Audited 29 Jul 2026·Last updated 28 Oct 2026·7 citations·Tier 1·0 uses

Wire Size Calculator (NEC Ampacity and Voltage Drop)

Size copper or aluminium AC wire from load amps, run length and conditions: 2023 NEC ampacity with heat, bundling and terminal limits, plus voltage drop.

Wire Size Calculator

What are you sizing?
The real running current of the load in branch-circuit mode — not the breaker you plan to use. In dwelling-service mode this is the service or feeder rating instead, and it must be between 100 A and 400 A.
A
120 for a standard receptacle circuit, 240 for a dryer, range, EV charger or a residential service, 208 or 480 line-to-line for commercial three-phase. This is the number the voltage-drop percentage is measured against. Low-voltage DC systems belong on the DC wire size calculator instead.
V
Phase
Conductor material
Conductor insulation temperature rating
Equipment termination rating
Is the load continuous?
Table 310.16 is built on 30 °C (86 °F). An attic in summer, a rooftop raceway or a boiler room is routinely 45–60 °C, and that is where ampacity quietly disappears — a 90 °C conductor keeps only 82% of its rating at 50 °C and 58% at 70 °C.
°C
Count only conductors that actually carry current. Equipment grounding conductors never count, and the neutral of a balanced three-phase four-wire circuit does not count either — but the neutral of a three-wire circuit fed from two phases of a three-phase system does. Four to six conductors costs you 20% of the ampacity; ten to twenty costs half of it.
Panel to load, measured along the route the cable actually takes, not straight-line. The calculator doubles it for the return path on single phase. Measure generously: bends, drops and the loop inside the panel all count.
ft
3% is the figure NEC 210.19(A) Informational Note No. 4 recommends for a branch circuit, and 5% for feeder plus branch circuit combined. Informational Notes are not enforceable code — but several jurisdictions adopt them by local amendment, and equipment does not care what the code says about it.
%
Conductor size to install
1 AWG copper — governed by ampacity. This is a 100 A non-continuous load needing 100 A of conductor ampacity, with 60 °C terminations, 90 °C insulation, a 1.00 ambient correction and a 1.00 bundling adjustment. Verify against the code edition your jurisdiction has actually adopted and have a licensed electrician sign off before any of it is installed.
The larger of the two minimum sizes, with the constraint that set it, sized to the 2023 NEC; local amendments govern, and a licensed electrician must confirm the conductor, terminations and breaker before installation.
Minimum size on ampacity
1 AWG copper — the smallest size whose 90 °C ampacity, after the 1.00 ambient correction and 1.00 bundling adjustment and capped at the 60 °C termination column, still reaches 100 A. It gets there with 110 A.
Minimum size on voltage drop
4 AWG copper — the smallest size with at least 35833 circular mils, which is what holds the drop over 100 ft one-way to 3 % of 240 V. Voltage drop is a recommendation in NEC 210.19(A) Informational Note No. 4, not an enforceable rule — unless your jurisdiction has adopted it by amendment, which several have.
Ampacity the conductor must have
100 A
Ampacity the chosen conductor actually has
110 A
Voltage drop on the run
3.0828 V
Voltage drop as a percentage
1.28
Voltage at the load
236.9172 V
Overcurrent device
100 A
Code basis and limits
Sized against NFPA 70, 2023 edition: Table 310.16 ampacities, Table 310.15(B)(1) ambient correction, Table 310.15(C)(1) bundling adjustment, 110.14(C) termination limits, 240.4(D) small-conductor limits and 240.6(A) standard device ratings. LOCAL AMENDMENTS GOVERN and adopted editions vary by jurisdiction — some are still on the 2017 or 2020 NEC, some are already on 2026, and many cities amend the tables. This is a design aid, not a permit: a licensed electrician must confirm the conductor, the terminations and the overcurrent device before work proceeds. Low-voltage DC systems are not covered here, and boats are governed by ABYC E-11 rather than the NEC.

Background.

Run a 20 A, 120 V circuit to a workshop 150 ft from the panel and 12 AWG copper satisfies the ampacity table. At full load, though, the 300 ft of wire out and back drops about 11.85 V — nearly 10 % of the supply — and the saw at the far end sees roughly 108 V. Holding the drop to 3 % takes 6 AWG, three sizes heavier, still on a 20 A breaker.

That is the whole problem in miniature. A conductor can be too small for two unrelated reasons. One is heat: current warms the copper, the copper cooks its insulation, and the National Electrical Code's ampacity rules exist to stop that. Those rules are enforceable. The other is voltage: every foot of wire has resistance, so part of the supply is spent getting to the load. Nothing burns, but motors run hot and slow, and the code only recommends a limit. Each constraint gets its own minimum size here, and the larger one is the answer.

The heat side is several rules stacked on Table 310.16 of the 2023 NEC. A load that runs three hours or more needs 125 % of its current in ampacity. Hot surroundings and crowded raceways shrink what a conductor may carry. Section 110.14(C) caps the result at the temperature rating of the breaker or lug the wire lands on. And 240.4(D) limits the breaker on 14, 12 and 10 AWG whatever the table says. There is also a separate path for a one-family dwelling's service or main feeder, which 310.12 lets you size at 83 % of its rating.

This is AC premises wiring only. Low-voltage DC systems and boats follow different rules, and local amendments override the national tables in many places. Use the result to plan and price the job; a licensed electrician must confirm the conductor, the terminations and the overcurrent device before anything is installed.

What is wire size calculator?

Wire size in North America is a conductor's cross-sectional area, named on the American Wire Gauge scale up to 4/0 and in thousands of circular mils (kcmil) above that. The gauge runs backwards, so 14 AWG is thin and 4/0 is thick, and every six gauge steps roughly quadruples the area: 14 AWG is 4,110 circular mils and 8 AWG is 16,510. A circular mil is the area of a circle one thousandth of an inch across.

Ampacity is the current a conductor can carry continuously without exceeding its insulation's temperature rating, and it belongs to the conductor as installed rather than to the wire on the reel. One 8 AWG THHN copper conductor is 55 A in Table 310.16's 90 °C column, 50 A once it lands on 75 °C terminals, 45.1 A run through a 50 °C attic, and 38.5 A sharing a raceway with six to eight others. Voltage drop is the loss along the length, set by resistance and current alone; bundling and ambient temperature do not enter it, and run length does not enter ampacity.

How to use this calculator.

  1. Choose the sizing basis. The dwelling option covers only the service or main feeder carrying a whole one-family dwelling's load, single-phase 120/240 V, rated 100–400 A — enter that rating as the current. Everything else, three-phase included, is a branch circuit or feeder.
  2. Enter the load's real running current, not the breaker size, and mark it continuous if it runs three hours or more, as EV charging and electric heat do. Set the nominal voltage and the phase.
  3. Choose the material and the insulation rating printed on the jacket; most building wire is 90 °C THHN/THWN-2. Set the termination rating from the labels on the breaker and lugs. If you cannot check them, automatic assumes 60 °C on circuits of 100 A or less.
  4. Enter the hottest ambient temperature along the route and count every current-carrying conductor in the raceway or cable, other circuits included.
  5. Measure the one-way length along the cable's real path, drops and the panel loop included, and set the drop budget: 3 % for a branch circuit, 5 % for feeder and branch circuit together.
  6. Read both minimum sizes and which one governs. Then confirm your jurisdiction's adopted code edition and amendments, and have a licensed electrician sign off before buying or pulling wire.

The formula.

I_req = I × 1.25 (continuous) · A_usable = min( A_table(T_ins) × C_amb × C_bundle , A_table(T_term) ) · VD = 2 · K · I · L / CM

The ampacity path runs in a fixed order. First comes the required current: the load itself, 1.25 × the load if it is continuous (NEC 210.19(A)(1)), or 0.83 × the rating on a one-family dwelling service or feeder (310.12). Next, each conductor size's Table 310.16 figure is taken from the column matching its insulation and multiplied by two factors: the ambient correction from Table 310.15(B)(1), which is 1.00 at the table's 30 °C basis and falls to 0.82 at 46–50 °C for 90 °C wire, and the bundling adjustment from Table 310.15(C)(1) — 0.80 for four to six current-carrying conductors, 0.70 for seven to nine, 0.50 for ten to twenty, then 0.45, 0.40 and 0.35. The ambient bands are whole degrees, so 30.1 °C already counts as the 31–35 °C band.

Section 110.14(C) then caps the derated figure at the termination column's ampacity. On automatic, the termination is taken as 60 °C when the circuit's breaker would be 100 A or less and 75 °C above that; the dwelling path always uses 75 °C. Finally, 240.4(D) rules out 14, 12 and 10 AWG copper when the required ampacity exceeds 15, 20 or 30 A, and 12 and 10 AWG aluminium above 15 or 25 A. The smallest size that survives all of that is the ampacity minimum.

The voltage-drop path is one equation solved for area: CM = M × K × I × L ÷ (V × budget % ÷ 100), where M is 2 for single phase (out and back) or √3 for three phase, L is the one-way length in feet, and K is 12.9 for copper or 21.2 for aluminium — the resistance in ohms of a one-circular-mil, one-foot conductor at 75 °C, from NEC Chapter 9 Table 8. I is the real running current, not the 125 % figure, because the extra 25 % is a heating margin rather than current that flows; on the dwelling path the 83 % figure is used. The smallest size with at least that many circular mils is the voltage-drop minimum, and the larger of the two minimums is recommended.

The breaker shown is the smallest standard 240.6(A) rating at or above the required ampacity, held to the 240.4(D) limit on small conductors; on the dwelling path it is the service rating.

The drop equation uses DC resistance at unity power factor and ignores reactance, which suits the common sizes; from about 2/0 upward inductance matters and NEC Chapter 9 Table 9 is the better tool. Table sizing also has edges: ambients beyond an insulation's column (above 55 °C for 60 °C wire, 70 °C for 75 °C wire, 85 °C for any), loads beyond a single 1000 kcmil conductor, which need engineered parallel sets, and circuits with their own rules, such as motors (Article 430) and air-conditioning equipment (Article 440).

A worked example.

Example

A 40 A EV charger goes on the far wall of a garage: 240 V single phase, 90 ft of copper THHN from the panel, three current-carrying conductors in the conduit, 30 °C ambient, and breaker and lugs labelled 75 °C. EV charging counts as continuous, so the conductor needs 40 × 1.25 = 50 A of ampacity. At 30 °C with three conductors both derating factors are 1.00, so only the terminal cap bites. 10 AWG copper is 40 A even in the 90 °C column, short of 50. 8 AWG is 55 A at 90 °C, capped to its 75 °C value of 50 A — exactly enough, so 8 AWG is the ampacity minimum with nothing spare. For voltage drop the budget is 3 % of 240 V, or 7.2 V, and the current is the real 40 A. Required area = 2 × 12.9 × 40 × 90 ÷ 7.2 = 12,900 circular mils. 10 AWG has 10,380, too little; 8 AWG has 16,510. So 8 AWG copper is also the voltage-drop minimum, and the recommendation is 8 AWG copper, governed by both constraints equally, on a 50 A breaker — the smallest standard rating at or above 50 A. On that conductor the drop is 2 × 12.9 × 40 × 90 ÷ 16,510 = 5.6257 V, which is 2.3440 % of 240 V, leaving 234.3743 V at the charger. 10 AWG fails here on both counts: besides falling 10 A short on ampacity, it would lose 8.948 V, or 3.7283 %, over the same run. The circuit is tight on heat and on voltage at once, which is why each has to be checked on its own.

phasesingle
conductor Materialcopper
insulation Rating90
ambient Temp C30
sizing BasisbranchCircuit
one Way Length Ft90
termination Rating75
max Voltage Drop Percent3
current Carrying Conductors3
continuous Loadyes
load Amps40
system Voltage240

Frequently asked questions.

What size wire does a 100 A subpanel need, and is a 100 A house service different?
As an ordinary feeder, 100 A in copper needs 3 AWG if the terminals are listed for 75 °C, but 1 AWG on the 60 °C default that 110.14(C) applies to equipment rated 100 A or less; in aluminium, 1 AWG or 1/0. As the service of a one-family dwelling, 310.12 sizes for 83 A, giving 4 AWG copper or 2 AWG aluminium. At 200 A the dwelling answer is 2/0 copper or 4/0 aluminium, where an ordinary 200 A feeder needs 3/0 copper.
Why shouldn't I pick the wire size from the breaker I plan to use?
Because the order runs the other way: the conductor is sized from the load, and the breaker is chosen to protect that conductor. Starting from the breaker can oversize a long run expensively or undersize a small one. A 25 A requirement shows the trap — the 75 °C column lists 12 AWG copper at 25 A, but 240.4(D) limits 12 AWG copper to a 20 A breaker, so the answer is 10 AWG. Motor circuits under Article 430 follow their own sizing rules entirely.
Is the 3 % voltage-drop limit actually required by the NEC?
In the base code, no. The 3 % branch-circuit and 5 % combined figures sit in Informational Notes to 210.19(A) and 215.2(A)(1), and Informational Notes are guidance, not enforceable requirements. Some jurisdictions adopt them as mandatory local amendments, so check yours. Either way the equipment feels the drop: motors run hotter and start harder on low voltage, and a sagging supply can upset chargers and electronics.
How can the breaker's temperature rating change my wire size?
Section 110.14(C) says a conductor may be counted only at the ampacity in the column matching what it connects to. Equipment for circuits of 100 A or less is treated as 60 °C unless it is listed and identified for 75 °C. Run the EV example on the automatic setting and the 50 A requirement is checked against the 60 °C column, where 8 AWG copper is only 40 A, so the answer becomes 6 AWG at 55 A. Reading the label to confirm 75 °C saves a size.
Is 90 °C THHN worth using when my terminals are only 75 °C?
Yes, because derating starts from the 90 °C figure. Take a 30 A load through a 50 °C attic in a cable bundle with six current-carrying conductors: 10 AWG copper falls to 40 × 0.82 × 0.80 = 26.24 A, too little, while 8 AWG falls to 55 × 0.82 × 0.80 = 36.08 A, which passes. Starting from a 75 °C or 60 °C column would leave less. The terminal cap still applies afterwards, so the higher rating never lets you exceed what the terminals allow.
How much larger does aluminium wire need to be than copper?
Usually one or two sizes. On ampacity aluminium trails copper by about a size: at 75 °C, 4/0 aluminium is 180 A against 230 A for 4/0 copper, and matching it takes 300 kcmil aluminium. On voltage drop its constant is 21.2 against 12.9, about 1.64 times the resistance, so it needs that much more area. The 40 A EV example becomes 6 AWG aluminium instead of 8 AWG copper. There is no 14 AWG aluminium in the table, and aluminium needs terminals listed for it.
Which conductors count as current-carrying for the bundling factor?
Every hot conductor counts and equipment grounding conductors never do. A neutral that carries only the imbalance between other conductors, as on a balanced three-phase four-wire circuit or a shared 120/240 V neutral, is not counted, unless a three-phase wye feeds mostly electronic loads, whose harmonics make it count. A neutral that carries full load current does count: the neutral of an ordinary 120 V circuit, or of a three-wire circuit taken from two phases of a three-phase system. So three 120 V circuits in one conduit, each with its own neutral, are six conductors, and the factor drops to 0.80.
How long can a run get before voltage drop decides the size?
Sooner than most people expect. Moving the 40 A EV charger from 90 ft to 200 ft leaves ampacity at 8 AWG but raises the area needed to 28,667 circular mils, past 6 AWG's 26,240, so the answer becomes 4 AWG. At 120 V the budget is only 3.6 V, which is why a 20 A circuit 150 ft away needs 6 AWG. When circuit conductors are upsized, the code also requires a wire-type grounding conductor to grow in proportion.
How is voltage drop different on a three-phase circuit?
The out-and-back factor of 2 becomes √3, about 1.732, because a balanced three-phase load has no separate return conductor and the drop is measured between phases. Higher voltage helps far more than the factor does. A 100 A, 250 ft copper feeder with 75 °C terminations needs 3 AWG at 480 V, where ampacity governs and the drop is 2.2116 %, but at 208 V voltage drop takes over and calls for 1/0 AWG, which still drops 2.5431 %. The dwelling path is single-phase only.
Does it matter which edition of the NEC my area has adopted?
The tables here follow NFPA 70, 2023 edition. The Table 310.16 ampacities carried over unchanged from earlier editions, where the same table was numbered 310.15(B)(16), but adopted editions lag by years and differ by state and city, and local amendments to conductor and voltage-drop rules are common. Confirm both the edition and any amendments with your local authority before buying wire. For 12–48 V DC systems use the DC wire size calculator, and size boat wiring to ABYC E-11, not the NEC.

References& sources.

  1. [1]National Fire Protection Association, NFPA 70 — National Electrical Code, 2023 edition. Table 310.16, "Ampacities of Insulated Conductors with Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30 °C (86 °F)". Source of every ampacity in this calculator. The code text itself is gated behind NFPA's free-access registration; the values used here were read from two independent reproductions and cross-checked against each other. Retrieved 2026-07-29.
  2. [2]NECA/IBEW Electricians, reproduction of NEC Table 310.15(B)(16) (formerly Table 310.16), "Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60 °C Through 90 °C". Read directly from the PDF on 2026-07-29. Used as the primary transcription source for the ampacity table. This is the 2011-edition numbering; every value is identical to the 2023-edition Table 310.16.
  3. [3]Conduit.site, reproduction of NEC Table 310.15(B)(1), "Ambient Temperature Correction Factors Based on 30 °C (86 °F)", 2020 NEC. Retrieved 2026-07-29. Source of all thirty-nine correction factors implemented here, across the 60 °C, 75 °C and 90 °C columns and the sixteen ambient bands from '10 °C or less' to '81–85 °C', including the points at which the 60 °C and 75 °C columns terminate and the conductor may no longer be used.
  4. [4]Mike Holt Enterprises, "Voltage Drop Calculations". Retrieved 2026-07-29. Source of the K constants used here — 12.9 ohm-circular-mils per foot for copper and 21.2 for aluminium, both defined as the DC resistance of a 1000-circular-mil conductor 1000 ft long at 75 °C, derived from NEC Chapter 9 Table 8 — of the VD = 2·K·I·L/CM and √3·K·I·L/CM forms, and of the stated limit that the method is suitable up to 1/0 with self-inductance needing a Q adjustment at 2/0 and above.
  5. [5]Zing², reproduction of NEC Table 310.15(C)(1), "Adjustment Factors for More Than Three Current-Carrying Conductors", noted as unchanged across the 2020, 2023 and 2026 editions. Retrieved 2026-07-29. Source of the 80 / 70 / 50 / 45 / 40 / 35 percent bands and of the rule that grounding conductors and the neutral of a balanced three-phase system are excluded from the count.
  6. [6]WireRef, "NEC Article 240 — Overcurrent Protection", 2023 edition with 2026 updates noted. Retrieved 2026-07-29. Source of the 240.6(A) standard ampere ratings list (15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A and above), of the 240.4(D) small-conductor limits for copper (14, 12 and 10 AWG at 15, 20 and 30 A — the page does not reproduce the aluminium limits of 15 A on 12 AWG and 25 A on 10 AWG, which are stated in 240.4(D) itself), and of the 240.4(B) next-higher-standard-rating allowance.
  7. [7]American Boat and Yacht Council, Standard E-11, "AC and DC Electrical Systems on Boats", excerpts published by Paneltronics. Read directly from the PDF on 2026-07-29. Cited as the scope boundary rather than as an input: E-11.14.2.6 requires 3 percent maximum drop on main feeders, bilge blowers, electronic equipment and navigation lights and 10 percent on non-critical circuits, and E-11.14.2.7 sizes conductors from ABYC's own Tables VI, IX and X. Marine wiring must be sized from those tables, not from the NEC tables this page implements.

How this page was produced

Published by
Quanta Calculator
Primary sources
7 cited below
Method
I_req = I × 1.25 (continuous) · A_usable = min( A_table(T_ins) × C_amb × C_bundle , A_table(T_term) ) · VD = 2 · K · I · L / CM
Published
Last verified

Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 1560 calculators remain free
  • No billing is enabled
Coming soon