Audited 29 Jul 2026·Last updated 28 Oct 2026·4 citations·Tier 2·0 uses

DC Wire Size Calculator (12V, 24V and 48V)

Size copper or aluminium cable for a 12, 24, 36, 48 or 120 V DC circuit from load, one-way run and drop budget, with an NEC Table 310.16 ampacity check.

DC Wire Size Calculator

DC system voltage
How do you know the load?
The steady current the circuit will actually draw. Ignored in watts mode. Inverters are the usual trap: a 2,000 W inverter at 12 V draws well over 170 A on the battery side once efficiency is allowed for, which is a busbar-and-lug problem rather than a wire-gauge one.
A
Ignored in amperes mode. Use the continuous rating rather than a peak or surge figure — surge is a separate problem that conductors mostly ride out but fuses and lugs do not.
W
Source to load, measured along the route the cable actually takes. The calculator doubles it for the return path. This is the number people get wrong most often, because ABYC's published tables are printed the other way round — their length column is source-to-device-and-back — so a figure copied across without halving or doubling is out by a factor of two.
ft
Conductor material
3% is the usual design target and matches NEC 210.19(A) Informational Note No. 4. ABYC E-11.14.2.6 uses the same 3% for circuits where drop must be kept to a minimum — main feeders, bilge blowers, electronics and navigation lights — and allows 10% for lighting and other circuits where drop is not critical.
%
Conductor insulation temperature rating
Conductor size to install
6 AWG copper — governed by voltage drop. That is 20 A over 15 ft one-way on a 12 V DC system, held to 3 % (0.36 V). Measure the run one-way; the calculator doubles it for the return path. This is a design aid — have a licensed electrician or a qualified installer confirm the conductor, the overcurrent protection and the terminations before anything is connected to a battery.
The conductor size and material to install, the larger of the voltage-drop and ampacity answers, with the constraint that decided it.
Minimum size on voltage drop
6 AWG copper — the smallest size with at least 21500 circular mils, which is what holds 3 % of 12 V (0.36 V) over this run. On a low-voltage DC system this is almost always the constraint that decides the answer.
Minimum size on ampacity
14 AWG copper — 25 A in the 90 °C column of NEC Table 310.16, which is enough for 20 A. This floor is taken at the table's own basis: 30 °C ambient, not more than three current-carrying conductors, no derating. Conductors running hot or bundled need the correction and adjustment factors, which the AC wire size calculator applies properly.
Circuit current
20 A
Circular mils required
21,500
Voltage drop on the run
0.295 V
Voltage drop as a percentage
2.46
Voltage at the load
11.705 V
Code basis and limits
Voltage drop from VD = 2·K·I·L/CM with the NFPA 70, 2023 edition Chapter 9 Table 8 constants (K = 12.9 for copper at 75 °C); ampacity floor from Table 310.16. The 3 % target is NEC 210.19(A) Informational Note No. 4, which is guidance rather than enforceable code — though several jurisdictions adopt it by amendment. LOCAL AMENDMENTS GOVERN and adopted editions vary by jurisdiction. A licensed electrician must sign off before work proceeds. BOATS ARE NOT COVERED HERE: marine DC wiring is governed by ABYC E-11, which uses its own ampacity table and its own voltage-drop Tables IX and X, and splits the budget 3 % for critical circuits and 10 % for non-critical ones. PV source and output circuits carry the extra 125 % stacking of NEC 690.8, and vehicle wiring is SAE territory rather than NEC.

Background.

On a 12-volt system, the usual 3% voltage-drop target leaves you 0.36 V to lose, for the whole trip from the battery to the load and back. On a 240 V circuit the same 3% is 7.2 V. That twentyfold difference is why low-voltage DC cable looks oversized to anyone used to house wiring: a 20 A load fifteen feet from a 12 V battery needs 6 AWG copper to stay inside the budget, while the same current over the same distance from a 120 V DC bank gets by on 14 AWG.

Choose the system voltage, give the load in amps or watts, measure the run one-way and set the drop you will accept. The calculator works out the conductor area the drop budget demands, finds the smallest standard size that meets it, checks the current against the NEC Table 310.16 ampacity for your insulation rating, and recommends whichever size is larger. It also shows the drop you will actually get on that size and the voltage left at the load. If the cable comes out uncomfortably heavy, try a higher system voltage: for the same power, doubling it cuts the copper needed to a quarter.

The method is NEC-based, which sets its limits. Boats follow ABYC E-11 and its own tables, solar array circuits carry extra multipliers under NEC 690.8, and wiring inside vehicles follows SAE practice. A battery bank can also push thousands of amperes into a short with nothing upstream to trip, so the fuse at the battery end and the terminations matter as much as the gauge; have a licensed electrician or qualified installer check the design before anything is connected.

What is dc wire size calculator?

DC wire sizing means choosing the conductor between a direct-current source and its load so that, at the expected current, the voltage lost in the wire stays within an agreed share of the supply and the wire does not overheat. On DC the loss is plain resistance, with no reactance or power factor, so Ohm's law describes it exactly once the conductor temperature is fixed. Resistance rises with length and falls with cross-sectional area, which North American practice measures in circular mils, the area of a circle one thousandth of an inch across. AWG sizes are steps on that scale: 8 AWG is 16,510 circular mils, 6 AWG is 26,240 and 4 AWG is 41,740. Both conductors of a DC circuit carry the full current, so the length that counts is out and back.

How to use this calculator.

  1. Choose the DC system voltage. If you have not settled on one yet, run the same load at 12 V and again at 24 V before buying cable.
  2. Say whether you know the load in amps or watts and fill in that field; watts are divided by the system voltage. Use the continuous rating, not surge. A 2,000 W inverter on 12 V draws 166.67 A before its own losses are counted, and more once they are.
  3. Enter the one-way length from source to load, measured along the route the cable will actually follow; the calculator doubles it for the return conductor.
  4. Pick copper unless you have a reason not to. Aluminium needs about 64% more area for the same drop and terminations listed for it.
  5. Set the drop budget: 3% is the normal design target; ABYC allows 10% for lighting and other circuits where drop is not critical.
  6. Choose the insulation rating, which only moves the ampacity check. Battery and welding cable is often rated 105 °C but is not NEC building wire, so the 90 °C column stands in for it here.

The formula.

CM = 2 · K · I · L / (V × d%) · VD = 2 · K · I · L / CM

The area needed is CM = 2 × K × I × L ÷ (V × d). I is the current in amperes, L the one-way length in feet, V the nominal system voltage, d the drop budget as a fraction, and K the resistance of a conductor one circular mil in area and one foot long: 12.9 ohms for copper and 21.2 for aluminium, both at 75 °C and derived from NEC Chapter 9 Table 8. The 2 accounts for the return conductor, which loses as much voltage as the outgoing one. As a cross-check, 12.9 ÷ 105,600 circular mils gives 0.1222 Ω per 1,000 ft, against the table's 0.122 for 1/0 copper.

The smallest standard size with at least that area is the voltage-drop answer. The ampacity check is a separate lookup: the smallest size whose Table 310.16 rating, in the column for your insulation, reaches the circuit current. It uses the table's own conditions of 30 °C ambient and no more than three current-carrying conductors together, with no correction for heat or bundling. The recommendation is the larger of the two sizes, and the drop on it is VD = 2 × K × I × L ÷ CM.

For a fixed power P, the current is P ÷ V and the allowed drop is V × d, so the required area varies as 1 ÷ V²: 24 V needs a quarter of the copper of 12 V, and 48 V a sixteenth. Aluminium's larger K is where its 64% area penalty comes from, since 21.2 ÷ 12.9 ≈ 1.64.

A worked example.

Example

A 20 A load sits 15 ft from a 12 V battery, wired in copper with 90 °C insulation and held to a 3% drop. The budget is 0.03 × 12 = 0.36 V for the round trip. The required area is 2 × 12.9 × 20 × 15 ÷ 0.36 = 7,740 ÷ 0.36 = 21,500 circular mils. 8 AWG, at 16,510, falls short; 6 AWG, at 26,240, clears it. On heat alone the circuit would need only 14 AWG, rated 25 A in the 90 °C column, so voltage drop decides and the answer is 6 AWG copper. On 6 AWG the actual drop is 7,740 ÷ 26,240 ≈ 0.2950 V, or 2.4581% of 12 V, leaving 11.7050 V at the load if the battery is sitting at a full 12 V. Under load a battery usually sags below its nominal voltage, and that sag comes off the load voltage on top of the cable drop, so the unused part of the budget is worth keeping.

conductor Materialcopper
insulation Rating90
one Way Length Ft15
max Voltage Drop Percent3
load Watts240
load Basisamps
load Amps20
system Voltage12

Frequently asked questions.

How does the gauge change with distance on a 12 V circuit?
Directly: the area needed is proportional to the run. For 20 A at a 3% budget in copper, 5 ft one-way needs about 7,167 circular mils, which is 10 AWG; 15 ft needs 21,500, which is 6 AWG; and 30 ft needs 43,000, which is 3 AWG. If the answer gets unwieldy, shortening the run or raising the system voltage helps more than buying heavier cable.
Why does a 24 V or 48 V system need so much thinner cable?
Because two things improve at once. For a 240 W load over 15 ft, 12 V means 20 A and a 0.36 V budget, needing 21,500 circular mils and 6 AWG. At 24 V it is 10 A and 0.72 V, needing 5,375 and 12 AWG. At 48 V it is 5 A and 1.44 V, needing only 1,343.75 circular mils, so the smallest size offered, 14 AWG, has room to spare.
Should I design for a 3% or a 10% voltage drop?
Go by what the load does at low voltage. ABYC E-11 requires 3% for main feeders, bilge blowers, electronics and navigation lights, and allows 10% for other lighting and non-critical circuits. LED lights usually just dim; motors slow and pumps lose output; inverters and many electronics draw more current as voltage falls and then shut off at their low-voltage cutout.
Do I measure the cable run one-way or out and back?
One-way, from source to load along the cable's route; the formula doubles it for the return conductor. ABYC's wire tables are headed with the length from source to device and back to source, so a number carried between the two without halving or doubling is out by a factor of two, often a full gauge or more at 12 V.
Can I use this for wiring on a boat?
No. Marine DC wiring is governed by ABYC E-11, which has its own ampacity table and its own voltage-drop tables IX and X, and under E-11.14.2.7 the larger of the two answers must be used. Read those tables directly for a boat rather than relying on this NEC-based method.
When does ampacity decide the size instead of voltage drop?
When the current is high and the run very short, as with a battery-to-inverter cable. At 150 A over 3 ft on 12 V copper, the drop budget needs only 32,250 circular mils, which 4 AWG covers, but carrying 150 A takes 1/0 AWG under Table 310.16, so 1/0 is recommended. Bundled or hot cable needs derating beyond that, which the wire size calculator applies.
Does this size the fuse, or work out solar array currents?
Neither. Overcurrent protection must be rated for DC and placed at the source end of the run, and it is a separate choice. Photovoltaic source and output circuits apply the 125% factors of NEC 690.8 before a conductor is sized, and battery storage circuits fall under Article 706. Work out that current first, then enter it here.

References& sources.

  1. [1]National Fire Protection Association, NFPA 70 — National Electrical Code, 2023 edition. Chapter 9 Table 8 (Conductor Properties — circular-mil areas and DC resistance at 75 °C), Table 310.16 (allowable ampacities, used here as a floor), and 210.19(A) Informational Note No. 4 (the 3% branch-circuit recommendation, which is guidance and not enforceable code). The code text is gated behind NFPA's free-access registration and was not opened directly; the values used here were transcribed from reproductions and cross-checked. Retrieved 2026-07-29.
  2. [2]American Boat and Yacht Council, Standard E-11, "AC and DC Electrical Systems on Boats", excerpts published by Paneltronics. Read directly from the PDF on 2026-07-29. E-11.14.2.6 requires a maximum 3 percent drop on panelboard and switchboard main feeders, bilge blowers, electronic equipment and navigation lights, and 10 percent on lighting and other circuits where drop is not critical; E-11.14.2.7 sizes conductors from Table VI and checks them against Tables IX and X, requiring the larger conductor where the two conflict. Cited as the scope boundary for this page: marine wiring must be sized from ABYC's tables, not from the NEC-based method used here. The tables also print their length column as source-to-device-and-back, which is the origin of the one-way/round-trip confusion this page warns about.
  3. [3]Mike Holt Enterprises, "Voltage Drop Calculations". Retrieved 2026-07-29. Source of the K constants used here — 12.9 ohm-circular-mils per foot for copper and 21.2 for aluminium, defined as the DC resistance of a 1,000-circular-mil conductor 1,000 ft long at 75 °C and derived from NEC Chapter 9 Table 8 — and of the VD = 2·K·I·L/CM form. The constants were checked arithmetically against Chapter 9 Table 8: 12.9 ÷ 105,600 circular mils gives 0.1222 Ω per 1,000 ft against the table's 0.122 for 1/0 copper, and 21.2 ÷ 211,600 gives 0.1002 against 0.100 for 4/0 aluminium.
  4. [4]NECA/IBEW Electricians, reproduction of NEC Table 310.15(B)(16) (renumbered Table 310.16 from the 2020 edition onward), "Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60 °C Through 90 °C". Read directly from the PDF on 2026-07-29. Source of the ampacity floor and of the circular-mil areas, shared with the AC wire size calculator so the two pages can never disagree about a table value.

How this page was produced

Published by
Quanta Calculator
Primary sources
4 cited below
Method
CM = 2 · K · I · L / (V × d%) · VD = 2 · K · I · L / CM
Published
Last verified

Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 1560 calculators remain free
  • No billing is enabled
Coming soon