grid battery bank in kWh from the daily energy you need backed up, days of autonomy, depth of discharge and round-trip efficiency.

Solar Battery Sizing Calculator

%
%
Required nominal battery capacity
27.7778
Nameplate battery capacity needed, in kWh, after allowing for depth of discharge and round-trip losses.
Required usable delivered capacity
22.2222
Backed-up load energy
20

Background.

To get 20 kWh out of a battery bank, you need one rated for nearly 28. Two allowances explain the gap. Most batteries should not be run completely flat, so only a fraction of the nameplate, the depth of discharge, counts as usable; and energy passing through a battery system loses some of itself to the charger, the inverter and the cells, which is what round-trip efficiency measures. Take the energy your backed-up circuits need in a day, multiply by the number of days the battery must carry them alone, divide by both allowances, and you have the nominal capacity to shop for.

That is the standard first pass for off-grid and backup designs, and it leans conservative: it assumes no solar recharging during the autonomy days and books the whole round-trip loss against the battery. It also says nothing about power. A bank with plenty of kilowatt-hours can still fail to start a well pump or a central air conditioner if its inverter's continuous and surge ratings are too small, and usable capacity shrinks in the cold and as the cells age. Those checks, and the manufacturer's warranty terms, come after the energy figure.

What is solar battery sizing calculator?

Battery sizing turns a daily energy need into a nameplate capacity. Four quantities are involved. The backed-up load energy is what the circuits on the battery actually consume over the autonomy period, in kWh. Days of autonomy is how long the battery must supply that load with no help from the grid or the panels. Depth of discharge (DoD) is the share of the nameplate you allow yourself to use: lead-acid banks are commonly limited to about half their rating to protect cycle life, while lithium iron phosphate batteries tolerate much deeper cycling. Round-trip efficiency is the energy you get back out divided by the energy you put in.

Capacity comes in two flavours on spec sheets. Nominal or total capacity is the full chemical rating of the cells. Usable capacity is what the battery's management system will actually let you draw, already reduced by the manufacturer's own depth-of-discharge limit. Comparing a usable figure from one product with a total figure from another is the quickest way to buy the wrong battery, so check which number each data sheet quotes before you compare prices per kWh.

The efficiency figure also depends on how the battery is wired into the solar system. In a DC-coupled system the panels charge the battery directly through a charge controller, and power is converted to AC once, on the way out. In an AC-coupled system, common when a battery is added to existing solar, the panel output is converted to AC by the solar inverter, back to DC to charge the battery, and to AC again on discharge. Each conversion costs a little, so use the round-trip figure the manufacturer quotes for the configuration you are actually installing.

How to use this calculator.

  1. Enter the daily backed-up energy in kWh. For individual appliances, divide the annual kWh on the yellow EnergyGuide label by 365, or multiply watts by hours of use and divide by 1,000. For a whole house, divide a monthly bill's kWh by the days in the billing period.
  2. Enter the days of autonomy: how long the battery must run those loads with no grid and no useful sun. A grid-tied backup system may need one; an off-grid cabin in a cloudy season may need several. Fractions are allowed: if the panels carry the house by day and only evening and overnight use falls on the battery, enter that share of a day, which is often well under one.
  3. Enter the maximum depth of discharge from the battery's data sheet. If the data sheet already quotes usable capacity, enter 100% and compare that usable figure with the required usable capacity result.
  4. Enter the round-trip efficiency from the data sheet, or keep 90% as a starting assumption for a lithium system.
  5. Round the nominal result up to the module sizes actually sold, then check separately that the inverter's continuous and surge power ratings can run your largest loads.

The formula.

nominal battery capacity = daily backed-up energy × autonomy days ÷ depth of discharge ÷ round-trip efficiency

Three results come from four inputs. Load energy L = E × D, where E is daily backed-up energy in kWh and D is days of autonomy. Required usable capacity U = L ÷ η, where η is round-trip efficiency as a fraction. Required nominal capacity N = L ÷ (DoD × η), with DoD also as a fraction. Dividing by DoD scales the usable requirement up to a nameplate that leaves the protected reserve untouched; dividing by η covers conversion losses.

The efficiency step is deliberately cautious. Round-trip efficiency covers both charging and discharging, yet only the discharge half reduces what a full battery can deliver. If the two halves lost equally, discharge efficiency would be the square root of round-trip efficiency, √0.9 ≈ 0.9487 for a 90% system, and 20 kWh of load would need about 21.08 kWh of stored energy rather than 22.22. The method's extra 5% or so is a margin, and it has a second use: the usable figure is also the energy the panels must put back in to refill the battery after delivering the load.

Because DoD and η multiply in the denominator, small changes compound. Dropping DoD from 80% to 50% raises the required nameplate by 60%; dropping efficiency from 90% to 85% adds another 6%. Days of autonomy scale everything in proportion, so the second day of autonomy costs as much battery as the first, and entering half a day for a night-only need halves all three results.

The model treats capacity as fixed, which suits lithium batteries better than lead-acid. Lead-acid capacity is usually rated at a slow, 20-hour discharge, and the same bank delivers noticeably less when drained in a few hours, so a lead-acid design serving heavy loads needs extra margin beyond what the formula shows.

Not modelled: battery capacity lost at low temperatures, gradual capacity fade with age, a backup reserve held back from daily cycling, the inverter's own standby draw, and any solar recharge during the outage. Each one can be handled by adjusting an input, as the questions below explain.

A worked example.

Example

Suppose the circuits you want on backup use 20 kWh a day, you want one full day of autonomy, the battery allows an 80% depth of discharge and the system's round-trip efficiency is 90%. Load energy: 20 kWh × 1 day = 20 kWh. Usable capacity: 20 ÷ 0.90 = 22.2222 kWh. That is the energy the battery must be able to hand over, with conversion losses included. Nominal capacity: 22.2222 ÷ 0.80 = 27.7778 kWh, the same as 20 ÷ (0.8 × 0.9) = 20 ÷ 0.72. Put another way, every kWh of daily load costs about 1.3889 kWh of nameplate at these settings. The 20 kWh spread over 24 hours is an average draw of only about 0.83 kW, but the loads will not arrive evenly; a refrigerator compressor, a microwave and a furnace blower switching on together set the power the inverter must supply, which is a separate check. In practice, batteries come in fixed module sizes. Built from 10 kWh nominal modules, this requirement rounds up to three, 30 kWh, leaving about 2.2222 kWh of headroom, a cushion that will be absorbed as the cells lose capacity over the years.

daily Energy Kwh20
autonomy Days1
maximum Depth Of Discharge Percent80
round Trip Efficiency Percent90

Frequently asked questions.

How do I work out my daily backed-up energy?
List the circuits the battery will carry and add up their daily use. A refrigerator whose EnergyGuide label says 600 kWh a year uses about 1.6438 kWh a day. For whole-house backup, a 900 kWh monthly bill means about 30 kWh a day, which at the default 80% and 90% needs about 41.6667 kWh of nameplate.
My battery's data sheet already lists usable capacity. What depth of discharge do I enter?
Enter 100%, then compare the product's usable rating with the required usable capacity result. The manufacturer has already applied its own depth-of-discharge limit to a usable figure, and dividing by 80% again would double-count the reserve and push you toward a battery a quarter larger than you need.
Does solar recharging during an outage reduce the size I need?
Yes, but the formula assumes it does not, which is the safe case for storms and winter outages. If you are confident of some harvest each day, enter the daily shortfall, load minus expected solar, as the daily energy. Base that expectation on a poor day, not an average one, because outages often coincide with bad weather. With a 20 kWh load and 8 kWh of dependable harvest, entering 12 kWh gives about 16.6667 kWh of nameplate instead of 27.7778.
Can a battery sized this way run my central air conditioner or well pump?
Energy and power are separate tests. This calculation answers whether the battery holds enough kilowatt-hours; whether it can start a motor depends on the inverter's continuous kW and its surge rating for the brief inrush when a compressor or pump starts. Soft-start devices can cut that inrush and bring a large motor within reach. In many modular systems each added unit raises available power as well as energy, which is sometimes the real reason to install more capacity than the energy figure alone calls for.
How much larger does a lead-acid bank need to be?
Considerably. For 10 kWh a day over two days, a lead-acid bank limited to 50% depth of discharge with 85% round-trip efficiency needs about 47.0588 kWh of nameplate. A lithium system at 80% and 90% needs about 27.7778 kWh for the same 20 kWh, so lead-acid needs roughly 1.69 times the rating. Lead-acid also wants regular full recharges to avoid sulfation, which a run of short winter days can make difficult.
How should I allow for cold weather and ageing?
Size for the battery you will have, not the one you buy. If a warranty guarantees 70% of original capacity at the end of its term and you want full autonomy until then, divide the nominal result by 0.7: 27.7778 becomes about 39.6825 kWh. Batteries in unheated garages or sheds also deliver less on cold days, and lithium cells generally must not be charged below freezing unless the unit heats itself, which matters for an off-grid bank that relies on winter sun.
Should I back up the whole house or only critical loads?
Critical loads are far cheaper to cover. Suppose moving refrigeration, lighting, internet, a gas furnace's blower and a few outlets onto a separate backed-up panel brings the daily need to 8 kWh. That needs about 11.1111 kWh of nameplate for one day and 33.3333 kWh for three, against about 41.6667 kWh for one day of a 30 kWh household.
What if the battery also cycles every day to cut my electricity bill?
Then only the backup reserve you set is guaranteed to be there when an outage starts. On a 30 kWh system with a 30% reserve, 9 kWh is held back. Make sure that reserve, not the full nameplate, covers the required usable capacity for the outage length you care about.
Do small round-the-clock loads like the inverter itself matter?
More than people expect, especially off-grid. A device drawing 30 W around the clock uses 0.03 × 24 = 0.72 kWh a day, and at 80% depth of discharge and 90% efficiency that alone needs 1 kWh of nameplate per day of autonomy. Add the inverter's idle draw, routers, security cameras and other always-on electronics to the daily energy.
Is there still a federal tax credit for a home battery?
Not for new installations. The residential clean energy credit covered battery storage of at least 3 kWh from 2023, but the IRS says the credit is not available for property placed in service after December 31, 2025. State, utility and local programs vary, and the DSIRE database lists those that remain.

How this page was produced

Published by
Quanta Calculator
Primary sources
5 cited below
Method
nominal battery capacity = daily backed-up energy × autonomy days ÷ depth of discharge ÷ round-trip efficiency