Audited 31 Jul 2026·Last updated 28 Oct 2026·5 citations·Tier 2·0 uses

kVA Calculator — Apparent Power from Volts and Amps, kW, or a Nameplate Rating

Work out kVA from volts and amps, the kVA a kW load needs at a given power factor, or the line current a kVA rating allows, on single or three phase.

kVA Calculator

Supply type
Solve for
In three-phase mode this must be the line-to-line voltage (e.g. 400 V, 415 V, 480 V), not line-to-neutral. Used by every mode except Volts.
V
Current in one line conductor, in amperes. Used by the kVA and Volts modes.
A
The kVA number on the transformer, generator or UPS nameplate. Used by the Amps and Volts modes.
kVA
The working power the load actually consumes. Used only by the 'kVA from a kW load' mode.
kW
A decimal between 0 and 1. Use 1 for a purely resistive load such as a heater; motors and drives are lower. Read it off the nameplate where you can.
Apparent power
83.1384
Apparent power S in kilovolt-amperes: the load the supply, transformer or generator has to carry, whatever share of it does work.
Apparent power (VA)
83,138.4388 VA
Line current
100 A
Line voltage
480 V
Real power
70.6677 kW
Reactive power
43.7959 kvar
Power factor applied
0.85
Reading and scope
On a three-phase supply, S = √3 × V × I = 1.7320508076 × 480 V × 100 A = 83138.44 VA = 83.1384 kVA of apparent power. At a power factor of 0.85 that is 70.6677 kW of real power and 43.7959 kvar of reactive power. The 480 V figure must be the LINE-TO-LINE voltage — the DOE fact sheet this page's √3 comes from specifies "RMS voltage, mean line-to-line of 3 phases". Using the line-to-neutral voltage instead understates the answer by a factor of √3 and is the single most common error in this calculation. The result assumes a balanced, sinusoidal, steady-state supply. Harmonics and unbalance — variable-frequency drives, switch-mode supplies, LED drivers — push the true apparent power above what √3 × V × I predicts. The reactive power is reported as a magnitude, because a single power-factor number does not say whether the load is lagging (inductive) or leading (capacitive). This is an electrical identity, not a code-compliance calculation. Conductor ampacity, overcurrent protection, continuous-load derating and transformer sizing margins are governed by the electrical code adopted in your jurisdiction, and local amendments vary — a licensed electrician or engineer must sign off before any work proceeds. Size real equipment by rounding up to the next standard kVA rating on the manufacturer's own list, with whatever margin your application needs.

Background.

How many amps can a 500 kVA transformer deliver on a 415 V three-phase supply? About 695.6 A per line. How large a generator does 100 kW of load need if its power factor is 0.8? At least 125 kVA. Both answers come out of one relation between voltage, current and apparent power, and both go wrong in the same two ways: dropping the √3 that a three-phase supply carries, or treating kVA and kW as interchangeable.

Real power, in kW, is the share of apparent power that leaves as shaft work, heat or light, and the ratio of the two is the power factor. A motor whose current runs partly out of step with the voltage still loads its supply with every ampere it draws, which is why transformers, generators and UPS units carry kVA ratings. At a power factor of 0.8, each kW of load needs 1.25 kVA of supply, so equipment sized on kW alone comes up 20 percent short.

On three phase, the V in S = √3 × V × I is the voltage between two lines. Type the line-to-neutral figure instead and the answer shrinks by a factor of √3: the 480 V, 100 A feeder in the worked example carries 83.1384 kVA, but entered as 277 V it reports 47.9778 kVA, an undersize of more than 40 percent.

The relations assume a balanced, sinusoidal, steady supply. Variable-speed drives, switch-mode power supplies and LED drivers draw distorted current, so √3 × V × I worked from a fundamental-frequency current reading understates their apparent power, and an unbalanced three-phase load has to be worked phase by phase. This is the physics, not a wiring-code calculation: cable ampacity, breaker sizing and derating follow the electrical rules adopted where you are, and a licensed electrician or engineer has to approve real work.

What is kva calculator?

Apparent power, S, is the product of the rms voltage and the rms current, measured in volt-amperes; divide by 1,000 for kVA. On an AC circuit it splits into two parts at right angles: real power P, in kilowatts, which is consumed, and reactive power Q, in kilovars, which is stored in magnetic or electric fields and handed back to the supply every cycle. They form the power triangle, S² = P² + Q², and the power factor is P ÷ S, the cosine of the angle between voltage and current for a sinusoidal supply. On a balanced three-phase supply each phase carries the phase voltage times the line current, and because the line-to-line voltage is √3 times the phase voltage, the total 3 × V_phase × I becomes √3 × V_line × I.

How to use this calculator.

  1. Choose single phase or three phase. In three-phase mode the voltage must be the line-to-line value, for example 208, 400, 415 or 480 V, not the 120, 230 or 277 V measured to neutral.
  2. Choose what to solve for: kVA from measured volts and amps, kVA from a kW load and its power factor (sizing a generator or UPS), amps from a kVA rating, or volts from a rating and a current. Fields the chosen mode does not use are ignored.
  3. Enter the power factor as a decimal (0.85, not 85), from the motor, drive or UPS nameplate where you can; use 1 only for resistive loads such as heaters. It does not change kVA worked out from volts and amps, but it sets the kW and kvar beside it, and in the kW mode it sets the answer.
  4. Round the kVA up to the next rating the manufacturer actually sells, add the margin your application needs, and have conductor and protection sizes checked against your local wiring rules.

The formula.

single phase: S = V × I three phase: S = √3 × V_LL × I P = S × PF Q = S × √(1 − PF²)

Single phase: S = V × I. Balanced three phase: S = √3 × V_LL × I, with V_LL the line-to-line voltage and I the current in one line. Real power is P = S × PF and reactive power is Q = S × √(1 − PF²), which follows from the power triangle without ever needing the phase angle itself. Every mode is the same identity rearranged, with k = 1 for single phase and √3 for three phase: I = S ÷ (k × V), V = S ÷ (k × I) and S = P ÷ PF. The √3 is not a correction factor but bookkeeping: three phases each carrying V_LL ÷ √3 sum to 3 ÷ √3 = √3 times V_LL × I. The calculator uses its exact value, 1.7320508…, rather than 1.73. Reactive power is reported as a magnitude because a single power-factor number cannot say whether the current lags the voltage, as in motors and transformers, or leads it, as with capacitor banks. Of all the inputs, the voltage reference is the one most often wrong: the line-to-neutral value in three-phase mode returns only 57.7 percent of the true kVA.

A worked example.

Example

A 480 V three-phase feeder is measured at 100 A per line, supplying motors whose nameplate power factor is 0.85. Apparent power is √3 × 480 × 100 = 1.7320508 × 48,000 = 83,138.4388 VA, or 83.1384 kVA. That is the figure the transformer, switchgear and cable must be rated to carry. Real power is 83.1384 × 0.85 = 70.6677 kW, the part the motors turn into shaft work and losses. For the reactive part, √(1 − 0.85²) = √0.2775 = 0.5268, and 83.1384 × 0.5268 = 43.7959 kvar circulating between the supply and the motor windings. The triangle closes: 70.6677² + 43.7959² = 4,993.92 + 1,918.08 = 6,912, which is 83.1384². Run in reverse, an 83.1384 kVA rating at 480 V three-phase corresponds to exactly 100 A per line.

phasethree
volts480
amps100
kva83.138
kw70.668
solve Forkva
power Factor0.85

Frequently asked questions.

How many amps can a 500 kVA transformer supply?
It depends on the voltage and the number of phases. On three phase, I = kVA × 1,000 ÷ (√3 × V), so 500 kVA is 695.6 A per line at 415 V, 721.7 A at 400 V and 601.4 A at 480 V. The power factor plays no part: the rating limits current, whatever the load does with it.
What size generator does a 100 kW load need?
Divide by the load's power factor. At 0.8, 100 kW needs 125 kVA, which on a 400 V three-phase supply is 180.4 A per line. That covers running load only; motor starting currents can be several times running current and need their own check, which a generator sizing calculator handles.
Why are transformers and generators rated in kVA and not kW?
Because the manufacturer cannot know the power factor of whatever you connect, and the limits that matter, winding temperature and insulation stress, depend on current and voltage alone. A kVA rating holds for any load; a kW figure would hold only at the one power factor it assumed.
I only have a line-to-neutral voltage. What do I enter on three phase?
On a balanced wye system, multiply it by √3 to get the line-to-line value: 230 V to neutral is about 400 V between lines and 277 V is about 480 V. The US Department of Energy motor fact sheet behind the three-phase formula defines V as the mean line-to-line rms voltage.
Does it matter if I round √3 to 1.73?
Only slightly: 1.73 is 0.12 percent low. The Department of Energy fact sheet's own example shows the effect, printing 22.9 kW for 469.7 V, 37 A and a power factor of 0.763, a figure 1.73 reproduces at 22.94 kW, while the exact √3 gives 22.9672 kW. For sizing equipment the difference is negligible.
What power factor should I use for a mix of loads?
Read each item's power factor from its nameplate and work out its kVA separately. Adding those kVA figures gives a conservative total, because loads at different power factors do not add exactly. Induction motors run at a lower power factor when lightly loaded, so a nameplate value is a best case for a motor that idles.

References& sources.

  1. [1]US Department of Energy, Office of Energy Efficiency and Renewable Energy, fact sheet DOE/GO-10097-517, "Determining Electric Motor Load and Efficiency", January 1997 (OSTI report numbers DOE/GO--10097-517; 319). Primary source for the three-phase relation. Equation 1 reads "Pi = V x I x PF x √3 / 1000", with "Pi = Three-phase power in kW", "V = RMS voltage, mean line-to-line of 3 phases", "I = RMS current, mean of 3 phases", "PF = Power factor as a decimal". Setting PF = 1 isolates the apparent power. RECORDED CONFLICT: the same document's worked example prints "469.7 x 37 x 0.763 x √3 / 1000 = 22.9 kW", while the exact √3 gives 22.9671681259 kW; the printed figure is reproduced by √3 ≈ 1.73, which yields 22.94 kW. This page uses the exact √3, giving 22.9671681259 rather than 22.94. Retrieved and text-verified 2026-07-29.
  2. [2]OpenStax (Rice University), University Physics Volume 2, §15.4 "Power in an AC Circuit". Primary source for the power factor and the rms voltage-current product. Equation 15.12 gives "Pave = (1/2)I₀V₀cos(ϕ)" and Equation 15.13 gives "Pave = (1/2)I₀V₀ = IrmsVrms = Irms²R"; the section states "In engineering applications, cos(ϕ) is known as the power factor, which is the amount by which the power delivered in the circuit is less than the theoretical maximum of the circuit due to voltage and current being out of phase", and defines the rms values as "Irms = (1/√2)I₀ and Vrms = (1/√2)V₀". Retrieved 2026-07-29.
  3. [3]OpenStax (Rice University), University Physics Volume 2, §9.5 "Electrical Energy and Power". Secondary check on the DC power identities underlying the AC forms: Equation 9.12 "P = IV" and Equation 9.13 "P = I²R = V²/R", plus "The energy unit on electric bills is the kilowatt-hour (kW·h), consistent with the relationship E = Pt" and "1 kW·h = 3.6 × 10⁶ J". Retrieved 2026-07-29.
  4. [4]International Electrotechnical Commission, IEC 60050 International Electrotechnical Vocabulary, part 131, entry 131-11-41 "apparent power". Cited by IEV reference number for the standardised definition of the term and its unit, the volt-ampere. ACCESS: GATED — electropedia.org returned HTTP 403 to the retrieval used for this page, so nothing is quoted from the entry and no figure on this page rests on it. Declared as unopened rather than presented as verified. Retrieval attempted 2026-07-29.
  5. [5]NIST, Special Publication 811, "Guide for the Use of the International System of Units (SI)", 2008 edition (DOI 10.6028/NIST.SP.811e2008). Used only for unit symbols and typography — V, A, W, VA — not for any electrical relation. NIST's own landing page notes that SP 811 "has not yet been updated to reflect the changes in the SI that came into effect on May 20, 2019"; none of those changes affect the symbols used here. Retrieved 2026-07-29.

How this page was produced

Published by
Quanta Calculator
Primary sources
5 cited below
Method
single phase: S = V × I three phase: S = √3 × V_LL × I P = S × PF Q = S × √(1 − PF²)
Published
Last verified

Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 1560 calculators remain free
  • No billing is enabled
Coming soon