Audited 29 Jul 2026·Last updated 28 Oct 2026·6 citations·Tier 1·0 uses

CFM Calculator (Air Changes, ASHRAE 62.2, Load and Tonnage)

Find the airflow in cfm a space needs by air changes per hour, the ASHRAE 62.2 whole-house ventilation rate, a sensible load at a supply ΔT, or tons × cfm/ton.

CFM Calculator

How do you want the airflow worked out?
The area of the space you are ventilating. In ASHRAE 62.2 mode this must be the floor area of the WHOLE dwelling unit, not one room — Equation 4.1a sets a single rate for the entire dwelling, which a balanced or exhaust ventilation system then distributes.
sq ft
Used with floor area to get the volume, which is what an air-change rate multiplies. It also drives the reported air-change rate in every other mode, so you can see how many times an hour the answer actually turns the room over. ASHRAE 62.2's Equation 4.1a does not use volume at all — it is a floor-area rule.
ft
How many times an hour you want the room's air replaced. This field is deliberately free, because air-change targets by room type are trade planning conventions and no standards body publishes them — there is no code that says a bathroom needs 8 ACH. Pick a rate you can justify for the specific nuisance you are clearing: moisture, odour, solvent fumes, heat. For the code-referenced dwelling ventilation number, use the ASHRAE 62.2 mode instead.
ACH
ASHRAE 62.2 uses bedroom count as its occupancy proxy — the equation assumes two people in a studio or one-bedroom unit and one more person per additional bedroom. Section 4.1.1 states that Nbr is 'not to be less than 1', so entering 0 for a studio is correct and the calculator counts it as 1.
The SENSIBLE portion of the load — the part that changes air temperature. On a cooling load calculation the total is split into sensible and latent, and only the sensible half belongs here; using the total will overstate the airflow. On a heating load the whole thing is sensible.
BTU/h
How far the supply air differs from the room air. Residential cooling is typically designed around a 18–22 °F drop; furnace heating uses the nameplate temperature-rise range instead, commonly 35–65 °F. The airflow is inversely proportional to this number, so halving it doubles the required cfm.
°F
One ton of refrigeration is 12,000 BTU/h by definition. Residential split systems are commonly sold in half-ton steps from 1.5 to 5 tons.
tons
400 is the full-load air volume rate ENERGY STAR's Version 6.2 central air conditioner and heat pump specification uses when it defines low-static, mid-static and mobile-home blower coil systems — a rating condition, not a design mandate. The same specification rates small-duct high-velocity systems at 220 scfm per ton instead, which is why this field is editable. The right figure for a specific machine comes from its expanded performance data via ACCA Manual S.
cfm/ton
Required airflow
320
The airflow the chosen method calls for, in cubic feet per minute; the four methods answer different questions, so compare like with like.
How this number was produced, and what it does not include
Air-change method: 2,400 cubic feet of space × 8 air changes per hour ÷ 60 minutes = 320 cfm. AIR-CHANGE TARGETS BY ROOM TYPE ARE PLANNING CONVENTIONS, NOT CODE — there is no standards body that publishes "8 ACH for a bathroom". They are useful for sizing an exhaust fan for a specific nuisance (moisture, odour, fumes) where you already know what rate clears it. The code-referenced number on this page is the ASHRAE 62.2 mode.
Required airflow (metric)
151.0232 L/s
Space volume
2,400 cu ft
Air changes per hour this airflow gives
8
Airflow per square foot
1.0667 cfm/sq ft
Scope, standard and limits
Airflow only. This page does not size ducts (ACCA Manual D), select equipment (ACCA Manual S), calculate a heating or cooling load (ACCA Manual J), model static pressure or fan curves, or handle latent load. It has NO duct-velocity mode on purpose — cfm from duct diameter and air speed is the continuity equation Q = A·v and is already answered by the flow rate calculator. The ASHRAE 62.2 mode implements Equation 4.1a of Section 4.1.1 as it has stood from the 2013 edition onward (2016, 2019 and 2022 leave §4.1.1 unchanged); it returns Qtot only, applies no infiltration credit, and does not compute the separate kitchen and bathroom local-exhaust requirements of Section 5. ASHRAE 62.2 is a purchased standard, LOCAL AMENDMENTS GOVERN, and the edition a jurisdiction has adopted varies — several energy codes reference 62.2 by a specific year. Commercial and institutional buildings are ASHRAE 62.1, a different standard with a different method entirely. Have a licensed mechanical contractor or design professional confirm any ventilation or airflow design before it is installed.

Background.

Ask how much air a 2,400 square foot, three-bedroom house needs and you can defend four very different answers: 102 cfm, 800 cfm, 1,111 cfm or 2,560 cfm. None of them is an error. The first is the outdoor-air ventilation rate ASHRAE Standard 62.2 sets for the whole dwelling. The second is what the blower of a two-ton air conditioner moves at 400 cfm per ton. The third is the supply air needed to carry 24,000 BTU/h of sensible heat at a 20 °F temperature difference. The fourth is eight air changes an hour, a rate someone might pick for clearing steam from a bathroom, applied to an entire house. Cubic feet per minute is a unit; the requirement depends on what the air is for.

That is why the calculator begins by asking which question you have. Air changes per hour suits one room with one nuisance — shower moisture, cooking smells, solvent fumes in a workshop, heat from a server cupboard — where you pick the rate yourself, because no standards body publishes air-change targets by room type. The ASHRAE 62.2 mode gives the code-referenced minimum of outdoor air for a dwelling from its floor area and bedroom count. The sensible-load mode gives the airflow that delivers a known heating or cooling load to a space. The tonnage mode multiplies an air conditioner's nominal capacity by an airflow per ton.

Every answer is also expressed three other ways: in litres per second, as the air changes per hour it produces in the space you described, and as cfm per square foot. Those side figures are where a mismatched method gives itself away. The 102 cfm whole-house rate works out to about a third of an air change per hour, which looks feeble until you remember that it is fresh outdoor air arriving around the clock, on top of whatever the building already leaks.

If what you actually have is a duct diameter and an air speed, the answer is Q = A × v, and the flow rate calculator handles it directly.

What is cfm calculator?

CFM, cubic feet per minute, measures a volume of air moved per unit of time. Its metric counterpart is litres per second, and the conversion is exact because the foot is defined exactly: 1 cfm = 0.3048³ ÷ 60 m³/s, or 0.4719474432 L/s. Air changes per hour restate the same flow relative to a room, cfm × 60 ÷ volume, which is why 50 cfm is a brisk rate in a small bathroom and almost nothing in an open-plan living area. Ventilation is narrower than airflow: it means outdoor air brought in to dilute indoor contaminants, so a furnace blower recirculating 1,200 cfm through a house supplies no ventilation at all unless some of that air comes from outside. Sensible heat is the part of a heating or cooling load that changes air temperature; latent heat is the part that changes its moisture content. A ton of refrigeration is 12,000 BTU per hour by definition, a figure inherited from the heat needed to melt a short ton of ice over a day.

How to use this calculator.

  1. Choose the method that matches your question: air changes for a room with a specific nuisance, ASHRAE 62.2 for whole-dwelling ventilation, sensible load when a load calculation gives you BTU/h, tonnage when you only know the equipment size.
  2. Enter floor area and ceiling height in every mode, since they produce the volume, air-change and per-square-foot figures. In ASHRAE 62.2 mode the area is the whole dwelling unit, not one room.
  3. For air changes, choose a rate you can justify for what you are clearing. For ASHRAE 62.2, enter the bedroom count as a whole number; a studio is 0, which the standard counts as 1.
  4. For the sensible-load method, take the sensible figure from your load calculation, not the total, and enter the supply-to-room temperature difference. Cooling designs commonly sit around an 18–22 °F drop; for heating, use the temperature rise printed on the furnace nameplate, often somewhere in the 35–65 °F range.
  5. For tonnage, enter nominal tons and the airflow per ton from the equipment's own performance data if you have it. 400 cfm per ton suits most conventional ducted systems; small-duct high-velocity systems are rated nearer 220.
  6. Read the method note under the result, which shows the arithmetic with your numbers, and have a licensed mechanical contractor or designer confirm anything that will be installed or submitted for a permit.

The formula.

ACH: cfm = V×ACH⁄60 · 62.2: Qtot = 0.03A + 7.5(N+1) · load: cfm = Qs⁄(1.08×ΔT) · tons: cfm = T×q

Each method is a single equation. Air changes: cfm = V × ACH ÷ 60, where V is floor area times ceiling height in cubic feet and 60 turns an hourly rate into a per-minute one. ASHRAE 62.2: Qtot = 0.03 × A + 7.5 × (N + 1), Equation 4.1a of Section 4.1.1, with A the dwelling's floor area in square feet and N the bedroom count, not less than 1. The area term stands in for emissions from the building and its contents; the bedroom term stands in for occupants, assuming two people in a studio or one-bedroom home and one more per extra bedroom. The SI version, Equation 4.1b, is 0.15 L/s per square metre plus 3.5 L/s per (N + 1); its rounded coefficients give 47.45 L/s for a house the I-P equation puts at 48.14 L/s.

Sensible load: cfm = Qs ÷ (1.08 × ΔT). The constant is derived rather than fitted: standard air weighs 0.075 lb per cubic foot and has a specific heat of 0.24 BTU per pound per °F, and there are 60 minutes in an hour, so 0.075 × 0.24 × 60 = 1.08 BTU/h per cfm per °F. Because ΔT sits in the denominator, halving it doubles the airflow. Thinner air carries less heat per cubic foot: at 5,000 feet air is roughly 14% less dense than at sea level, so the constant falls to about 0.93 and the required cfm rises accordingly. The calculator keeps the sea-level 1.08.

Tonnage: cfm = tons × cfm per ton. The 400 default is the full-load airflow ENERGY STAR's Version 6.2 specification uses when it defines low-static, mid-static and mobile-home blower coil systems; the same document defines small-duct high-velocity systems at no less than 220 scfm per ton.

In every mode the result is converted to litres per second at 0.4719474432 L/s per cfm, re-expressed as air changes per hour (cfm × 60 ÷ V) and divided by floor area. The 62.2 result is Qtot: no infiltration credit is subtracted and the separate kitchen and bathroom exhaust requirements are not included.

A worked example.

Example

A 2,400 square foot, three-bedroom house with 8 foot ceilings is being air-sealed, and the owner wants the whole-dwelling ventilation rate under ASHRAE 62.2. The area term is 0.03 × 2,400 = 72 cfm. The occupancy term counts the bedrooms plus one, 3 + 1 = 4, at 7.5 cfm each: 7.5 × 4 = 30 cfm. Together, Qtot = 72 + 30 = 102 cfm, which converts to 102 × 0.4719474432 = 48.14 L/s. The house encloses 2,400 × 8 = 19,200 cubic feet. Moving 102 cfm, or 6,120 cubic feet an hour, through that volume gives 6,120 ÷ 19,200 ≈ 0.319 air changes per hour, one complete exchange roughly every 3.1 hours. Spread over the floor it is 102 ÷ 2,400 = 0.0425 cfm per square foot. The edition matters. Under ASHRAE 62.2-2010 the area coefficient was 0.01, so the same house would have come to 24 + 30 = 54 cfm, barely half today's figure. The 102 cfm is also the total required rate, Qtot. If a blower-door test has measured the house's infiltration, Section 4.1.2 lets part of that leakage count toward the total, so the mechanical fan may be smaller. Without a test, the fan has to supply the full 102 cfm, continuously.

bedrooms3
air Changes Per Hour8
ceiling Height Ft8
cooling Tons2
methodashrae622
supply Delta T F20
sensible Load Btuh24,000
cfm Per Ton400
floor Area Sq Ft2,400

Frequently asked questions.

How many cfm does a small bathroom exhaust fan need?
By the air-change method, a 5 by 8 foot bathroom with an 8 foot ceiling holds 320 cubic feet, so 8 air changes an hour is 320 × 8 ÷ 60 ≈ 42.7 cfm, and a 50 cfm fan gives about 9.4. One cfm per square foot of floor is another widely quoted rule of thumb for small bathrooms. ASHRAE 62.2 also has its own local-exhaust requirements for bathrooms in Section 5, which this calculator does not compute.
Why is the ASHRAE 62.2 figure so much lower than the air-change answer?
Because it answers a different question. The 62.2 rate is a continuous minimum of outdoor air for diluting what a household and its building give off, delivered day and night. Air-change targets are usually chosen to clear a short burst of moisture or odour from one room quickly. Applying a bathroom-style 8 air changes to a whole 19,200 cubic foot house gives 2,560 cfm, which would be a large, cold and expensive draught.
Which edition of ASHRAE 62.2 does the formula follow?
Equation 4.1a as it has stood since the 2013 edition, with 0.03 cfm per square foot. Editions up to 2010 used 0.01, a third as much, which is the difference between 54 and 102 cfm for a 2,400 square foot three-bedroom house. Addendum h to the 2019 edition revised the infiltration rules in Section 4.1.2 while still pointing to 4.1.1 for Qtot. Energy codes reference specific years, so check which one your jurisdiction has adopted.
Does a 102 cfm result mean I should buy a 102 cfm fan?
Not necessarily, in either direction. The result is Qtot, the total required ventilation. Section 4.1.2 allows an infiltration credit, Qfan = Qtot − (Qinf × Aext), where Qinf comes from a blower-door test at 50 Pa and is capped at two-thirds of Qtot, and Aext is 1 for a detached house. Without a test there is no credit. A fan's rated airflow also falls as duct resistance rises, so check delivered flow, not just the box.
How is a studio apartment handled when it has no bedrooms?
Enter 0. Section 4.1.1 says the bedroom count is not to be taken as less than 1, so a studio is treated like a one-bedroom unit, which the standard assumes houses two people. A 500 square foot studio therefore needs 0.03 × 500 + 7.5 × (1 + 1) = 15 + 15 = 30 cfm. The bedroom field accepts whole numbers only, since the standard counts rooms rather than fractions.
Should I enter my total cooling load or only the sensible part?
Only the sensible part. The 1.08 equation describes heat that changes air temperature; latent heat, the moisture the coil condenses, does not belong in it. Suppose a 24,000 BTU/h cooling load is 75% sensible: the correct airflow at a 20 °F difference is 18,000 ÷ 21.6 ≈ 833 cfm, while entering the full 24,000 gives about 1,111 cfm, a third too much.
Why do the sensible-load and tonnage answers disagree for the same system?
Because neither knows what the other assumes. A two-ton unit at 400 cfm per ton moves 800 cfm; at a 20 °F supply difference that air carries 1.08 × 800 × 20 = 17,280 BTU/h of sensible heat, 72% of the unit's nominal 24,000 BTU/h, leaving the rest for moisture removal. Real coils vary, so that split is only illustrative, but it shows the source of the gap: entering all 24,000 BTU/h as sensible in the load mode is what produces 1,111 cfm.
Is 400 cfm per ton the right figure for every air conditioner?
No. It is the full-load airflow ENERGY STAR's Version 6.2 specification uses to define conventional blower coil systems, a rating condition rather than a design rule. The same specification rates small-duct high-velocity systems at no less than 220 scfm per ton, which for two tons is 440 cfm. The figure for a particular unit comes from its manufacturer's expanded performance data, typically chosen during equipment selection under ACCA Manual S.
What temperature difference should I use for a furnace?
The temperature rise range printed on the furnace's nameplate, which on many units falls somewhere between 35 and 65 °F. Heating uses a much larger difference than cooling, so it needs far less air for the same load: 24,000 BTU/h at a 50 °F rise is 24,000 ÷ (1.08 × 50) ≈ 444 cfm, against about 1,111 cfm for the same load at a 20 °F cooling drop.
Can I use the ASHRAE 62.2 mode for an office or shop?
No. Standard 62.2 covers dwelling units. Offices, shops, schools and other commercial or institutional spaces fall under ASHRAE 62.1, which uses its own per-person and per-area rates for each occupancy type. Process exhaust such as paint booths, fume hoods or commercial kitchen hoods follows separate rules again, often tied to exposure limits for specific contaminants. The air-change mode can still give a rough room figure, but not a code answer.

References& sources.

  1. [1]ANSI/ASHRAE Addendum m to ANSI/ASHRAE Standard 62.2-2013, "Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings". Read directly from the ASHRAE-published addendum PDF on 2026-07-29. Source of Section 4.1.1 "Total Ventilation Rate" and Equation 4.1a (I-P), Qtot = 0.03·Afloor + 7.5·(Nbr + 1), together with its variable definitions — including the clause that Nbr is "not to be less than 1" — the SI form Equation 4.1b, and Tables 4.1a and 4.1b, all fifty cells of which follow from the equation.
  2. [2]ANSI/ASHRAE Addendum h to ANSI/ASHRAE Standard 62.2-2019. Read directly from the ASHRAE-published addendum PDF on 2026-07-29. Source of the infiltration-credit relation this page deliberately does not apply: Equation 4-2, Qfan = Qtot − (Qinf × Aext), with Qfan the required mechanical ventilation rate, Qinf the effective annual average infiltration rate from a single-point blower-door test at 50 Pa per ASTM E1827 or ANSI/RESNET/ICC Standard 380, and Aext equal to 1 for detached dwelling units. This addendum revises Section 4.1.2 while continuing to refer to Section 4.1.1 for Qtot, which is the evidence that Equation 4.1a is unchanged in the 2019 edition.
  3. [3]ASHRAE, ANSI/ASHRAE Standard 62.2, "Ventilation and Acceptable Indoor Air Quality in Residential Buildings" — the governing standard. Sold by ASHRAE; the full current edition was not opened. Sections 4.1.1 and 4.1.2 reach this page through the two ASHRAE-published addenda cited above, which are open documents. Section 5's separate local-exhaust requirements for kitchens and bathrooms are not implemented here.
  4. [4]U.S. Environmental Protection Agency and U.S. Department of Energy, ENERGY STAR Program Requirements, Product Specification for Central Air Conditioner and Heat Pump Equipment, Version 6.2, Section 1 (Definitions). Read directly from the PDF on 2026-07-29. Source of the 400 cfm per rated ton figure and of the fact that it is a rating condition rather than a design mandate: low-static, mid-static and mobile-home blower coil systems are defined by their external static pressure "when operated at the cooling full-load air volume rate not exceeding 400 cfm per rated ton of cooling", while small-duct high-velocity systems are defined at "at least 220 scfm per rated ton of cooling".
  5. [5]National Institute of Standards and Technology, "Guide for the Use of the International System of Units (SI)", NIST Special Publication 811, Appendix B.8. Retrieved 2026-07-29. Source of the exact airflow conversion used here: cubic foot per minute (ft³/min) → 4.719 474 × 10⁻⁴ m³/s. The calculator carries this to full precision as 0.3048³ ÷ 60 = 0.000 471 947 443 2 m³/s, or 0.471 947 443 2 L/s per cfm.
  6. [6]ASHRAE Handbook — Fundamentals, psychrometrics and standard-air properties. Source of the standard-air density of 0.075 lb/ft³ and specific heat of 0.24 BTU/lb·°F from which the sensible-heat constant 1.08 = 0.075 × 0.24 × 60 is derived. ASHRAE Handbook access is gated behind purchase or membership; the constant is not taken on authority here but reconstructed from its published components.

How this page was produced

Published by
Quanta Calculator
Primary sources
6 cited below
Method
ACH: cfm = V×ACH⁄60 · 62.2: Qtot = 0.03A + 7.5(N+1) · load: cfm = Qs⁄(1.08×ΔT) · tons: cfm = T×q
Published
Last verified

Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 1560 calculators remain free
  • No billing is enabled
Coming soon