Audited ·Last updated 31 Jul 2026·5 citations·Tier 2·0 uses

kVA Calculator — Apparent Power from Volts and Amps, kW, or a Nameplate Rating

Find kVA from volts and amps, size a transformer or generator from a kW load and power factor, or convert a kVA rating back to amps. Single and three phase.

kVA Calculator

Supply type
Solve for
In three-phase mode this must be the line-to-line voltage (e.g. 400 V, 415 V, 480 V), not line-to-neutral. Used by every mode except Volts.
V
Current in one line conductor, in amperes. Used by the kVA and Volts modes.
A
The kVA number on the transformer, generator or UPS nameplate. Used by the Amps and Volts modes.
kVA
The working power the load actually consumes. Used only by the 'kVA from a kW load' mode.
kW
A decimal between 0 and 1. Use 1 for a purely resistive load such as a heater; motors and drives are lower. Read it off the nameplate where you can.
Apparent power
83.1384
Apparent power S in kilovolt-amperes — the total the supply, transformer or generator must actually carry, regardless of how much of it does useful work.
Apparent power (VA)
83,138.4388 VA
Line current
100 A
Line voltage
480 V
Real power
70.6677 kW
Reactive power
43.7959 kvar
Power factor applied
0.85
Reading and scope
On a three-phase supply, S = √3 × V × I = 1.7320508076 × 480 V × 100 A = 83138.44 VA = 83.1384 kVA of apparent power. At a power factor of 0.85 that is 70.6677 kW of real power and 43.7959 kvar of reactive power. The 480 V figure must be the LINE-TO-LINE voltage — the DOE fact sheet this page's √3 comes from specifies "RMS voltage, mean line-to-line of 3 phases". Using the line-to-neutral voltage instead understates the answer by a factor of √3 and is the single most common error in this calculation. The result assumes a balanced, sinusoidal, steady-state supply. Harmonics and unbalance — variable-frequency drives, switch-mode supplies, LED drivers — push the true apparent power above what √3 × V × I predicts. The reactive power is reported as a magnitude, because a single power-factor number does not say whether the load is lagging (inductive) or leading (capacitive). This is an electrical identity, not a code-compliance calculation. Conductor ampacity, overcurrent protection, continuous-load derating and transformer sizing margins are governed by the electrical code adopted in your jurisdiction, and local amendments vary — a licensed electrician or engineer must sign off before any work proceeds. Size real equipment by rounding up to the next standard kVA rating on the manufacturer's own list, with whatever margin your application needs.

Background.

kVA is the size of an electrical supply. kW is how much of it does work. The gap between them is why a 100 kW load will not run on a 100 kVA generator, and why the transformer feeding your workshop is rated in a unit most people never meet anywhere else. This calculator moves between the two in every direction, on single-phase and balanced three-phase supplies.

Apparent power, written S and measured in volt-amperes, is simply the product of the voltage and the current the supply has to deliver: S = V × I on a single-phase circuit, and S = √3 × V × I on a balanced three-phase one, where V is the line-to-line voltage. Nothing about the load's behaviour enters that product. Conductors heat up according to the current they carry and insulation is stressed by the voltage across it, so the volt-ampere product is what actually determines the size of every piece of equipment in the path — the cable, the switchgear, the transformer, the generator, the UPS. That is why they are all sold in kVA.

Real power, written P and measured in watts, is the part of that apparent power that leaves the circuit as motion, heat or light. On an AC supply the voltage and current do not necessarily peak at the same instant; the cosine of the angle between them is the power factor, and P = S × PF. A resistive load such as an immersion heater has a power factor of 1 and consumes every volt-ampere it draws. An induction motor at 0.8 lagging draws 25 percent more current than its wattage suggests, because a quarter of the apparent power is spent building and collapsing magnetic fields rather than turning the shaft. That circulating component is reactive power, Q, measured in kilovars, and it is the third side of a right triangle whose other two sides are P and S.

The practical consequences show up the moment you size something. Convert a kW load to kVA by dividing by the power factor, never by assuming they are the same. Convert a kVA rating to amps to check it against the cable and the protective device. Convert measured volts and amps to kVA to see how much headroom a transformer has left. All four of those moves are on this page, as a dropdown, along with the kW and kvar that accompany each answer.

Two warnings worth reading before you trust a number. In three-phase mode the voltage must be the line-to-line value — the source this page's √3 comes from specifies "RMS voltage, mean line-to-line of 3 phases", and quietly using line-to-neutral instead is the most common way this calculation goes wrong, by a factor of 1.73. And the whole model assumes a balanced, sinusoidal, steady-state supply. Variable-frequency drives, switch-mode power supplies and LED drivers draw distorted current whose true apparent power is higher than √3 × V × I predicts, and an unbalanced three-phase load is not described by a single line current at all.

Finally, this is an electrical identity, not a code compliance calculation. Conductor ampacity, overcurrent protection, continuous-load derating and transformer sizing margins are governed by the electrical code adopted where you are, and local amendments vary. Use the number here to understand the physics and to sanity-check a quote; have a licensed electrician or engineer sign off before any work proceeds.

What is kva calculator?

kVA stands for kilovolt-ampere, a unit of apparent power — the product of the root-mean-square voltage across a circuit and the root-mean-square current through it, divided by a thousand. It measures the total electrical burden a supply has to carry, without regard to how much of that burden ends up doing useful work.

Apparent power exists as a separate quantity because AC voltage and current are not necessarily in step. In a purely resistive circuit they rise and fall together and every volt-ampere becomes a watt. Add inductance — a motor winding, a transformer core, a fluorescent ballast — and the current lags the voltage, so part of the energy flowing into the load each cycle flows straight back out again. That returned energy still had to travel down the cable and through the transformer, still heated the conductors on the way, and still counts against the equipment's rating, but it never turned into anything. Apparent power counts it. Real power does not.

The three quantities form the power triangle: S² = P² + Q², where S is apparent power in kVA, P is real power in kW, and Q is reactive power in kvar. The power factor is the ratio P ÷ S, which is also the cosine of the phase angle between voltage and current. On a single-phase supply S = V × I. On a balanced three-phase supply each phase carries V_phase × I_line, and because the line-to-line voltage is √3 times the phase voltage, the total works out to S = √3 × V_line-to-line × I_line — the origin of the √3 that appears in every three-phase formula.

How to use this calculator.

  1. Choose the supply type. Three phase applies the √3 factor and expects the line-to-line voltage; single phase does not.
  2. Choose what you want to solve for: kVA from measured volts and amps, kVA from a kW load, amps from a kVA rating, or volts from a kVA rating.
  3. Enter the line voltage. On three phase this is the line-to-line value — 208 V, 400 V, 415 V or 480 V on common systems, not the 120 V or 230 V you measure to neutral.
  4. Enter whichever of current, kVA rating or kW load your chosen mode asks for. Fields the mode does not read are ignored and can be left at zero.
  5. Enter the power factor as a decimal. Use 1 for a purely resistive load; read it off the nameplate for a motor or a drive. It does not affect the kVA figure computed from volts and amps, but it does set the kW and kvar that go with it.
  6. Read the apparent power in kVA as the headline, then check the line current against your cable and protective device, and the kW against what the load actually needs.
  7. Round up to the next standard rating on the manufacturer's list before ordering anything, and have the installation signed off by a licensed electrician or engineer.

The formula.

single phase: S = V × I three phase: S = √3 × V_LL × I P = S × PF Q = S × √(1 − PF²)

Start with the single-phase case, because the three-phase one is built from it. Apparent power is the plain product of the rms voltage and the rms current: S = V × I. There is no phase angle in that expression, which is exactly the point — it describes what the supply has to carry, not what the load does with it. Real power carries the angle: P = V × I × cos φ, and cos φ is the power factor. OpenStax University Physics Volume 2 gives both forms in section 15.4, as Equation 15.12 for the general case and Equation 15.13 for a resistor, and names the factor: "In engineering applications, cos(ϕ) is known as the power factor." Dividing the general expression by the resistive one isolates V × I as the power-factor-free product, which is apparent power.

On a balanced three-phase supply, each of the three phases delivers V_phase × I_line, so the total is 3 × V_phase × I_line. Three-phase equipment is labelled with the line-to-line voltage rather than the phase voltage, and in a balanced system those differ by √3, so substituting V_phase = V_LL ÷ √3 turns 3 × V_phase × I into √3 × V_LL × I. That is where the √3 comes from — it is a consequence of measuring voltage between lines instead of to neutral, not a fudge factor.

The US Department of Energy states the resulting relation directly. Fact sheet DOE/GO-10097-517, Determining Electric Motor Load and Efficiency, gives Equation 1 as "Pi = V x I x PF x √3 / 1000", with V defined as "RMS voltage, mean line-to-line of 3 phases" and I as "RMS current, mean of 3 phases". Setting PF = 1 in that equation leaves the apparent power in kVA. This page uses the exact √3 = 1.7320508075688772935…, carried at forty significant digits, and rounds once at the very end. That matters more than it looks: the fact sheet's own worked example prints 22.9 kW for 469.7 V, 37 A and PF 0.763, while the exact √3 gives 22.9671681259 kW. Substituting the schoolbook √3 ≈ 1.73 reproduces the printed figure at 22.94 kW, so the difference is the source's hand-calculation rounding rather than a disagreement about physics. Both values are recorded, and a test on this calculator asserts the exact one and explicitly rejects 22.94.

The reactive power follows from the power triangle. If P = S cos φ then Q = S sin φ, and since sin φ = √(1 − cos²φ), the calculator computes Q = S × √(1 − PF²) without ever needing the angle itself. It reports the magnitude only: a single power-factor number does not record whether the current lags the voltage (an inductive load, the usual case) or leads it (a capacitive one), so signing the result would be inventing information the input never carried.

Every mode on the page is a rearrangement of the same identity. Amps from a rating is I = S ÷ (√3 × V). Volts from a rating is V = S ÷ (√3 × I). kVA from a kW load is S = P ÷ PF, and once S is known the current follows from the voltage. Nothing is solved numerically and nothing is approximated; each answer is a closed-form inverse of the one relation.

A worked example.

Example

A 480 V three-phase feeder is measured at 100 A per line, supplying a mixed motor load whose nameplate power factor is 0.85. The apparent power is S = √3 × 480 × 100. Carrying √3 at full precision as 1.7320508075688772935, that is 83138.4387633061 VA, or 83.1384387633 kVA — the figure the transformer, the switchgear and the cable all have to be rated for. The real power is S × 0.85 = 70.6676729488 kW, which is what the motors actually convert into shaft work and heat. The reactive power is S × √(1 − 0.85²) = S × √0.2775 = S × 0.5267826876 = 43.7958902181 kvar, circulating between the supply and the motor windings without doing net work. The three close the power triangle: 70.6676729488² + 43.7958902181² = 83.1384387633², which the calculator's own tests assert. Read the other way round, a 83.1384387633 kVA rating on a 480 V three-phase system corresponds to exactly 100 A per line, and the same rating at 100 A implies exactly 480 V — both round trips are exact. Note what would happen if the 480 V were mistaken for a line-to-neutral figure: the correct line-to-line voltage on such a system is 480 V and the line-to-neutral is 277 V, so entering 277 V would return 47.9778073697 kVA instead of 83.1384387633 kVA — 57.7 percent of the right answer, a 42 percent undersize that would put the transformer into thermal overload. Before ordering anything on the strength of 83.1384387633 kVA, round up to the next standard rating the manufacturer actually sells, add the margin your application needs, and have a licensed electrician or engineer confirm the conductor and overcurrent sizing against the code adopted in your jurisdiction.

phasethree
volts480
amps100
kva83.138
kw70.668
solve Forkva
power Factor0.85

Frequently asked questions.

What is the difference between kVA and kW?
kVA is apparent power, the plain product of volts and amps that the supply has to carry. kW is real power, the part of it that becomes motion, heat or light. They are linked by the power factor: kW = kVA × PF. For a purely resistive load such as a heater the power factor is 1 and the two are numerically equal. For a motor at 0.8 lagging, a 100 kVA supply delivers only 80 kW of useful work, and the remaining apparent power is spent building and collapsing magnetic fields. This is why generators and UPS units are rated in kVA and why sizing one against a kW figure without dividing by the power factor undersizes it.
How do I convert kVA to amps?
Set the mode to "Amps — from a kVA rating" and enter the line voltage. On a single-phase supply the amps are I = kVA × 1000 ÷ V. On a balanced three-phase supply they are I = kVA × 1000 ÷ (√3 × V), with V the line-to-line voltage. Worked through: 83.1384387633 kVA on a 480 V three-phase system is 83138.4387633061 ÷ (1.7320508076 × 480) = 100 A per line. The power factor plays no part in this conversion — that is the whole reason apparent power exists as a separate quantity.
Why is there a √3 in the three-phase formula?
Because three-phase equipment is labelled with the voltage between two lines, not the voltage from a line to neutral. Each phase of a balanced load carries V_phase × I_line, so the total apparent power is 3 × V_phase × I_line. In a balanced system the line-to-line voltage is √3 times the phase voltage, so substituting V_phase = V_LL ÷ √3 gives 3 ÷ √3 = √3, and the total becomes √3 × V_LL × I_line. The √3 is bookkeeping about which voltage you measured, not a mysterious three-phase correction.
Which voltage do I enter for a three-phase supply?
The line-to-line voltage, always. On a 480Y/277 V system that is 480, not 277; on a 400Y/230 V system it is 400, not 230; on a 208Y/120 V system it is 208, not 120. The US Department of Energy fact sheet this page's formula comes from is explicit about it, defining V as "RMS voltage, mean line-to-line of 3 phases". Entering the line-to-neutral value instead understates the apparent power by a factor of 1.73, which is large enough to specify a transformer that will overheat.
What power factor should I use if I do not know it?
Find it rather than guess it. Motor and drive nameplates carry it, and so do UPS and generator datasheets. If you are sizing a supply for a mixed load, the honest approach is to work out the kVA of each item from its own nameplate and add those, rather than adding watts and applying one blanket power factor. Where you genuinely cannot obtain a figure, run the calculation at two plausible values and see how much the answer moves — if the difference matters, the number is worth chasing down. This page does not supply a default power factor for you to inherit blindly, because the right value is a property of your load and nothing else.
Can the power factor be greater than 1?
No, and the calculator refuses values above 1. The power factor is the ratio of real power to apparent power, and the real power a load consumes cannot exceed the volt-amperes the supply delivers to it. If you have entered something like 85 and been rejected, you have typed a percentage: enter 0.85. A power factor of exactly 0 is also refused, because a load that converts nothing into work has no meaningful kW answer.
Does this account for harmonics, unbalance or inrush?
No. The formulas assume a balanced, sinusoidal, steady-state supply. Non-linear loads — variable-frequency drives, switch-mode power supplies, LED drivers, rectifiers — draw current with significant harmonic content, and their true apparent power is higher than √3 × V × I computed from a fundamental-frequency reading. An unbalanced three-phase load is not described by a single line current at all and has to be treated phase by phase. Motor starting inrush can be several times the running current and is a separate sizing question, which is what a generator sizing calculation with starting watts addresses.
Can I use this number to size a cable or a breaker?
Not on its own. The current shown here is the electrical answer to the question you asked; conductor ampacity, overcurrent protection, continuous-load derating, ambient temperature correction, conduit fill and voltage-drop limits are all governed by the electrical code adopted in your jurisdiction, and local amendments change the answer. Adopted code editions vary between jurisdictions as well. Treat this page as physics and a sanity check on a quote, and have a licensed electrician or engineer do the compliance work before anything is installed.

References& sources.

  1. [1]US Department of Energy, Office of Energy Efficiency and Renewable Energy, fact sheet DOE/GO-10097-517, "Determining Electric Motor Load and Efficiency", January 1997 (OSTI report numbers DOE/GO--10097-517; 319). Primary source for the three-phase relation. Equation 1 reads "Pi = V x I x PF x √3 / 1000", with "Pi = Three-phase power in kW", "V = RMS voltage, mean line-to-line of 3 phases", "I = RMS current, mean of 3 phases", "PF = Power factor as a decimal". Setting PF = 1 isolates the apparent power. RECORDED CONFLICT: the same document's worked example prints "469.7 x 37 x 0.763 x √3 / 1000 = 22.9 kW", while the exact √3 gives 22.9671681259 kW; the printed figure is reproduced by √3 ≈ 1.73, which yields 22.94 kW. This page uses the exact √3 and a test asserts 22.9671681259 and explicitly rejects 22.94. Access: open. Retrieved and text-verified 2026-07-29.
  2. [2]OpenStax (Rice University), University Physics Volume 2, §15.4 "Power in an AC Circuit". Primary source for the power factor and the rms voltage-current product. Equation 15.12 gives "Pave = (1/2)I₀V₀cos(ϕ)" and Equation 15.13 gives "Pave = (1/2)I₀V₀ = IrmsVrms = Irms²R"; the section states "In engineering applications, cos(ϕ) is known as the power factor, which is the amount by which the power delivered in the circuit is less than the theoretical maximum of the circuit due to voltage and current being out of phase", and defines the rms values as "Irms = (1/√2)I₀ and Vrms = (1/√2)V₀". Access: open. Retrieved 2026-07-29.
  3. [3]OpenStax (Rice University), University Physics Volume 2, §9.5 "Electrical Energy and Power". Secondary check on the DC power identities underlying the AC forms: Equation 9.12 "P = IV" and Equation 9.13 "P = I²R = V²/R", plus "The energy unit on electric bills is the kilowatt-hour (kW·h), consistent with the relationship E = Pt" and "1 kW·h = 3.6 × 10⁶ J". Access: open. Retrieved 2026-07-29.
  4. [4]International Electrotechnical Commission, IEC 60050 International Electrotechnical Vocabulary, part 131, entry 131-11-41 "apparent power". Cited by IEV reference number for the standardised definition of the term and its unit, the volt-ampere. ACCESS: GATED — electropedia.org returned HTTP 403 to the retrieval used for this page, so nothing is quoted from the entry and no figure on this page rests on it. Declared as unopened rather than presented as verified. Retrieval attempted 2026-07-29.
  5. [5]NIST, Special Publication 811, "Guide for the Use of the International System of Units (SI)", 2008 edition (DOI 10.6028/NIST.SP.811e2008). Used only for unit symbols and typography — V, A, W, VA — not for any electrical relation. NIST's own landing page notes that SP 811 "has not yet been updated to reflect the changes in the SI that came into effect on May 20, 2019"; none of those changes affect the symbols used here. Access: open. Retrieved 2026-07-29.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 977 calculators remain free
  • No billing is enabled
Coming soon