Heat Loss Calculator
Conductive heat loss through one wall, roof, floor or window from its area, R-value and indoor and outdoor design temperatures, in BTU per hour and watts.
Heat Loss Calculator
Background.
An insulation label that says R-13 tells you how well a wall resists heat. It does not tell you how much heat leaves through it, and that rate is what sizes a furnace, compares one insulation upgrade with another, or explains why one room is always cold. The rate depends on three things: the size of the surface, how strongly it resists heat flow, and how much colder it is outside than in. Multiply the area by the temperature difference, divide by the R-value, and you have the heat flow in BTU per hour.
Written as Q = U × A × ΔT, with U = 1/R, this is the conduction equation of the ASHRAE Handbook — Fundamentals and of the Department of Energy's building-science course notes. Every term acts in proportion. Double the area or the temperature difference and the loss doubles; double the R-value and it halves. That last rule has a practical edge. Taking a surface from R-1 to R-2 halves its loss, and so does taking an attic from R-30 to R-60, but per square foot the first upgrade saves thirty times as many BTUs as the second.
Each run covers one assembly: a stretch of wall, a roof, a floor, a window or a door. A house is the sum of its assemblies plus the warm air that leaks out through gaps and is replaced by cold air, which a conduction figure does not include. The outdoor temperature to use is a design temperature, the cold night the heating must cope with, not a seasonal average; for houses that is normally the 99% heating design temperature from ASHRAE's climate tables for the nearest weather station. Enter an outdoor temperature above the indoor one and the result turns negative, meaning heat is flowing in rather than out.
What is heat loss calculator?
Heat loss here is the steady rate at which heat conducts through one building assembly when the air on each side is held at a fixed temperature, measured in BTU per hour or watts. In US units R-value is in ft²·°F·h/BTU, which reads naturally: an R-13 wall needs 13 °F of temperature difference to push one BTU per hour through each square foot. U-value is the reciprocal, the BTU per hour that flow through a square foot for each degree of difference. The R-value that belongs in the calculation is the whole assembly's: every layer from drywall to siding, plus the thin films of still air on each face, added together, and reduced where framing bridges the insulation. Because the result is a rate, it describes one moment at design conditions, not a season's fuel use.
How to use this calculator.
- Measure one assembly in square feet. For a wall, take length times height and subtract the windows and doors, which get their own runs.
- Enter the R-value of the whole assembly. The R-13 in the field's hint is the rating of batts in a 2×4 stud cavity; studs lower the effective figure and sheathing, drywall and air films raise it, so use an assembly table where you can.
- Enter the indoor design temperature; 70 °F is the usual figure for heating.
- Enter the outdoor design temperature for your location, typically the 99% heating dry-bulb from ASHRAE climate data, not the average January temperature.
- Read the heat loss in BTU per hour and watts, then repeat for each assembly and add the results for the room or house.
The formula.
The temperature difference comes first: ΔT = indoor temperature − outdoor temperature, in °F. The R-value is inverted to give U = 1/R, in BTU per hour per square foot per °F. Heat loss is then Q = U × A × ΔT in BTU per hour, and dividing by 3.412142, the number of BTU per hour in a watt from the NIST SP 811 conversion tables, gives the same rate in watts. The product U × A, often written UA, is the assembly's loss per degree of temperature difference and is the handiest number to carry around. Two combining rules follow from the physics. Layers stacked in series, such as drywall, insulation and sheathing, add their R-values. Areas side by side, such as a wall and the window in it, add their UA values; averaging R-values by area understates the loss whenever the areas differ much in quality. The equation assumes steady conditions. It ignores the heat stored in heavy materials, sunshine on the surface, air leakage and the effect of wind beyond what the outside air film already allows for, which is why it is a design-day conduction figure and not a prediction of what a thermostat will see.
A worked example.
Take a 200 sq ft exterior wall rated R-13, with 70 °F inside and an outdoor design temperature of 20 °F. The temperature difference is 70 − 20 = 50 °F. The U-value is 1 ÷ 13 = 0.0769 BTU/hr·ft²·°F. Heat loss is U × A × ΔT, which is simplest to do as 200 × 50 ÷ 13 = 769.2308 BTU per hour. Dividing by 3.412142 gives 225.4393 W. The wall's UA is 200 ÷ 13 = 15.38 BTU per hour for every degree of difference, and that is the figure to keep. On a 0 °F night the same wall would lose 70 × 15.38, about 1,076.92 BTU per hour, and for a whole-season estimate the UA goes straight into the degree-day method described below.
Frequently asked questions.
How do I account for a window in the wall I am measuring?
My insulation is rated in metric RSI. How do I convert it?
Can I turn BTU per hour into a yearly heating figure?
What does a negative result tell me about summer heat gain?
Should basement walls and floors use the outdoor design temperature?
Why does adding attic insulation save less each time I add more?
References& sources.
- [1]ASHRAE. "ASHRAE Handbook — Fundamentals." American Society of Heating, Refrigerating and Air-Conditioning Engineers.
- [2]U.S. Department of Energy, Building Science Education. "Heat Loss Calculations and Principles" (Course No. M05-003).
- [3]U.S. Department of Energy, Building Science Education. "Conduction and U-value vs. R-value."
- [4]National Institute of Standards and Technology (2008). "Guide for the Use of the International System of Units (SI), NIST Special Publication 811." U.S. Department of Commerce.
How this page was produced
- Published by
- Quanta Calculator
- Overseen by
- Daniel, Quanta Calculator Researcher
- Primary sources
- 4 cited below
- Method
- Q = U×A×ΔT = (A⁄R)×(Ti−To)
- Published
- Last verified
Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.
In this category
Embed
Quanta Pro
Paid features are coming later.
- All 1560 calculators remain free
- No billing is enabled