Audited ·Last updated 31 Jul 2026·6 citations·Tier 1·0 uses

Watts to Amps Calculator — Current Drawn by a Load on DC, Single-Phase and Three-Phase Supplies

Convert watts to amps at any voltage on DC, single-phase or three-phase AC, with power factor. Solves back to watts or volts and shows the apparent power.

Watts to Amps Calculator

Supply type
Solve for
The load's real power in watts — the figure on its nameplate or label. Used by the Amps and Volts modes.
W
In three-phase mode this must be the line-to-line voltage (208 V, 400 V, 415 V, 480 V), not the line-to-neutral value. Used by the Amps and Watts modes.
V
Current in amperes. Used by the Watts and Volts modes.
A
A decimal between 0 and 1. Use 1 for resistive loads (heaters, kettles, incandescent lamps). Motors and drives are lower — read it off the nameplate. Ignored on DC.
Current drawn
12.5
The steady-state rms current the load draws, in amperes: I = P ÷ (k × V × PF), with k = 1 on DC and single phase and k = √3 on balanced three phase.
Current (mA)
12,500 mA
Real power
1,500 W
Real power (kW)
1.5 kW
Supply voltage
120 V
Apparent power
1,500 VA
Power factor applied
1
Reading and scope
On a single-phase AC supply, I = P ⁄ (V × PF) = 1500 W ⁄ (120 V × 1) = 12.5 A. That is 1500 W (1.5 kW) of real power drawn as 12.5 A at 120 V, with an apparent power of 1500 VA. At a power factor of 1 the load is purely resistive — a heater, an incandescent lamp, a kettle — so its volt-amperes equal its watts. This is a steady-state figure for a balanced, sinusoidal supply. Motor starting inrush and switch-on surge are several times this current and are a separate calculation. Harmonic-rich loads — variable-frequency drives, switch-mode power supplies, LED drivers — draw more current than this predicts. It is also not a code-compliance calculation. Conductor ampacity, overcurrent-device rating, continuous-load derating, ambient-temperature correction and voltage-drop limits are governed by the electrical code adopted in your jurisdiction, and local amendments vary. A licensed electrician must size and sign off the circuit before any work proceeds — no ampacity or breaker table is asserted here.

Background.

Watts tell you how much work a device does. Amps tell you how hard the wiring has to work to deliver it. Converting between the two takes one more piece of information — the voltage — and, on an AC supply, one more still: the power factor. This calculator handles all three supply types you are likely to meet, and runs the relation in whichever direction you need.

On a DC circuit the arithmetic is as simple as it looks. Power is the product of voltage and current, P = IV, so the current is I = P ÷ V. A 60 W bulb on a 12 V system draws 5 A; a 0.5 W standby load on USB's 5 V draws 100 mA. Nothing else enters into it, because a DC supply has no phase angle and every volt-ampere the supply delivers arrives as a watt.

AC is where people get caught out. The voltage and the current both alternate, and in anything containing a coil or a capacitor they do not peak at the same instant. The cosine of the angle between them is the power factor, and the real power is P = V × I × PF. Turn that around and the current is I = P ÷ (V × PF) — which means a load with a power factor of 0.8 draws a quarter more current than its wattage alone suggests. That extra current is real. It heats the conductors, it counts against the breaker, and it is the reason motors and drives need bigger supply cable than a heater of the same wattage. Purely resistive loads — heaters, kettles, toasters, incandescent lamps — have a power factor of 1, so for those the AC calculation collapses back to the DC one.

Three-phase supplies add a factor of √3. Each phase carries current at the phase voltage, but three-phase equipment is labelled with the voltage measured between two lines, which in a balanced system is √3 times the phase voltage. The result is I = P ÷ (√3 × V × PF), the form the US Department of Energy publishes in its motor load fact sheet as Equation 1, where it defines the voltage explicitly as "RMS voltage, mean line-to-line of 3 phases". That definition is worth reading twice. On a 480Y/277 V system the line-to-line voltage is 480, not 277; on a 400Y/230 V system it is 400, not 230. Entering the line-to-neutral figure instead inflates the calculated current by 73 percent, which is the single most common error in this calculation.

The calculator also reports the apparent power in volt-amperes alongside the current, because that is the number transformers, generators and UPS units are rated in. At a power factor of 1 the two are numerically identical; below 1 the volt-amperes exceed the watts, and the gap is exactly what a kVA rating exists to describe.

Two limits matter before you act on a number. First, everything here is a steady-state figure. A motor's starting inrush can be five or more times its running current for a fraction of a second, and switch-mode supplies draw a brief charging surge at switch-on; neither is captured by a wattage-to-current conversion, and both matter when sizing a generator or a protective device. Second, loads with distorted current waveforms — variable-frequency drives, LED drivers, computer power supplies — draw more current than the fundamental-frequency arithmetic predicts, because the harmonic content adds to the rms total without adding to the watts.

Finally, and this is on the page next to the result rather than buried in an FAQ: this is physics, not compliance. Conductor ampacity, overcurrent-device rating, continuous-load derating, ambient-temperature correction, conduit fill and voltage-drop limits are all governed by the electrical code adopted in your jurisdiction, and local amendments change the answer. Use this page to understand the load and to sanity-check a design, then have a licensed electrician size and sign off the circuit before anything is installed.

What is watts to amps calculator?

A watts-to-amps conversion is the rearrangement of the electrical power equation to solve for current. Power, measured in watts, is the rate at which a device converts electrical energy into something useful. Current, measured in amperes, is the rate at which charge flows through the conductors feeding it. They are linked by the voltage, and on AC by the power factor as well.

The three forms are: I = P ÷ V for direct current, I = P ÷ (V × PF) for single-phase alternating current, and I = P ÷ (√3 × V × PF) for a balanced three-phase supply where V is the line-to-line voltage. The √3 is not a correction factor invented for three-phase work — it is the ratio between line-to-line and line-to-neutral voltage in a balanced system, and it appears because three-phase equipment is labelled with the former.

The distinction between watts and volt-amperes matters more the further the power factor falls below 1. Watts measure the energy actually converted; volt-amperes measure the product of voltage and current the supply must deliver. Conductors heat according to current, not according to watts, so a 1000 W load at a power factor of 0.5 stresses the wiring exactly as hard as a 2000 W resistive load would. That is why supply equipment is rated in kVA and why the power factor is not an optional refinement on an AC calculation.

How to use this calculator.

  1. Choose the supply type: single-phase AC for ordinary mains, three-phase AC for industrial and commercial supplies, or DC for battery, solar and USB systems.
  2. Choose what you are solving for — amps from watts and volts, watts from amps and volts, or volts from watts and amps.
  3. Enter the load's power in watts, taken from its nameplate or label rather than estimated.
  4. Enter the supply voltage. On three phase this must be the line-to-line value: 208, 400, 415 or 480 V on common systems, never the 120 V or 230 V measured to neutral.
  5. Enter the power factor as a decimal. Use 1 for heaters, kettles and incandescent lamps; take the nameplate figure for motors and drives. On DC the field is ignored.
  6. Read the current as the headline, and check the apparent power in volt-amperes if you are sizing a generator, transformer or UPS.
  7. Add headroom for motor starting inrush and for harmonic-rich loads, then have a licensed electrician confirm conductor and overcurrent sizing against the code adopted where you are.

The formula.

DC: I = P ⁄ V 1-phase AC: I = P ⁄ (V × PF) 3-phase AC: I = P ⁄ (√3 × V_LL × PF) S = P ⁄ PF

The direct-current case is the base everything else is built on. OpenStax University Physics Volume 2, section 9.5, gives it as Equation 9.12: "P = IV". Dividing both sides by V gives I = P ÷ V. Because a DC supply has no phase angle, there is nothing else to account for; the calculator forces the power factor to 1 in DC mode and ignores whatever is in the field.

On alternating current the same product holds, but between root-mean-square quantities and with the phase angle carried explicitly. Section 15.4 of the same book gives Equation 15.12 as "Pave = (1/2)I₀V₀cos(ϕ)" and Equation 15.13 as "Pave = (1/2)I₀V₀ = IrmsVrms = Irms²R", and defines the rms values as "Irms = (1/√2)I₀ and Vrms = (1/√2)V₀". The section names the factor directly: "In engineering applications, cos(ϕ) is known as the power factor, which is the amount by which the power delivered in the circuit is less than the theoretical maximum of the circuit due to voltage and current being out of phase." Putting those together, P = V_rms × I_rms × PF, so I = P ÷ (V × PF).

For a balanced three-phase supply the US Department of Energy publishes the relation directly. Fact sheet DOE/GO-10097-517, Determining Electric Motor Load and Efficiency, gives Equation 1 as "Pi = V x I x PF x √3 / 1000", with V defined as "RMS voltage, mean line-to-line of 3 phases", I as "RMS current, mean of 3 phases" and PF as "Power factor as a decimal". Rearranged for current, I = P ÷ (√3 × V × PF). The √3 arises because each phase delivers V_phase × I_line, giving 3 × V_phase × I_line in total, and substituting V_phase = V_line-to-line ÷ √3 turns the 3 into a √3.

This calculator carries √3 as 1.7320508075688772935… at forty significant digits and rounds only once, at the very end. The difference is measurable: the DOE fact sheet's own worked example measures a 40-hp motor at 469.7 V, 37 A and power factor 0.763 and prints 22.9 kW, whereas the exact √3 gives 22.9671681259 kW. Substituting the schoolbook √3 ≈ 1.73 reproduces the printed figure at 22.94 kW, so the gap is the source's 1997 hand-calculation rounding rather than a disagreement about the physics. Both values are recorded in the citation below, this page uses the exact one, and a test asserts 22.9671681259 while explicitly rejecting 22.94. Run the other way — the direction this page is actually used in — 22 967.1681259 W at 469.7 V and power factor 0.763 returns exactly 37 A, closing the loop on the source's own measurement.

The apparent power reported alongside the current is S = k × V × I, which is algebraically identical to P ÷ PF. It is the quantity transformers, generators and UPS units are rated in, and it exceeds the watts by exactly the reciprocal of the power factor. Every mode on the page is a closed-form rearrangement of the same single relation; nothing is solved numerically and nothing is approximated.

A worked example.

Example

A 1500 W portable space heater is plugged into a 120 V single-phase outlet. A heating element is essentially a resistor, so the current and voltage stay in step and the power factor is 1. The current is I = 1500 ÷ (120 × 1) = 12.5 A exactly, which the calculator also reports as 12500 mA. The real power is 1500 W, or 1.5 kW, meaning the heater consumes 1.5 kilowatt-hours for every hour it runs. Because the power factor is 1, the apparent power is the same number in different units: 120 V × 12.5 A = 1500 VA. Now change one thing. Suppose the same 1500 W of real power were drawn by a motor with a power factor of 0.8 instead. The current becomes 1500 ÷ (120 × 0.8) = 15.625 A — exactly 1.25 times higher, because 1 ÷ 0.8 = 1.25 — and the apparent power rises to 1875 VA even though the useful work is unchanged at 1500 W. The wiring feels the 15.625 A, not the 1500 W, which is the whole reason power factor belongs in this calculation. Third variation, on a three-phase supply: 3000 W at 400 V line-to-line with a power factor of 0.9 gives I = 3000 ÷ (1.7320508076 × 400 × 0.9) = 4.8112522432 A per line. Had the 400 V been entered as the 230 V line-to-neutral figure instead, the answer would have come out 73 percent too high. In all three cases the number is the steady-state current only: the heater draws 12.5 A from the moment it is switched on, but the motor's starting inrush is several times its 15.625 A running current for a fraction of a second, and that is what a protective device has to ride through. Use these figures to understand the load; have a licensed electrician size the conductor and the overcurrent device against the code adopted in your jurisdiction.

volts120
amps12.5
systemacSingle
watts1,500
solve Foramps
power Factor1

Frequently asked questions.

How many amps does a 1500 W heater draw?
On a 120 V single-phase circuit, 12.5 A: I = 1500 ÷ 120 = 12.5. On a 230 V or 240 V supply the same heater draws about half that — 1500 ÷ 240 = 6.25 A — which is why the same appliance needs a heavier cable in a 120 V country than in a 230 V one. A resistive heating element has a power factor of 1, so no correction is needed. Whether a given circuit can carry that current continuously is a code question about conductor ampacity and overcurrent-device rating, not an arithmetic one; ask a licensed electrician.
What is the formula to convert watts to amps?
It depends on the supply. On DC, amps = watts ÷ volts. On single-phase AC, amps = watts ÷ (volts × power factor). On balanced three-phase AC, amps = watts ÷ (√3 × line-to-line volts × power factor), with √3 = 1.7320508076. The power factor is 1 for purely resistive loads, so for a heater or an incandescent lamp the AC formula reduces to the DC one.
Why do I need the power factor, and what if I do not know it?
Because on AC the current and voltage can be out of step, and the current is set by the volt-amperes the supply delivers rather than by the watts the load converts. Leaving the power factor out understates the current by a factor of 1 ÷ PF — a quarter too low at PF 0.8, a third too low at PF 0.75. Find the real figure rather than guessing: motor, drive, UPS and generator nameplates all carry it. If you genuinely cannot get one, run the calculation at two plausible values and see whether the difference changes any decision you are about to make. Resistive loads are the safe case at exactly 1.
Which voltage do I enter for a three-phase supply?
The line-to-line voltage, without exception. On a 480Y/277 V system enter 480; on 400Y/230 V enter 400; on 208Y/120 V enter 208. The US Department of Energy fact sheet this page's formula comes from defines the term explicitly as "RMS voltage, mean line-to-line of 3 phases". Entering the line-to-neutral value instead inflates the calculated current by a factor of √3, about 73 percent, which is enough to specify wildly oversized cable or to make a healthy load look like an overload.
Is watts to amps the same as watts to volt-amperes?
No, and the calculator shows both. Watts are real power — energy actually converted into heat, light or motion. Volt-amperes are apparent power, the product of the voltage and the current the supply has to deliver, which is what cables, breakers, transformers, generators and UPS units are sized against. They are related by S = P ÷ PF, so they are numerically equal only when the power factor is 1. A 1000 W load at power factor 0.5 presents 2000 VA to the supply and draws the current of a 2000 W resistive load.
Does this work for 12 V DC and solar or battery systems?
Yes — choose the DC supply type, which forces the power factor to 1 and ignores that field entirely. A 100 W device on a 12 V battery draws 100 ÷ 12 = 8.33 A; the same device behind a 24 V bank draws 4.17 A. This is the reason low-voltage DC runs need such heavy cable: halve the voltage and you double the current for identical work, and the voltage drop along the run grows with it. If you are sizing the cable itself, the current here is the input to that calculation, not the answer to it.
Does the answer include motor starting inrush?
No. Everything on this page is a steady-state root-mean-square figure. An induction motor's locked-rotor or starting current is commonly several times its running current for a fraction of a second, and switch-mode power supplies draw a brief charging surge at the moment they are energised. Neither is derivable from a wattage figure. Inrush is what determines whether a generator can start a load and which overcurrent-device characteristic is appropriate, and it has to come from the equipment's own data, not from a conversion.
Can I use this current to pick a breaker or a cable size?
Not on its own. This page gives the current the load draws, which is one input to that decision. Conductor ampacity, overcurrent-device rating, continuous-load derating, ambient-temperature and grouping corrections, conduit fill and voltage-drop limits are governed by the electrical code adopted in your jurisdiction, and local amendments change the answer. Adopted code editions differ between jurisdictions too, so a rule of thumb from one country can be wrong in another. Treat this as physics and a sanity check, and have a licensed electrician size and sign off the circuit before anything is installed.

References& sources.

  1. [1]OpenStax (Rice University), University Physics Volume 2, §9.5 "Electrical Energy and Power". Primary source for the DC form. Equation 9.12 gives "P = IV" and Equation 9.13 gives "P = I²R = V²/R"; the section states "The energy unit on electric bills is the kilowatt-hour (kW·h), consistent with the relationship E = Pt" and "1 kW·h = 3.6 × 10⁶ J". Access: open. Retrieved 2026-07-29.
  2. [2]OpenStax (Rice University), University Physics Volume 2, §15.4 "Power in an AC Circuit". Primary source for the AC form and the power factor. Equation 15.12 gives "Pave = (1/2)I₀V₀cos(ϕ)"; Equation 15.13 gives "Pave = (1/2)I₀V₀ = IrmsVrms = Irms²R"; the rms values are defined as "Irms = (1/√2)I₀ and Vrms = (1/√2)V₀"; and the section states "In engineering applications, cos(ϕ) is known as the power factor, which is the amount by which the power delivered in the circuit is less than the theoretical maximum of the circuit due to voltage and current being out of phase", plus "For a resistor, ϕ = 0". Access: open. Retrieved 2026-07-29.
  3. [3]US Department of Energy, Office of Energy Efficiency and Renewable Energy, fact sheet DOE/GO-10097-517, "Determining Electric Motor Load and Efficiency", January 1997 (OSTI report numbers DOE/GO--10097-517; 319). Primary source for the three-phase form. Equation 1 reads "Pi = V x I x PF x √3 / 1000" with "V = RMS voltage, mean line-to-line of 3 phases", "I = RMS current, mean of 3 phases" and "PF = Power factor as a decimal". RECORDED CONFLICT: the same document's worked example prints "469.7 x 37 x 0.763 x √3 / 1000 = 22.9 kW", while the exact √3 gives 22.9671681259 kW; the printed figure is reproduced by √3 ≈ 1.73, which yields 22.94 kW. This page uses the exact √3, a test asserts 22.9671681259 and explicitly rejects 22.94, and the inverse returns the source's own 37 A exactly. Access: open. Retrieved and text-verified 2026-07-29.
  4. [4]International Electrotechnical Commission, IEC 60050 International Electrotechnical Vocabulary, part 131, entry 131-11-41 "apparent power". Cited by IEV reference number for the standardised definition of apparent power and its unit, the volt-ampere. ACCESS: GATED — electropedia.org returned HTTP 403 to the retrieval used for this page, so nothing is quoted from the entry and no figure on this page rests on it. Declared as unopened rather than presented as verified. Retrieval attempted 2026-07-29.
  5. [5]NIST, Special Publication 811, "Guide for the Use of the International System of Units (SI)", 2008 edition (DOI 10.6028/NIST.SP.811e2008). Used only for unit symbols and typography — W, V, A, VA, mA — not for any electrical relation. NIST's own landing page notes that SP 811 "has not yet been updated to reflect the changes in the SI that came into effect on May 20, 2019"; none of those changes affect the symbols used here. Access: open. Retrieved 2026-07-29.
  6. [6]OpenStax (Rice University), University Physics Volume 2, §15.2 "Simple AC Circuits", consulted as a secondary check on the phase relationships behind the power factor — the resistor's zero phase angle, and the ±90° angles of the inductor and capacitor that make a real load's power factor less than 1. Access: open. Retrieved 2026-07-29.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 977 calculators remain free
  • No billing is enabled
Coming soon