Subpanel Sizing Calculator
Estimate the feeder current for a subpanel from its load in VA, a demand factor and a margin, then choose the feeder breaker from standard ratings.
Subpanel Sizing Calculator
Background.
Most subpanels begin with a main panel that has run out of spaces, or with a part of the property that needs its own: a garage turned workshop, a basement suite, an addition, a detached shop. The first number to settle is the feeder current, because it fixes the breaker in the main panel that feeds the subpanel and the size of the wire between the two.
The arithmetic is identical to the Electrical Service Load Calculator's: load times a demand factor, plus a margin, divided by the voltage. With the defaults, 10,000 VA at 80% with a 25% margin stays at 10,000 VA, or 41.6667 A at 240 V. What changes is how the result is read. Under the 2023 NEC a feeder's conductors and its breaker must both be able to carry the calculated load with any continuous loads counted at 125%, and the breaker has to be a standard rating. The next standard rating above 41.6667 A is 45 A.
A subpanel never adds capacity. Every ampere it serves still passes through the main service, so the service load calculation has to include the subpanel's loads. If the service is already close to its rating, a subpanel moves the problem without solving it.
The calculator gives the current only. It does not choose the conductors, the panel or the grounding, and it does not deal with the extra rules for a subpanel in a separate building, which needs its own disconnect and grounding electrode.
What is subpanel sizing calculator?
Sizing a subpanel means settling three ratings that are easy to mix up. The feeder breaker in the main panel and the ampacity of the feeder conductors both follow from the calculated load. The subpanel's bus rating only has to be at least as large as the breaker protecting it, so a 100 A panel fed from a 60 A breaker is ordinary and leaves room for more circuits later. Panel spaces are a separate count again, since every 240 V circuit takes two. The design current this calculator returns belongs to the first two decisions.
How to use this calculator.
- In Connected or calculated load, total what the subpanel will feed in volt-amperes: nameplate ratings of fixed equipment such as a compressor, a mini-split or an EV charger, plus an allowance for lighting and receptacles. If the subpanel serves part of a house, use the same dwelling rules as the service calculation.
- In Applicable demand factor, use 100% unless you know of loads that never coincide, such as two machines that are never run at the same time or a heater and an air conditioner on the same panel.
- In Design margin, carry the 125% rule for continuous loads: 25% if the whole load is continuous, or 25% times the continuous share if only part of it is (the worked example shows how). Add any headroom for future circuits on top.
- In System voltage or design divisor, enter 240 for a 120/240 V subpanel, 208 if it is fed from two legs of a 208Y/120 V system, or 360.27 for a balanced 208 V three-phase panel.
- Read Load per design divisor as the minimum feeder current, pick the feeder breaker at or above it from the standard ratings (40, 45, 50, 60, 70, 80, 90, 100 A and so on), and size the conductors to be protected by that breaker with the Wire Size Calculator.
The formula.
Design load = L × d × (1 + m) and feeder current = design load ÷ V, where L is the load you enter in volt-amperes, d the demand factor and m the margin as fractions, and V the voltage. The demand-adjusted load, L × d, is shown before the margin is applied.
The margin field is where a subpanel calculation differs in practice from a whole-service one. The code requires a feeder to carry its noncontinuous loads at 100% and its continuous loads, those running three hours or more, at 125%. If a share c of the load is continuous, that requirement is the same as a margin of 25% × c. An EV charger making up 76.8% of a feeder's load therefore calls for a 19.2% margin, and a feeder that is entirely continuous load calls for the full 25%.
The arithmetic stops at current. Neutral sizing, conductor temperature ratings, voltage drop on a long run and the number of panel spaces all sit outside it.
A worked example.
With the defaults, 10,000 VA × 0.80 = 8,000 VA of demand-adjusted load, and 8,000 × 1.25 = 10,000 VA of design load; 10,000 ÷ 240 = 41.6667 A. The 80% and the 25% cancel, so the result is simply the connected load in amperes. Now suppose 7,680 VA of that 10,000 is a 32 A EV charger, a continuous load, and the other 2,320 VA is lighting and receptacles. The feeder has to carry 7,680 × 1.25 + 2,320 = 11,920 VA. Entering 10,000 VA with a 100% demand factor and a 19.2% margin (25% of the charger's 76.8% share) reproduces it: 11,920 VA, or 49.6667 A. A 45 A feeder breaker clears the plain 41.6667 A but not the 49.6667 A the continuous rule demands, so 50 A is the smallest standard rating that works for this subpanel.
Frequently asked questions.
Does adding a subpanel give my house more electrical capacity?
Can the subpanel be rated higher than the breaker that feeds it?
What changes when the subpanel is in a detached garage or shop?
Why are the neutral and ground bars separate in a subpanel?
How far from the main panel can a subpanel go before the wire size goes up?
Does the feeder breaker have to match the design current exactly?
References& sources.
- [1]NFPA 70, National Electrical Code 2023; load calculations, feeders and continuous loads. Retrieved 2026-08-07.
- [2]International Code Council. 2024 International Residential Code (IRC). Retrieved 2026-08-07.
- [3]U.S. Occupational Safety and Health Administration. Electrical — standards and hazards. Retrieved 2026-08-07.
How this page was produced
- Published by
- Quanta Calculator
- Overseen by
- Daniel, Quanta Calculator Researcher
- Primary sources
- 3 cited below
- Method
- design load = connected load × demand factor × (1 + design margin)
- Published
- Last verified
Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.
In this category
Embed
Quanta Pro
Paid features are coming later.
- All 1560 calculators remain free
- No billing is enabled