Audited 29 Jul 2026·Last updated 31 Jul 2026·6 citations·Tier 1·0 uses

CFM Calculator (Air Changes, ASHRAE 62.2, Load and Tonnage)

Work out required airflow in CFM four ways: air changes per hour, the ASHRAE 62.2 whole-house ventilation rate, a sensible load at a supply ΔT, or cfm per ton.

CFM Calculator

How do you want the airflow worked out?
The area of the space you are ventilating. In ASHRAE 62.2 mode this must be the floor area of the WHOLE dwelling unit, not one room — Equation 4.1a sets a single rate for the entire dwelling, which a balanced or exhaust ventilation system then distributes.
sq ft
Used with floor area to get the volume, which is what an air-change rate multiplies. It also drives the reported air-change rate in every other mode, so you can see how many times an hour the answer actually turns the room over. ASHRAE 62.2's Equation 4.1a does not use volume at all — it is a floor-area rule.
ft
How many times an hour you want the room's air replaced. This field is deliberately free, because air-change targets by room type are trade planning conventions and no standards body publishes them — there is no code that says a bathroom needs 8 ACH. Pick a rate you can justify for the specific nuisance you are clearing: moisture, odour, solvent fumes, heat. For the code-referenced dwelling ventilation number, use the ASHRAE 62.2 mode instead.
ACH
ASHRAE 62.2 uses bedroom count as its occupancy proxy — the equation assumes two people in a studio or one-bedroom unit and one more person per additional bedroom. Section 4.1.1 states that Nbr is 'not to be less than 1', so entering 0 for a studio is correct and the calculator counts it as 1.
The SENSIBLE portion of the load — the part that changes air temperature. On a cooling load calculation the total is split into sensible and latent, and only the sensible half belongs here; using the total will overstate the airflow. On a heating load the whole thing is sensible.
BTU/h
How far the supply air differs from the room air. Residential cooling is typically designed around a 18–22 °F drop; furnace heating uses the nameplate temperature-rise range instead, commonly 35–65 °F. The airflow is inversely proportional to this number, so halving it doubles the required cfm.
°F
One ton of refrigeration is 12,000 BTU/h by definition. Residential split systems are commonly sold in half-ton steps from 1.5 to 5 tons.
tons
400 is the full-load air volume rate ENERGY STAR's Version 6.2 central air conditioner and heat pump specification uses when it defines low-static, mid-static and mobile-home blower coil systems — a rating condition, not a design mandate. The same specification rates small-duct high-velocity systems at 220 scfm per ton instead, which is why this field is editable. The right figure for a specific machine comes from its expanded performance data via ACCA Manual S.
cfm/ton
Required airflow
320
The airflow the selected method calls for, in cubic feet per minute. Read the method note below it before acting on the number — the four methods answer four different questions and are not interchangeable.
How this number was produced, and what it does not include
Air-change method: 2,400 cubic feet of space × 8 air changes per hour ÷ 60 minutes = 320 cfm. AIR-CHANGE TARGETS BY ROOM TYPE ARE PLANNING CONVENTIONS, NOT CODE — there is no standards body that publishes "8 ACH for a bathroom". They are useful for sizing an exhaust fan for a specific nuisance (moisture, odour, fumes) where you already know what rate clears it. The code-referenced number on this page is the ASHRAE 62.2 mode.
Required airflow (metric)
151.0232 L/s
Space volume
2,400 cu ft
Air changes per hour this airflow gives
8
Airflow per square foot
1.0667 cfm/sq ft
Scope, standard and limits
Airflow only. This page does not size ducts (ACCA Manual D), select equipment (ACCA Manual S), calculate a heating or cooling load (ACCA Manual J), model static pressure or fan curves, or handle latent load. It has NO duct-velocity mode on purpose — cfm from duct diameter and air speed is the continuity equation Q = A·v and is already answered by the flow rate calculator. The ASHRAE 62.2 mode implements Equation 4.1a of Section 4.1.1 as it has stood from the 2013 edition onward (2016, 2019 and 2022 leave §4.1.1 unchanged); it returns Qtot only, applies no infiltration credit, and does not compute the separate kitchen and bathroom local-exhaust requirements of Section 5. ASHRAE 62.2 is a purchased standard, LOCAL AMENDMENTS GOVERN, and the edition a jurisdiction has adopted varies — several energy codes reference 62.2 by a specific year. Commercial and institutional buildings are ASHRAE 62.1, a different standard with a different method entirely. Have a licensed mechanical contractor or design professional confirm any ventilation or airflow design before it is installed.

Background.

"CFM calculator" is four questions wearing one name, and the four answers for the same room routinely differ by a factor of ten. That is not a flaw in any of them. A bathroom fan clearing shower moisture, a whole-house ventilation system meeting a code minimum, a supply register delivering a cooling load, and an air handler matched to a three-ton condenser are genuinely different problems that happen to share a unit. This page asks which one you are solving before it gives you a number, and then tells you, beside the answer, what that particular method does not cover.

The air-change method is the oldest and the loosest. Take the room's volume, decide how many times an hour you want to replace it, divide by sixty. A 300 square foot room with an 8 foot ceiling holds 2,400 cubic feet, and eight air changes an hour is 320 cfm. It is the right method when you know the rate that clears the nuisance you care about — moisture, odour, solvent vapour, waste heat — and it is worth saying plainly that air-change targets by room type are trade conventions rather than code. There is no standards body that publishes "a bathroom needs eight air changes per hour". That is why this calculator leaves the rate as a field you fill in rather than picking one for you from a hidden table.

The ASHRAE 62.2 method is the one with actual standing. Standard 62.2, Ventilation and Acceptable Indoor Air Quality in Residential Buildings, sets a minimum outdoor-air rate for a whole dwelling unit, and several energy codes and above-code programmes reference it. Section 4.1.1's Equation 4.1a is Qtot = 0.03 × Afloor + 7.5 × (Nbr + 1): three hundredths of a cfm for each square foot of floor area, plus 7.5 cfm for each bedroom plus one. The area term stands in for what the building itself emits — materials, finishes, furnishings — and the bedroom term stands in for the people, on the assumption of two occupants in a studio or one-bedroom unit and one more per additional bedroom. A 2,400 square foot three-bedroom house comes out at 102 cfm, which works out to about a third of an air change per hour and strikes most people as far too small until they realise it is outdoor air, continuously, on top of whatever the house leaks.

The sensible-load method is the one an installer uses. The rate at which an airstream carries heat is Qs = 1.08 × cfm × ΔT, so the airflow needed to deliver a known load at a known supply temperature difference is that equation rearranged. The 1.08 is not a fudge factor: it is the density of standard air, 0.075 pounds per cubic foot, times the specific heat of air, 0.24 BTU per pound per degree Fahrenheit, times sixty minutes in an hour. Two consequences follow immediately and both matter. Airflow is inversely proportional to the temperature difference, so designing around a 10 °F drop instead of a 20 °F drop doubles the ductwork you need. And it handles sensible heat only — nothing in that equation removes moisture, which is why a system sized purely on sensible capacity can hold temperature perfectly and still leave a house clammy.

The tonnage method is the shortcut, and it is the one most often quoted without its caveat. Multiply nominal tons by an airflow per ton, usually 400. That figure comes from equipment rating conditions rather than from design: ENERGY STAR's central air conditioner and heat pump specification defines several ducted system classes by their static pressure when operated at a full-load air volume rate "not exceeding 400 cfm per rated ton of cooling" — while rating small-duct high-velocity systems at 220 scfm per ton instead. So 400 is a convention attached to particular equipment classes, not a law of airflow, and the number for a specific machine comes out of its manufacturer's expanded performance data.

One thing this page deliberately will not do: calculate cfm from a duct diameter and an air velocity. That is the continuity equation, Q = A × v, and it is already answered by the flow rate calculator, which takes exactly those two inputs and returns CFM among its outputs. Duplicating it here would split one question across two pages for no benefit to anyone.

And one limit worth stating before you read any number: in ASHRAE 62.2 mode this returns Qtot, the total required ventilation rate, not Qfan, the required mechanical ventilation rate. Section 4.1.2 lets you subtract an infiltration credit from Qtot — but only where a blower door test has actually been performed, and that credit is capped at two-thirds of Qtot. No web page can do that step for you, so this one does not pretend to.

What is cfm calculator?

CFM is cubic feet per minute, the customary US unit of volumetric airflow. Its SI counterpart is litres per second, and the conversion is exact rather than approximate because the foot is defined exactly: one cubic foot per minute is 0.3048³ ÷ 60 cubic metres per second, or 0.471947 litres per second. It measures volume of air per unit time, not mass and not heat, which is why every method on this page needs a second quantity — a rate, a floor area, a temperature difference, a capacity — to turn a requirement into an airflow.

Air changes per hour, ACH, expresses the same airflow relative to the size of the space: how many times in an hour the airflow equals the room's volume. Converting between them is arithmetic — cfm = volume × ACH ÷ 60 — and the useful consequence is that the same cfm means completely different things in different rooms. Fifty cfm is about six air changes an hour in a small bathroom and about a tenth of one in a great room.

Ventilation rate, in the ASHRAE 62.2 sense, is specifically the rate of OUTDOOR air brought into a dwelling. That is a narrower idea than airflow: a furnace blower moving 1,200 cfm around a house is providing no ventilation at all if none of that air comes from outside. Standard 62.2 sets a whole-dwelling minimum for outdoor air, plus separate local-exhaust requirements for kitchens and bathrooms which this page does not compute.

Sensible heat is the part of a thermal load that changes air temperature, as distinct from latent heat, which changes its moisture content. The Qs = 1.08 × cfm × ΔT relation on this page governs sensible heat only. A cooling load calculation splits the total into both, and using the total where the equation wants the sensible part will overstate the airflow — a common and expensive error.

A ton of refrigeration is 12,000 BTU per hour by definition, a legacy of the rate at which a ton of ice melts over a day. Airflow per ton is a rating and design convention connecting a machine's capacity to the air it is expected to move, and it varies by equipment class rather than being universal.

How to use this calculator.

  1. Pick the method that matches the question you actually have. If you are sizing an exhaust fan for a specific nuisance, use air changes. If you are meeting a residential ventilation code requirement, use ASHRAE 62.2. If you know a load in BTU/h, use the sensible-load method. If you have a tonnage and want a starting airflow, use tonnage.
  2. Enter the floor area and ceiling height. These are read in every mode, because they are what turn any airflow into a volume and an air-change rate. In ASHRAE 62.2 mode the area must be the whole dwelling unit, not one room.
  3. For the air-change method, set a rate you can justify for the nuisance you are clearing. The field is free because there is no code table of ACH by room type, whatever else you may have read.
  4. For ASHRAE 62.2, enter the bedroom count. A studio is 0, and the standard counts it as 1.
  5. For the sensible-load method, enter the SENSIBLE load only — not the total cooling load — and the supply-to-room temperature difference you are designing around.
  6. For the tonnage method, enter nominal tons and the airflow per ton from the equipment's own data if you have it. 400 is a rating condition for most ducted classes, not a universal figure.
  7. Read the method note under the result. It shows the arithmetic with your numbers in it and names what the method leaves out.
  8. Check the resulting air-change rate as a sanity check. A whole-house ASHRAE 62.2 rate well under one air change per hour is normal and correct; a bathroom exhaust rate of eight or more is normal too. A number wildly outside what you expected usually means the wrong method, not a wrong answer.
  9. Take any ventilation or airflow design to a licensed mechanical contractor or design professional before it is installed, and confirm which edition of ASHRAE 62.2 your jurisdiction references.

The formula.

ACH: cfm = V×ACH⁄60 · 62.2: Qtot = 0.03A + 7.5(N+1) · load: cfm = Qs⁄(1.08×ΔT) · tons: cfm = T×q

The air-change method is a unit conversion with a decision inside it. Volume in cubic feet times air changes per hour gives cubic feet per hour; dividing by sixty gives cubic feet per minute. For a 300 square foot room with an 8 foot ceiling the volume is 2,400 cubic feet, and at 8 air changes per hour that is 2,400 × 8 ÷ 60 = 320 cfm. The decision is the rate, and the honest position is that nobody authoritative publishes one. Air-change targets circulate as trade rules of thumb, they vary between sources, and they exist because they are a convenient way to express "clear this nuisance at about this speed". Treat the rate as your judgement, not as a lookup.

The ASHRAE 62.2 method is Equation 4.1a of Section 4.1.1, quoted from the standard: Qtot = 0.03 × Afloor + 7.5 × (Nbr + 1), with Qtot in cfm, Afloor the dwelling-unit floor area in square feet, and Nbr the number of bedrooms, not to be less than one. For the worked example's 2,400 square foot three-bedroom house that is 0.03 × 2,400 = 72 cfm from the area term plus 7.5 × 4 = 30 cfm from the occupancy term, totalling 102 cfm. The SI form of the same rule, Equation 4.1b, is Qtot = 0.15 × Afloor + 3.5 × (Nbr + 1) in litres per second and square metres.

Two things about that coefficient deserve to be said out loud. First, 0.03 is edition-specific. Standard 62.2-2010 and earlier used 0.01, one third as much, and the change arrived with the 2013 edition — for this same house that is the difference between 54 cfm and 102 cfm, so citing "ASHRAE 62.2" without a year is meaningless. Second, Qtot is not the fan you buy. Section 4.1.2 allows an infiltration credit, Qfan = Qtot − (Qinf × Aext), where Qinf may be no greater than two-thirds of Qtot, but the credit is available only where a blower door test has been performed. This page returns Qtot and says so, because inventing an infiltration figure would be the difference between a code-compliant house and one that merely looks compliant on paper.

The sensible-load method rearranges the airstream heat equation. The rate at which moving air carries sensible heat is mass flow times specific heat times temperature difference; converting cubic feet per minute into pounds per hour using standard air density and then into BTU per hour gives Qs = 0.075 × 0.24 × 60 × cfm × ΔT, and 0.075 × 0.24 × 60 is exactly 1.08. Solving for airflow, cfm = Qs ÷ (1.08 × ΔT). For 24,000 BTU/h at a 20 °F difference that is 24,000 ÷ 21.6 = 1,111 cfm. Because ΔT sits in the denominator, the relationship is inverse: design around 10 °F instead of 20 °F and the same load needs 2,222 cfm, twice the duct. The constant shifts with air density, so work well above sea level needs a corrected value.

The tonnage method is a multiplication whose interest is entirely in the second number. Two tons at 400 cfm per ton is 800 cfm. ENERGY STAR's Version 6.2 central air conditioner and heat pump specification defines low-static, mid-static and mobile-home blower coil systems by the static pressure they produce "when operated at the cooling full-load air volume rate not exceeding 400 cfm per rated ton of cooling", and defines small-duct high-velocity systems at "at least 220 scfm per rated ton" — nearly half. So 400 belongs to particular equipment classes as a rating condition, and using it as a universal design figure will be wrong for anything unusual.

Every mode also reports the same three derived figures, which is deliberate: the volume, the air-change rate the answer works out to, and the airflow per square foot. Those let you cross-check one method against another's intuition. All arithmetic is carried in exact decimal at forty significant digits and rounded once, at the end, to ten decimal places. The only step function anywhere on the page is ASHRAE's rule that Nbr is not to be less than 1, and it is applied to the value you entered, not to a rounded one.

A worked example.

Example

A 2,400 square foot, three-bedroom house with 8 foot ceilings is being tightened up, and the question is how much mechanical ventilation ASHRAE 62.2 asks for. Equation 4.1a has two terms. The area term is 0.03 cfm per square foot: 0.03 × 2,400 = 72 cfm. That part stands in for what the building itself gives off — finishes, cabinetry, furnishings, adhesives — and it scales with the building rather than with the people. The occupancy term is 7.5 cfm per bedroom plus one: with three bedrooms that is 7.5 × 4 = 30 cfm, on the standard's assumption of two people in a studio or one-bedroom unit and one more for each extra bedroom. Adding them gives a total required ventilation rate of 102 cfm, or 48.14 litres per second. That number is worth sitting with, because it looks wrong to most people the first time. The house holds 19,200 cubic feet, so 102 cfm turns the whole volume over 0.32 times an hour — about once every three hours. It is 0.0425 cfm for every square foot of floor. Neither figure sounds like much. But this is continuous outdoor air, delivered whether or not anyone opens a window, on top of whatever the envelope leaks; the standard is setting a floor for dilution, not a rate for making a room feel breezy. Two caveats belong right here rather than further down. First, the 0.03 coefficient dates from the 2013 edition. Under ASHRAE 62.2-2010 the area coefficient was 0.01, and this same house would have needed 0.01 × 2,400 + 30 = 54 cfm — barely half. Citing "ASHRAE 62.2" without naming a year does not identify a requirement. Second, 102 cfm is Qtot, the total required ventilation rate, not the fan you install. Section 4.1.2 permits an infiltration credit if a blower door test has been done, subtracting a measured infiltration figure capped at two-thirds of Qtot, and this page does not apply it because it has no test result to apply. For comparison, running the same house through the other three methods: at 8 air changes an hour it would need 2,560 cfm, at a 24,000 BTU/h sensible load and a 20 °F drop it would need 1,111 cfm, and a two-ton system at 400 cfm per ton would move 800 cfm. Those are all correct answers to different questions, and none of them is a ventilation rate.

bedrooms3
air Changes Per Hour8
ceiling Height Ft8
cooling Tons2
methodashrae622
supply Delta T F20
sensible Load Btuh24,000
cfm Per Ton400
floor Area Sq Ft2,400

Frequently asked questions.

How do I calculate CFM for a room?
Multiply the room's volume by the air changes per hour you want and divide by sixty. Volume is floor area times ceiling height, so a 300 square foot room with an 8 foot ceiling holds 2,400 cubic feet, and eight air changes an hour is 2,400 × 8 ÷ 60 = 320 cfm. The only difficult part is the rate, and the honest answer is that it is your judgement rather than a lookup: air-change targets by room type circulate widely as trade conventions, they disagree with each other, and no standards body publishes them. Choose a rate that clears the specific nuisance — moisture, odour, fumes, heat — you actually have.
What is the ASHRAE 62.2 ventilation formula?
Qtot = 0.03 × Afloor + 7.5 × (Nbr + 1), where Qtot is the total required ventilation rate in cfm, Afloor is the dwelling-unit floor area in square feet, and Nbr is the number of bedrooms, which the standard says is not to be less than 1. That is Equation 4.1a of Section 4.1.1, in inch-pound units; the SI form is Qtot = 0.15 × Afloor + 3.5 × (Nbr + 1) in litres per second and square metres. The standard also publishes Tables 4.1a and 4.1b as an alternative to the equation, and the two agree — this calculator reproduces all fifty published cells of Table 4.1a from the equation, which is one of its tests.
Which edition of ASHRAE 62.2 does this use, and does the edition matter?
It implements Equation 4.1a as it has stood from the 2013 edition onward. The edition matters enormously here, more than for most standards. ASHRAE 62.2-2010 and earlier used an area coefficient of 0.01 rather than 0.03 — one third as much — and the change arrived with the 2013 revision. For a 2,400 square foot three-bedroom house that is the difference between 54 cfm and 102 cfm. The 2016, 2019 and 2022 editions leave Section 4.1.1 alone; Addendum h to 62.2-2019, for instance, revises the infiltration credit in 4.1.2 while still pointing at 4.1.1 for Qtot. Check which year your jurisdiction's energy code references before treating any number as a requirement.
Is 102 cfm really enough for a whole house?
For the purpose ASHRAE 62.2 sets, yes — and it does look small. It works out to about a third of an air change per hour, or roughly one complete turnover every three hours. Two things reconcile it with intuition. First, it is continuous outdoor air, running whether anyone is home or not, so the dose over a day is large even though the instantaneous rate is not. Second, it sits on top of infiltration, not instead of it; the standard's own infiltration credit provision exists precisely because a leaky house is already getting some of this for free. It is a dilution floor for contaminants, not an amount of air chosen to make rooms feel fresh.
Why does this page not compute the fan size directly?
Because the step between the total required ventilation rate and the mechanical ventilation rate needs a measurement this page cannot make. Section 4.1.2 of the standard gives Qfan = Qtot − (Qinf × Aext), where Qinf is an effective annual average infiltration rate derived from a blower door test at 50 Pa and capped at two-thirds of Qtot, and Aext is 1 for a detached dwelling. Without a real test result, any infiltration figure would be invented, and inventing one is the difference between a compliant house and one that looks compliant. So the page returns Qtot, states that it is Qtot, and points at the clause. Local exhaust for kitchens and bathrooms is a separate Section 5 requirement that this page also does not compute.
Where does the number 1.08 come from?
It is derived, not fitted. The rate at which an airstream carries sensible heat is mass flow times specific heat times temperature difference. Air at ASHRAE standard conditions has a density of 0.075 pounds per cubic foot and a specific heat of 0.24 BTU per pound per degree Fahrenheit, and there are 60 minutes in an hour, so converting cubic feet per minute through pounds per hour to BTU per hour gives 0.075 × 0.24 × 60 = 1.08 exactly. That is why the constant is 1.08 rather than something rounder. It moves with air density, so design work at altitude uses a corrected value — at 5,000 feet the correction is on the order of 15 percent.
Why does the calculator refuse to work out CFM from duct size and air speed?
Because that calculation already exists on this site and duplicating it would split one question across two pages. Airflow from a duct's cross-sectional area and the air velocity through it is the continuity equation, Q = A × v, and the flow rate calculator takes a diameter and a velocity and returns the result in CFM along with six other units. Sending you there is a better answer than a fifth mode here. The same reasoning is why this page does not do duct sizing, static pressure or fan curves — those are ACCA Manual D territory and a different job.
Is 400 CFM per ton a rule?
It is a rating condition attached to particular equipment classes, and it gets quoted as if it were a law of nature. ENERGY STAR's Version 6.2 specification for central air conditioners and heat pumps defines low-static, mid-static and mobile-home blower coil systems by the external static pressure they produce when operated at a cooling full-load air volume rate 'not exceeding 400 cfm per rated ton of cooling' — and in the same list of definitions rates small-duct high-velocity systems at 'at least 220 scfm per rated ton', which is close to half. Design airflow for a specific machine comes from its manufacturer's expanded performance data, selected under ACCA Manual S, which is why this calculator leaves the figure editable rather than hard-coding 400.
Can I use the sensible-load method for a cooling load?
Yes, but only with the sensible part of it. A cooling load calculation splits the total into sensible heat, which changes air temperature, and latent heat, which changes its moisture content. Qs = 1.08 × cfm × ΔT describes sensible heat only — no amount of airflow at a given temperature difference removes a stated quantity of water. Feeding the total cooling load into the sensible equation therefore overstates the required airflow, sometimes by 25 percent or more in a humid climate, and it also hides the real design question, which is whether the equipment's sensible heat ratio matches the building's. Use the sensible figure and check the latent separately.
When should I not use this calculator?
For commercial, institutional or multifamily common spaces — those are ASHRAE 62.1, a different standard with a per-person and per-area method and its own occupancy category table, not 62.2's dwelling equation. For anything where the answer feeds a permit application, since the authority having jurisdiction will want a design from a professional rather than a web page. For process ventilation, laboratory fume hoods, paint booths, grow rooms, commercial kitchen hoods or anything with a contaminant-specific exposure limit. And for duct design, fan selection or static pressure, none of which this page attempts.

References& sources.

  1. [1]ANSI/ASHRAE Addendum m to ANSI/ASHRAE Standard 62.2-2013, "Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings". Read directly from the ASHRAE-published addendum PDF on 2026-07-29. Source of Section 4.1.1 "Total Ventilation Rate" and Equation 4.1a (I-P), Qtot = 0.03·Afloor + 7.5·(Nbr + 1), together with its variable definitions — including the clause that Nbr is "not to be less than 1" — the SI form Equation 4.1b, and Tables 4.1a and 4.1b, all fifty cells of which this calculator regenerates from the equation in its test suite.
  2. [2]ANSI/ASHRAE Addendum h to ANSI/ASHRAE Standard 62.2-2019. Read directly from the ASHRAE-published addendum PDF on 2026-07-29. Source of the infiltration-credit relation this page deliberately does not apply: Equation 4-2, Qfan = Qtot − (Qinf × Aext), with Qfan the required mechanical ventilation rate, Qinf the effective annual average infiltration rate from a single-point blower-door test at 50 Pa per ASTM E1827 or ANSI/RESNET/ICC Standard 380, and Aext equal to 1 for detached dwelling units. This addendum revises Section 4.1.2 while continuing to refer to Section 4.1.1 for Qtot, which is the evidence that Equation 4.1a is unchanged in the 2019 edition.
  3. [3]ASHRAE, ANSI/ASHRAE Standard 62.2, "Ventilation and Acceptable Indoor Air Quality in Residential Buildings" — the governing standard. Sold by ASHRAE; the full current edition was not opened. Sections 4.1.1 and 4.1.2 reach this page through the two ASHRAE-published addenda cited above, which are open documents. Section 5's separate local-exhaust requirements for kitchens and bathrooms are not implemented here.
  4. [4]U.S. Environmental Protection Agency and U.S. Department of Energy, ENERGY STAR Program Requirements, Product Specification for Central Air Conditioner and Heat Pump Equipment, Version 6.2, Section 1 (Definitions). Read directly from the PDF on 2026-07-29. Source of the 400 cfm per rated ton figure and of the fact that it is a rating condition rather than a design mandate: low-static, mid-static and mobile-home blower coil systems are defined by their external static pressure "when operated at the cooling full-load air volume rate not exceeding 400 cfm per rated ton of cooling", while small-duct high-velocity systems are defined at "at least 220 scfm per rated ton of cooling".
  5. [5]National Institute of Standards and Technology, "Guide for the Use of the International System of Units (SI)", NIST Special Publication 811, Appendix B.8. Retrieved 2026-07-29. Source of the exact airflow conversion used here: cubic foot per minute (ft³/min) → 4.719 474 × 10⁻⁴ m³/s. The calculator carries this to full precision as 0.3048³ ÷ 60 = 0.000 471 947 443 2 m³/s, or 0.471 947 443 2 L/s per cfm.
  6. [6]ASHRAE Handbook — Fundamentals, psychrometrics and standard-air properties. Source of the standard-air density of 0.075 lb/ft³ and specific heat of 0.24 BTU/lb·°F from which the sensible-heat constant 1.08 = 0.075 × 0.24 × 60 is derived. ASHRAE Handbook access is gated behind purchase or membership; the constant is not taken on authority here but reconstructed from its published components, and that arithmetic is asserted in this calculator's test suite.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 977 calculators remain free
  • No billing is enabled
Coming soon