Audited 29 Jul 2026·Last updated 31 Jul 2026·6 citations·Tier 1·0 uses

Beam Deflection Calculator

Work out how far a beam sags under load, check it against the IRC and IBC L/360 or L/240 deflection limit, and get the moment of inertia you need.

Beam Deflection Calculator

Support and load arrangement
What do you want to find?
Clear distance face to face of supports. For a cantilever this is the projection beyond the support, not the whole member.
ft
Pounds per lineal foot of beam. Used by the two uniform load cases. Enter the LIVE load alone for an IRC-style L/360 check, or the full dead-plus-live load for an IBC D+L check — the page deflects whatever you type.
plf
Used by the two point load cases — a post landing on the beam, a header carrying a girder end, a hot tub corner.
lb
NDS 2018 Supplement Table 4A: Douglas Fir-Larch No.2 1,600,000 · Hem-Fir No.2 1,300,000 · Spruce-Pine-Fir No.1/No.2 1,400,000 · Southern Pine No.2 1,400,000 (Table 4B). Structural steel is 29,000,000. LVL and glulam use the manufacturer's published value.
psi
How is the section defined?
Dressed thickness, not nominal. A 2x is 1.5 in, so a two-ply built-up beam is 3.0 in and a three-ply is 4.5 in.
in
Dressed depth. PS 20 dry sizes: 2x6 = 5.5 · 2x8 = 7.25 · 2x10 = 9.25 · 2x12 = 11.25 · 2x14 = 13.25 in.
in
Used only when the section is entered directly. Take it from the AISC shape tables for steel or the manufacturer's table for I-joists and LVL.
in⁴
Deflection limit
Deflection
0.3277
Maximum elastic deflection under the load you entered — at midspan for the simply supported cases, at the free end for the cantilevers. This is small-deflection Euler-Bernoulli theory: it assumes the material stays elastic, the beam is prismatic and laterally braced, and it excludes shear deformation and long-term creep, which roughly doubles the dead-load portion in wood over the life of the building.
Verdict against the code limit
0.3277 in of deflection on a simply supported beam under a uniform load. The limit you selected is L/360, which on this member is 0.4 in — L is the clear span. This member MEETS that limit, at 81.9 % of it, deflecting L/439. Deflection limits come from IRC 2021 Table R301.7 and IBC 2021 Table 1604.3; the edition your jurisdiction has adopted and its local amendments govern, and they differ between jurisdictions. A deflection check is serviceability only — it says nothing about bending, shear or bearing capacity — and a licensed structural engineer or architect must sign off before work proceeds.
Allowable deflection
0.4 in
Deflects L over
439.4531
Percentage of the limit used
81.92
Moment of inertia required
291.6 in⁴
Moment of inertia used
355.957 in⁴
Maximum bending moment
7,200 ft-lb
Maximum shear
2,400 lb

Background.

A beam that is strong enough can still be unacceptable. Bounce a floor and the drywall over it cracks; sag a header and the door under it binds; deflect a lintel and the brick above it steps. That is why building codes carry a separate serviceability limit — a maximum sag expressed as the span divided by a number — alongside the strength requirements. This page computes the sag, compares it against the limit you select, and tells you the stiffness you would need to satisfy that limit exactly.

The mathematics is elastic beam theory, and for the four arrangements almost every residential and light-commercial member falls into, the answers are closed-form. A simply supported beam under a uniform load deflects five times the load times the span to the fourth, over three hundred and eighty-four times the modulus of elasticity times the moment of inertia. Concentrate that same total load at midspan instead and the deflection drops to five-eighths of the uniform figure, because the load has moved on average closer to the supports. Turn the beam into a cantilever and the numbers get dramatically worse: a cantilever under a uniform load deflects forty-eight times as far as the same beam simply supported over the same length.

The two things worth internalising are the exponents. Span appears to the fourth power, so a beam spanning twelve feet sags sixteen times as far as the same beam spanning six. Depth appears cubed, because the moment of inertia of a rectangle is breadth times depth cubed over twelve — so swapping a 2x6 for a 2x12 cuts deflection to an eighth, while nailing on a second 2x6 alongside only halves it. Deeper always beats wider, and by a very large margin. This is the single most useful piece of structural intuition a builder can have, and it is why the answer to a bouncy floor is almost never more joists.

The limit itself is a code value, not an opinion. IRC 2021 Table R301.7 gives L/360 for floors including deck floors and for ceilings with plaster or stucco, L/240 for ceilings with gypsum board and for all other structural members, L/180 for rafters steeper than 3:12 with no ceiling attached, and L/600 for lintels supporting masonry veneer. IBC 2021 Table 1604.3 covers the same ground for commercial work, with separate columns for live load alone and for dead plus live. Both tables carry the same footnote about cantilevers — for a cantilever member, L is taken as twice the length of the cantilever — and this page implements that rule, which is why a four-foot cantilever checked at L/240 gets an allowance of 0.4 inches rather than 0.2.

One decision the page deliberately leaves to you: which load to deflect. IRC-style checks and the AWC span tables apply L/360 to the live load only, on the reasoning that the dead-load sag is already there when the finishes go on and is not what cracks them. IBC Table 1604.3 tabulates dead plus live separately. This calculator deflects whatever load you type into the field, so enter the live load alone for an IRC-style check and the full load for a D+L check. Guessing on your behalf would produce a confidently wrong answer in half the cases, which is worse than asking.

The worked example is a two-ply 2x12 Douglas Fir-Larch header, three inches of dressed breadth by 11.25 inches deep, spanning twelve feet and carrying 400 pounds per lineal foot, with a modulus of elasticity of 1,600,000 psi from NDS Table 4A. Its moment of inertia is 355.95703125 in⁴ and it deflects 0.32768 inches, which is L/439 — comfortably inside the 0.4 inch allowance that L/360 gives a twelve-foot span, at 81.92 percent of it. To land exactly on the limit the header would need 291.6 in⁴, so there is real margin here.

Finally, the scope, which matters more than the arithmetic. Deflection is a serviceability check and nothing else. A member that passes L/360 may still fail in bending, in horizontal shear, in bearing at its ends, or by lateral-torsional buckling if it is not braced. This page reports the maximum moment and shear so you can carry them into those checks, but it does not perform them. It also uses instantaneous elastic deflection: NDS 3.5.2 requires long-term creep to be accounted for in wood, which typically means adding half again or more of the dead-load deflection over the life of the building. Adopted code editions and local amendments vary between jurisdictions, and a licensed structural engineer or architect must sign off on a structural member before work proceeds.

What is beam deflection calculator?

Deflection is how far a loaded beam moves out of line, measured perpendicular to its original axis at the point where the movement is greatest. For a simply supported beam that point is at or near midspan; for a cantilever it is the free end. It is a serviceability quantity rather than a safety one: a beam bends visibly long before it breaks, and the codes limit the bending so that finishes, doors, windows and occupants' nerves survive.

The governing quantities are the modulus of elasticity E, which is a property of the material, and the moment of inertia I, which is a property of the shape. Their product EI is the flexural rigidity, and every deflection formula on this page has the form δ = K ÷ (E·I) where K depends only on the load, the span and the support conditions. That structure is why solving for the required moment of inertia is trivial once the deflection is known, and it is why the calculator can answer both questions from one computation.

The limit is written as the span divided by a number — L/360, L/240, L/180 — so it scales with span rather than being a fixed distance. A twelve-foot floor joist is allowed 0.4 inches of live-load sag at L/360; a twenty-four-foot girder is allowed 0.8. The denominators come from IRC Table R301.7 and IBC Table 1604.3 and vary with what the member supports: a brittle plaster ceiling gets a stricter limit than a rafter with nothing under it, and a lintel carrying brick veneer gets the strictest of all at L/600.

This calculator handles prismatic, laterally braced, elastic members under a single load arrangement at a time. It does not handle continuous beams over three or more supports, partial-span or triangular loads, combined uniform-plus-point loading, composite action with the sheathing, shear deflection in short deep members or I-joists, or long-term creep. For those you need a frame analysis or the joist manufacturer's software.

How to use this calculator.

  1. Pick the support and load arrangement. If the beam rests on a wall or post at each end it is simply supported; if it projects past its support with nothing under the far end it is a cantilever.
  2. Choose whether you want the deflection of a section you already have, or the moment of inertia you would need to meet the limit.
  3. Enter the span face to face of supports. For a cantilever, enter only the projection beyond the support.
  4. Enter the load. Use the uniform field in pounds per lineal foot for the two uniform cases and the concentrated field in pounds for the two point cases. Enter live load alone for an IRC-style L/360 check, or dead plus live for an IBC D+L check.
  5. Enter the modulus of elasticity. The hint carries the NDS Table 4A and 4B values for the four common framing species; steel is 29,000,000 psi.
  6. Define the section. Enter dressed breadth and depth for sawn or built-up lumber — a two-ply 2x12 is 3.0 by 11.25 inches — or switch to entering the moment of inertia directly for steel shapes and I-joists.
  7. Select the deflection limit that matches what the member supports, using IRC Table R301.7 or IBC Table 1604.3 for your jurisdiction's adopted edition.
  8. Read the verdict beside the result, then carry the maximum moment and shear into a bending, shear and bearing check — passing deflection alone never proves a beam is adequate.

The formula.

δ = 5wL⁴ ⁄ (384 · E · I)

All four cases share the form δ = K ÷ (E·I), with the span converted to inches and the uniform load converted from pounds per foot to pounds per inch. For a simply supported beam under a uniform load, K = 5wL⁴/384; for a point load at midspan, K = PL³/48; for a cantilever under a uniform load, K = wL⁴/8; and for a cantilever with a point load at the free end, K = PL³/3. Because the required moment of inertia is just K ÷ (E · δ_allowable), the same K serves both directions and the two modes are exact inverses of one another — a test asserts that a section with exactly the required I deflects exactly to the limit. Working the example: the header spans 12 ft, so L = 144 in; the load is 400 plf, so w = 400/12 = 33.333… lb/in; the section is 3.0 in by 11.25 in, so I = 3.0 × 11.25³ ÷ 12 = 355.95703125 in⁴. The numerator is 5 × 33.333… × 144⁴ = 71,663,616,000 and the denominator is 384 × 1,600,000 × 355.95703125 = 218,700,000,000, giving 0.32768 in exactly. The span-to-deflection ratio is 144 ÷ 0.32768 = 439.453125, so the header deflects L/439. The allowable deflection at L/360 is 144 ÷ 360 = 0.4 in, so the utilisation is 0.32768 ÷ 0.4 = 81.92 percent and the verdict is a pass. The moment of inertia that would land exactly on the limit is 186,624,000 ÷ (1,600,000 × 0.4) = 291.6 in⁴. Statics gives the moment and shear independently of the section: M = wL²/8 = 400 × 12² ÷ 8 = 7,200 ft-lb and V = wL/2 = 400 × 12 ÷ 2 = 2,400 lb. Rounding happens only at the return boundary — every intermediate step, including the fourth powers, is carried at twenty significant digits — and the pass/fail verdict classifies the unrounded ratio, so a member that displays 0.4000 in on both sides of the limit still flips its verdict correctly. For the two cantilever cases the allowable deflection is computed from twice the projection, following IRC 2021 Table R301.7 footnote b and IBC 2021 Table 1604.3 footnote i.

A worked example.

Example

A two-ply 2x12 Douglas Fir-Larch header spans 12 feet over a wide opening in a floor-supporting wall and carries 400 pounds per lineal foot. Dressed, the section is 3.0 inches by 11.25 inches, giving a moment of inertia of 355.95703125 in⁴, and NDS Table 4A gives Douglas Fir-Larch No.2 a modulus of elasticity of 1,600,000 psi. The calculator returns 0.32768 inches of deflection, which is L/439. The L/360 limit for a floor member allows 0.4 inches over a 12-foot span, so the header uses 81.92 percent of its deflection allowance and passes. To land exactly on the limit it would need 291.6 in⁴ — about 82 percent of what it has. Statics gives a maximum moment of 7,200 ft-lb and a maximum shear of 2,400 pounds at each end, which are the numbers to carry into the bending, shear and bearing checks that this page does not perform. Note what happens if the same load and span are given to a single 2x12 instead of two: the moment of inertia halves to 177.978 in⁴ and the deflection doubles to 0.65536 inches, which is L/220 and fails an L/360 requirement by a wide margin. Note also what happens if the two plies are 2x8s rather than 2x12s: depth is cubed, so 7.25³ against 11.25³ multiplies the deflection by 3.735 to 1.2239 inches, or L/118.

depth In11.25
width In3
moment Of Inertia In4355.957
modulus Of Elasticity Psi1,600,000
distributed Load Plf400
section Moderectangular
point Load Lb2,400
deflection Limit Denominator360
span Ft12
solve Fordeflection
load CasesimpleUniform

Frequently asked questions.

What does L/360 actually mean?
It means the beam may not sag more than its span divided by 360. Convert the span to inches first: a 12-foot span is 144 inches, so L/360 allows 144 ÷ 360 = 0.4 inches. A 20-foot span gets 240 ÷ 360 = 0.667 inches. The limit scales with span rather than being a fixed number, because a longer member is expected to move more and because the finishes over it are stretched over a longer distance. L/360 is the IRC Table R301.7 limit for floors including deck floors and for ceilings with plaster or stucco.
Which deflection limit applies to my member?
IRC 2021 Table R301.7 gives L/360 for floors, deck floors and plaster or stucco ceilings; L/240 for ceilings with gypsum board or other flexible finishes and for all other structural members; L/180 for rafters steeper than 3:12 with no finished ceiling attached to them; L/600 for lintels supporting masonry veneer; and H/180 for interior walls and partitions. IBC 2021 Table 1604.3 covers commercial work and splits the requirement into live-load and dead-plus-live columns. L/480 is not a code value — it is common practice for floors under stone or ceramic tile, where the tile industry rather than the building code sets the expectation. Confirm which edition your jurisdiction has adopted, because local amendments govern.
Should I enter the live load or the total load?
It depends on which check you are performing, and this page deliberately does not decide for you. IRC-style checks and the AWC Span Tables for Joists and Rafters apply L/360 to the live load alone, because the dead-load sag is already present when the finishes are installed. IBC Table 1604.3 tabulates a separate dead-plus-live column, usually at a looser denominator such as L/240. Enter the live load for the first kind of check and the full load for the second. Entering the total load against an L/360 limit is a conservative answer, not a wrong one, but it will make members look worse than the code requires.
Why is a deeper beam so much better than a wider one?
Because the moment of inertia of a rectangle is breadth times depth cubed, divided by twelve. Depth is cubed and breadth is not. Doubling the breadth — adding a second ply — halves the deflection. Doubling the depth divides the deflection by eight. On the worked example, swapping the two-ply 2x12 for two 2x8s multiplies deflection by 11.25³/7.25³ = 3.735, from 0.32768 to 1.2239 inches. This is why the fix for a bouncy floor is almost never more joists at closer spacing: it is deeper joists, or a mid-span beam that halves the span, since span enters to the fourth power.
Why is the cantilever limit based on twice the projection?
Because both codes say so. IRC 2021 Table R301.7 footnote b and IBC 2021 Table 1604.3 footnote i both state that for cantilever members L shall be taken as twice the length of the cantilever. The reasoning is that a cantilever deflecting at its tip behaves like half of a simply supported span of twice the length, so doubling keeps the allowance comparable. A four-foot cantilever checked at L/240 therefore gets 2 × 48 ÷ 240 = 0.4 inches, not 0.2. This calculator applies the rule automatically for the two cantilever cases and says so beside the result.
My beam passes deflection. Is it strong enough?
Not necessarily, and this is the most important limitation on the page. Deflection is a serviceability check. A member also has to pass bending — the maximum moment divided by the section modulus must not exceed the adjusted bending design value — plus horizontal shear, bearing at the supports, and lateral-torsional buckling if the compression edge is not braced by sheathing. On short, heavily loaded, deep members bending or shear usually governs; on long, lightly loaded members deflection usually governs. The calculator reports the maximum moment and shear precisely so you can carry them into those checks.
Does wood keep sagging after it is loaded?
Yes. The figure this page returns is the instantaneous elastic deflection. Wood creeps under sustained load, and NDS 3.5.2 requires the long-term deflection to be computed by multiplying the dead-load portion of the deflection by a time-dependent factor — 1.5 for seasoned lumber in dry service and 2.0 for unseasoned lumber or wet service — and adding the live-load deflection. A dead-load-dominated beam can therefore end up substantially lower than the number here after a few years. Steel does not creep at ordinary temperatures, so the elastic figure stands.
What modulus of elasticity should I use?
For visually graded sawn lumber, NDS 2018 Supplement Table 4A gives Douglas Fir-Larch 1,900,000 psi for Select Structural, 1,700,000 for No.1 and 1,600,000 for No.2; Hem-Fir 1,600,000 / 1,500,000 / 1,300,000; and Spruce-Pine-Fir 1,500,000 for Select Structural and 1,400,000 for the combined No.1/No.2 grade. Table 4B gives Southern Pine 1,800,000 / 1,600,000 / 1,400,000 for the same three grades. Structural steel is 29,000,000 psi. LVL, PSL, glulam and I-joists all carry manufacturer-published values that are specific to the product and must be taken from that manufacturer's evaluation report, not guessed.
Can this replace an engineer?
No. It computes one closed-form serviceability check on one idealised member. It assumes the beam is prismatic, laterally braced, elastic, simply supported or fixed exactly as described, and loaded by exactly one arrangement at a time. Real framing has continuity over supports, combined uniform and point loads, notches, holes, connections and load paths that have to work all the way to the footing. Adopted code editions and local amendments vary between jurisdictions. A licensed structural engineer or architect must confirm the design and sign off before work proceeds.

References& sources.

  1. [1]International Code Council — IRC 2021 Table R301.7, Allowable Deflection of Structural Members, with footnote b: "For cantilever members, L shall be taken as twice the length of the cantilever." Rows used: floors including deck floors L/360, ceilings with gypsum board L/240, rafters steeper than 3:12 with no ceiling attached L/180, all other structural members L/240, lintels supporting masonry veneer L/600.
  2. [2]ICC Building Code Action Committee — code change proposal reproducing Table R301.7 in full with all footnotes, used to confirm every row and the cantilever footnote verbatim.
  3. [3]International Code Council — IBC 2021 Section 1604.3 and Table 1604.3, Deflection Limits, footnote i: "l = Length of the member between supports. For cantilever members, l shall be taken as twice the length of the cantilever."
  4. [4]American Wood Council — NDS 2018 Supplement, Table 4A and Table 4B, Reference Design Values for Visually Graded Dimension Lumber, giving the modulus of elasticity values quoted in the field hint and FAQ.
  5. [5]American Wood Council — Span Tables for Joists and Rafters, 2021 edition, section 3, confirming the PS 20 dressed dry sizes used for the depth hint (2x6 = 1.5 x 5.5, 2x8 = 1.5 x 7.25, 2x10 = 1.5 x 9.25, 2x12 = 1.5 x 11.25) and the L/360 live-load deflection basis.
  6. [6]American Institute of Steel Construction — Steel Construction Manual, Table 3-23, "Shears, Moments and Deflections", the standard tabulation of the four closed-form cases implemented here. Print and member-gated; the four expressions were independently re-derived from the moment-curvature relation and that derivation is asserted in the test suite.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 977 calculators remain free
  • No billing is enabled
Coming soon