Audited 31 Jul 2026·Last updated 28 Oct 2026·4 citations·Tier 2·0 uses

3 Phase Motor Amperage Calculator — Line Current from Horsepower, and Motor Load from a Measured Current

Work out a three-phase motor's line current from horsepower or kW, voltage, efficiency and power factor, or estimate its load from a measured current.

3 Phase Motor Amperage Calculator

What do you want to work out?
The SHAFT OUTPUT on the nameplate, never the electrical input. A '25 hp' motor delivers 25 hp at the shaft and draws more than that from the supply.
Rating unit
This must be the LINE-TO-LINE voltage — 208, 230, 460 or 575 on a typical North American three-phase supply. Entering the line-to-neutral voltage changes the answer by a factor of √3 and is the most common error in this calculation.
V
From the nameplate — usually printed as NEMA nominal efficiency. Most modern premium-efficiency induction motors sit between 89 and 96 percent. Efficiency falls away below about half load.
%
From the nameplate, as a decimal. Typically 0.8 to 0.9 at full load for an induction motor, and it collapses much faster than efficiency at part load — a motor at 25 percent load can sit below 0.5.
Only read in the second mode. Use the mean of the three phases if they differ; a large imbalance is itself a fault worth investigating before you trust any of this arithmetic.
A
Line current
29.0794
Current in each of the three supply lines, in amperes, at the load entered; a physics figure, not the NEC sizing current.
Electrical input power
19.9252 kW
Apparent power
23.1689 kVA
Shaft output
18.65 kW
Shaft output in the rating unit
25
Losses
1.2752 kW
Load as a percentage of the rating
100.00
Efficiency applied
93.60
Power factor applied
0.86
Reading of the result
A 25 hp (electric, 746 W) three-phase motor on a 460 V line-to-line supply, at 93.6 percent efficiency and a power factor of 0.86, draws I = P ÷ (√3 × V × η × PF) = 18650 W ÷ (1.7320508076 × 460 V × 0.936 × 0.86) = 29.0794 A of line current. It takes 19.9252 kW of electrical input to deliver 18.65 kW at the shaft, so 1.2752 kW becomes heat. The 460 V figure must be the LINE-TO-LINE voltage — the DOE fact sheet this √3 comes from specifies "RMS voltage, mean line-to-line of 3 phases". Using the line-to-neutral voltage instead changes the answer by a factor of √3. The result assumes a balanced, sinusoidal, steady-state supply and the nameplate efficiency and power factor you entered. Both fall away from their nameplate values at part load — power factor much faster than efficiency — so a lightly loaded motor draws more current than a straight proportion of this figure. Starting current is a different quantity again: a direct-on-line induction motor draws several times its running current for the first seconds, which is why motor protection is not sized on running current at all. NOT A CODE SIZING CURRENT. NEC 430.6(A)(1) requires that, other than for low-speed, high-torque and multispeed motors, the full-load current values in NEC Tables 430.247 through 430.250 be used to determine conductor ampacities and the ampere ratings of switches and branch-circuit short-circuit and ground-fault protection — instead of the current marked on the motor nameplate, and therefore instead of the current computed here. This page does not reproduce Table 430.250: the reproductions available disagree with one another in several cells, and a full-load current taken from a wrong table is worse than no table at all. Look the value up in the code edition adopted in your jurisdiction. Local amendments govern, adopted editions vary, and a licensed electrician or electrical engineer must sign off before any work proceeds.

Background.

Ask how much current a 25-horsepower, 460-volt motor draws and there are three answers, each right for a different job. Physics, using the motor's efficiency and power factor, gives about 29.08 amps. The nameplate gives the manufacturer's measured full-load amps, normally within a few percent of that. The electrical code gives a third figure from a standard table, and that is the one conductors, disconnects and branch-circuit protection must be sized from. This calculator does the physics, in both directions.

The forward direction starts from a point that is easy to get backwards: a motor's horsepower or kilowatt rating is what it delivers at the shaft. The supply has to provide more, because some energy becomes heat in the windings, the iron core and the bearings. Divide the shaft power by the efficiency to get the electrical input, then divide by √3 times the line-to-line voltage times the power factor to get the current in each line.

The reverse direction is the useful one on site. Clamp an ammeter on a running motor and the same relationship, read backwards, says what fraction of its rating the motor is actually delivering. The US Department of Energy's fact sheet on motor load and efficiency is built around this estimate, because oversized motors are common and one loafing along at a fraction of its rating runs at a poor power factor.

The voltage must be measured line to line: 460 on a 460-volt system, not the roughly 266 volts from any one line to neutral. Use the smaller figure and the current comes out √3, about 1.73, times too high.

What is 3 phase motor amperage calculator?

Three-phase motor amperage is the current flowing in each of the three supply lines feeding a balanced motor, in amperes. It is not an independent property of the motor but follows from the rated shaft output, the efficiency, the power factor and the line-to-line voltage. Power factor is the share of the apparent power, volts times amps, that does real work; the remainder sustains the magnetic field. Nameplates also list full-load amps (FLA), the maker's measured current at rated load, and a code letter describing the much larger inrush at starting.

How to use this calculator.

  1. Choose the direction: the current drawn at the nameplate rating, or the load implied by a current you measured.
  2. Enter the rated output and its unit. "hp" on a nameplate normally means the 746 W electrical horsepower; the 745.7 W mechanical horsepower is offered because the DOE fact sheet uses it.
  3. Enter the line-to-line voltage at the motor. Motors with a 460 V nameplate normally run on 480 V systems, so a measured supply voltage gives a current closer to what a meter will show.
  4. Enter the full-load efficiency as a percentage and the power factor as a decimal, both from the nameplate. If an older motor does not list them, any figure you assume makes the result an estimate.
  5. For a load estimate, clamp all three lines while the motor does its normal work, and enter the average. Phases that differ markedly point to a supply or winding fault worth fixing first.
  6. Use the result for energy, heat and loading questions. Wire and breaker sizes come from the NEC table, not from this current.

The formula.

I = P_shaft ⁄ (√3 × V_LL × η × PF) Pi = √3 × V_LL × I × PF load% = (Pi × η) ⁄ P_rated × 100

Start with the energy balance. Everything drawn from the supply leaves either through the shaft or as heat, so the electrical input is Pi = P_shaft ÷ η. On a balanced three-phase supply the real power is also Pi = √3 × V_LL × I × PF, Equation 1 of the DOE fact sheet, with V_LL the line-to-line voltage and I the line current. Setting the two equal gives I = P_shaft ÷ (√3 × V_LL × η × PF).

The √3 is there because in a balanced system the voltage between two lines is √3 times the voltage from each line to the neutral point. Three phases each carrying V_LN × I × PF therefore add up to √3 × V_LL × I × PF.

Two more results come from the same terms. Apparent power, S = √3 × V_LL × I, is what transformers and generators are rated in, and real power is S × PF. The losses are Pi − P_shaft.

The load mode runs the relationship backwards: Pi from the measured current, shaft power = Pi × η, and load = shaft power ÷ rated output × 100%. The DOE sheet's Equations 2 and 3 reach the same result in a different arrangement.

All of it assumes a balanced, sinusoidal, steady supply at the efficiency and power factor entered. Below full load both fall, power factor much faster, so a lightly loaded motor draws more current than a straight proportion suggests, and a load estimate made with the full-load power factor reads high. Starting inrush and the distorted supply current of a variable-frequency drive are outside the model.

A worked example.

Example

A 25 hp motor has a 460 V nameplate, 93.6% full-load efficiency and a power factor of 0.86. Its shaft output is 25 × 746 = 18,650 W. Dividing by the efficiency gives the electrical input: 18,650 ÷ 0.936 = 19,925.21 W, or 19.9252 kW, of which 1.2752 kW ends up as heat in the windings, core and bearings. For the current, divide that input by √3 × 460 × 0.86 = 685.1993. The result is 19,925.21 ÷ 685.1993 = 29.0794 A in each line. Multiplying back without the power factor gives the apparent power, √3 × 460 × 29.0794 = 23.1689 kVA, which is the figure to check against a transformer or generator feeding this motor. That 29.0794 A is the running current at full rated load and nameplate voltage. It is not the figure for choosing conductors or protection; NEC 430.6(A)(1) sends you to Table 430.250 for that.

volts460
efficiency Percent93.6
rated Output UnithpElectric
measured Amps29.079
rated Output25
solve Forcurrent
power Factor0.86

Frequently asked questions.

Why does my clamp meter read less than the calculated current?
Usually because the motor is not at full load, or the supply is above nameplate voltage. The same 25 hp motor delivering its full rating on a 480 V supply draws about 27.87 A rather than 29.08, since current falls as voltage rises for the same power. Rounded nameplate efficiency and power factor account for a little more.
Can I size the wire and breaker from this current?
No. NEC 430.6(A)(1) requires the full-load currents in Tables 430.247 through 430.250, rather than the nameplate or a calculated value, for conductor ampacity, switch ratings and branch-circuit short-circuit and ground-fault protection, except for low-speed, high-torque and multispeed motors. Overload relays are set from the nameplate current. Check the code edition your jurisdiction has adopted, and have a licensed electrician sign off.
How do I tell whether a motor is oversized?
Use the load mode. Suppose the 25 hp motor reads 18 A at 460 V: input is √3 × 460 × 18 × 0.86 = 12.33 kW, shaft output 12.33 × 0.936 = 11.54 kW, about 61.9% load. At part load the real power factor is lower than 0.86, so the true figure is lower still; with 0.75 it drops to about 54%.
Should I enter 460 or 480 volts?
Enter the voltage actually present at the motor terminals if you can measure it. Nameplate voltages sit a little below system voltages, so a 460 V motor normally runs from a 480 V supply and a 200 V motor from 208 V. For a quick estimate the nameplate figure is fine; it gives a slightly higher, more conservative current.
Which horsepower should I choose, electrical or mechanical?
Electrical, at 746 W, unless your source states otherwise. The mechanical horsepower is 745.6999 W, the figure the DOE fact sheet rounds to 0.7457 kW. On the 25 hp example it lowers the shaft power to 18,642.5 W and the current from 29.0794 A to 29.0677 A, a 0.04% change well inside nameplate tolerances.
Why is the starting current so much higher than this?
A motor started direct on line draws several times its running current for the first few seconds, until the rotor comes up to speed. The nameplate code letter indicates how large that inrush is, in locked-rotor kVA per horsepower. Soft starters and variable-frequency drives reduce it. None of this affects the running current calculated here.

References& sources.

  1. [1]US Department of Energy, Office of Energy Efficiency and Renewable Energy, 'Determining Electric Motor Load and Efficiency', fact sheet DOE/GO-10097-517 (January 1997). Source of Equation 1, 'Pi = V x I x PF x √3 / 1000', with V defined as 'RMS voltage, mean line-to-line of 3 phases' and I as 'RMS current, mean of 3 phases'; and of the load estimate, its Equation 2, 'Pir = hp x 0.7457 / Efl' (input power at full-rated load), combined with its Equation 3, 'Load = Pi / Pir x 100%' — together Load = Pi ÷ (hp × 0.7457 ÷ Efl) × 100%. Also the source of the worked example (469.7 V, 37 A, PF 0.763) used as this page's independent check. Authority: US DOE / EERE. Document revision: January 1997. Locator: Equations 1, 2 and 3, and the worked example. Retrieved 2026-07-29.
  2. [2]NIST Special Publication 811, 'Guide for the Use of the International System of Units (SI)', Appendix B.9 'Factors for units listed alphabetically'. Source of both horsepower definitions: horsepower (electric) = 7.46 E+02 W exactly, and horsepower (550 ft·lbf/s) = 7.456 999 E+02 W. The exact mechanical value used here, 745.6998715822702 W, follows from the international foot (0.3048 m) and pound-force (4.4482216152605 N). Authority: National Institute of Standards and Technology. Document revision: SP 811, 2008 edition. Locator: Appendix B.9. Retrieved 2026-07-29.
  3. [3]NFPA 70, National Electrical Code, 430.6(A)(1) 'Ampacity and Motor Rating Determination — General Motor Applications', reproduced by ElectricalLicenseRenewal: other than for motors built for low speeds (less than 1200 RPM) or high torques, and for multispeed motors, the values given in Tables 430.247 through 430.250 shall be used to determine the ampacity of conductors or ampere ratings of switches and branch-circuit short-circuit and ground-fault protection, instead of the actual current rating marked on the motor nameplate. This is the rule that makes the current computed on this page unusable for code sizing, and it is stated beside the result. Authority: NFPA, via an open code-reproduction host. Locator: 430.6(A)(1). Access: gated at NFPA, open at the reproduction. Retrieved 2026-07-29.
  4. [4]EC&M (Electrical Construction & Maintenance), 'Motors and the NEC' — independent confirmation that NEC Article 430 sizes motor circuits from the Table 430.247–430.250 full-load current rather than the nameplate value, and that motor branch-circuit protection and overload protection are separate devices under 430.52 and 430.32 respectively. Used to check the scope statement, not to source any numeric value. Authority: EC&M / Endeavor Business Media. Result: agree. Retrieved 2026-07-29.

How this page was produced

Published by
Quanta Calculator
Primary sources
4 cited below
Method
I = P_shaft ⁄ (√3 × V_LL × η × PF) Pi = √3 × V_LL × I × PF load% = (Pi × η) ⁄ P_rated × 100
Published
Last verified

Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 1560 calculators remain free
  • No billing is enabled
Coming soon