Audited 29 Jul 2026·Last updated 31 Jul 2026·6 citations·Tier 1·0 uses

Beam Load Calculator

Turn floor or roof psf into the load on one beam. Tributary width, IRC live loads, end reactions, maximum moment and the section modulus you need.

Beam Load Calculator

What is over this beam?
Used only when the occupancy is set to Custom. This is where a roof snow load, a roof live load or a commercial IBC Table 1607.1 value goes.
psf
The permanent weight of the construction itself. 10 psf is the usual allowance for a light-frame floor with subfloor, joists and one finished ceiling; 15–20 psf for heavier finishes, tile, gypcrete or a second ceiling; 15 psf for a typical asphalt-shingled roof assembly.
psf
The width of floor or roof this beam picks up. For a beam receiving joists from both sides it is HALF the joist span on the left plus HALF the joist span on the right — joists spanning 8 ft on each side give a tributary width of 8 ft, not 16.
ft
Face to face of supports — post to post, or wall to wall.
ft
A post from above landing on the middle of the beam, a girder end, a stair stringer. Leave at zero if the load is purely distributed. This page places it at midspan, where its moment and the uniform-load moment add exactly.
lb
The reference Fb from NDS Table 4A or 4B after all applicable adjustment factors. Douglas Fir-Larch No.2 has a reference Fb of 900 psi, so a 2x12 with the 1.0 size factor and no repetitive-member factor gives Fb' = 900 psi; add the size factor for shallower members and the 1.15 repetitive factor where it applies. Steel and engineered lumber use their own published values.
psi
NDS Table 4A reference Fv: Douglas Fir-Larch 180 · Hem-Fir 150 · Spruce-Pine-Fir 135 · Southern Pine 175 psi (Table 4B). Fv is not adjusted by the size or repetitive-member factors.
psi
Uniform load on the beam
400
Live plus dead, in pounds per lineal foot of beam. This is the number every span table, sizing chart and deflection formula wants. It is allowable-stress dead plus live — ASCE 7-16 §2.4.1 basic combination 2 — which governs a residential floor beam; a roof beam must also be checked against the combinations that include snow and roof live load.
Load path and code framing
40 psf live (room other than a sleeping room) plus 10 psf dead, over a tributary width of 8 ft, is 400 lb per lineal foot on the beam. Each end delivers 2400 lb into whatever is under it, so the post, wall, bearing and footing below have to carry that — the load path does not stop at the beam. LIVE LOADS: the tabulated values are IRC 2021 Table R301.5, Minimum Uniformly Distributed Live Loads. Guards, handrails and garage floors additionally require concentrated-load checks that this page does not perform, and roof members must also be checked for snow and roof live load. COMBINATION: this is allowable-stress dead plus live, ASCE 7-16 §2.4.1 basic combination 2. CODE AND SIGN-OFF: the edition adopted in your jurisdiction and its local amendments govern, and adopted editions differ between jurisdictions. A licensed structural engineer or architect must confirm the design and sign off before work proceeds.
Maximum bending moment
7,200 ft-lb
Reaction at each end
2,400 lb
Required section modulus, S
72 in³
Required cross-sectional area for shear
20 in²
Total load on the beam
4,800 lb
Live load share
320 plf
Dead load share
80 plf
Live load applied
40 psf
Tributary area
96 sq ft

Background.

Before you can size a beam you have to know what is on it, and that is a different question from how strong the beam is. It is a bookkeeping problem: an area load in pounds per square foot has to be collected off a strip of floor or roof and delivered onto one line of framing, then split between two supports, then converted into the moment and shear the member actually has to resist. Getting that bookkeeping wrong is the most common way an otherwise careful sizing calculation produces a dangerous answer, because everything downstream inherits the error.

The hinge of the whole thing is tributary width, and it is the single most misunderstood quantity in residential framing. A beam picks up the floor that drains onto it. A joist spanning between two beams delivers half its load to each end, so the beam under it collects half the joist span from one side plus half the joist span from the other. If joists span eight feet on each side of a central girder, the girder's tributary width is eight feet — not sixteen. Doubling that number, which people do constantly, doubles the moment and can turn an adequate beam into a failed one on paper or, worse, an inadequate beam into an apparently generous one when the mistake runs the other way.

The live load is a code value, not an estimate. IRC 2021 Table R301.5, Minimum Uniformly Distributed Live Loads, sets 40 pounds per square foot for rooms other than sleeping rooms, 30 for sleeping rooms, 40 for exterior balconies and decks, 40 for stairs, 50 for passenger-vehicle garages, 30 for habitable attics and attics served by fixed stairs, 20 for uninhabitable attics with limited storage and 10 for uninhabitable attics without storage. Those are the options this calculator offers. Guards, handrails and guard in-fill are deliberately absent, because the same table specifies them as concentrated loads — 200 pounds and 50 pounds respectively — and treating a concentrated requirement as a uniform one is a category error rather than a conservative simplification.

Dead load is yours to estimate, and the field asks for it rather than assuming it. Ten pounds per square foot is the conventional allowance for a light-frame floor with subfloor, joists and one finished ceiling. Fifteen to twenty is more honest under ceramic tile, stone, gypcrete or a double ceiling, and about fifteen covers a typical asphalt-shingled roof assembly. A heavy tile roof can reach thirty. Since dead load is permanent, it is also the part that matters for long-term creep in wood, which is why the calculator reports the live and dead shares separately rather than only their sum.

Once the line load exists, the statics are exact and short. The total load is the line load times the span, plus any concentrated load. Each end reaction is half of that, for a symmetric arrangement. The maximum moment for a uniform load is the load times the span squared over eight, and a concentrated load at midspan adds its own load times the span over four — and because both maxima occur at the same point, they add directly with no interaction term to worry about. The required section modulus is the moment in inch-pounds divided by the adjusted bending design value, and the required cross-sectional area for horizontal shear is three times the reaction divided by twice the adjusted shear design value, which is the rectangular-section form of the shear stress relation.

The worked example is a girder under a living-area floor. Joists span eight feet on each side, so the tributary width is eight feet; the girder runs twelve feet between posts; live load is the code's 40 pounds per square foot and dead load is 10. That gives 400 pounds per lineal foot — 320 live and 80 dead — over a tributary area of 96 square feet, a total of 4,800 pounds, 2,400 pounds into each post, a maximum moment of 7,200 foot-pounds and a required section modulus of 72 cubic inches at an adjusted bending value of 1,200 psi. That last number is worth sitting with: a two-ply 2x12 has a section modulus of only 63.28 cubic inches, so it fails bending here even though the very same beam, span and load pass the L/360 deflection check with 18 percent to spare. Deflection and strength are separate checks, and either one can be the one that bites.

What this page does not do is size the beam. It stops at the demands — moment, shear, reaction — and leaves the capacity side to the species, grade, size and adjustment factors that belong on a span page or in an engineer's calculation. It also does not generate load combinations beyond dead plus live, does not handle continuous beams over three or more supports, cantilever overhangs, unequal spans or off-centre point loads, and does not check bearing, connections or the columns and footings that ultimately take the reactions. Adopted code editions and local amendments vary between jurisdictions, and a licensed structural engineer or architect must confirm the design and sign off before work proceeds.

What is beam load calculator?

A beam load calculation is the conversion of an area load into a line load and then into the internal forces one member has to resist. It has three stages. First, collect: multiply the design load in pounds per square foot by the tributary width in feet to get pounds per lineal foot. Second, distribute: split the line load between the supports to get the end reactions. Third, resolve: compute the maximum bending moment and shear from the span and the load arrangement.

Tributary width is the width of the supported surface that drains onto the member. For a simply supported joist or rafter it is the on-centre spacing. For a beam or girder receiving members from both sides it is half the span of what lands on the left plus half the span of what lands on the right. For a beam under a bearing wall carrying a floor above and a roof above that, every level contributes its own tributary strip and they accumulate downward — which is why a first-floor girder in a two-storey house carries far more than the floor immediately over it.

Live load is the transient occupancy load set by the building code and tabulated by use. Dead load is the permanent weight of the construction and is estimated from the assembly. Their sum, under the allowable-stress dead-plus-live combination, is what this page distributes. Section modulus S is the geometric property that resists bending — for a rectangle it is breadth times depth squared over six — and the required S is simply the moment divided by the allowable bending stress.

This calculator handles one simply supported beam with a uniform load and at most one concentrated load at midspan. It does not handle continuous beams, cantilevers, off-centre or multiple point loads, triangular or partial-span loads, moving loads, lateral loads, or the column and footing design that the reactions feed into.

How to use this calculator.

  1. Choose what is over the beam. The option list is IRC 2021 Table R301.5, and the psf value it applies is shown beside the result so the code figure you are relying on is visible.
  2. Enter the dead load for the assembly. Use 10 psf for a plain light-frame floor, 15–20 psf for tile, stone or gypcrete, and about 15 psf for a shingled roof.
  3. Enter the tributary width. For a beam picking up joists from both sides this is half the joist span on the left plus half the joist span on the right — not the full width of the room.
  4. Enter the beam span, face to face of supports.
  5. Add a concentrated load at midspan if a post, girder end or stringer lands there. Leave it at zero otherwise.
  6. Enter the adjusted bending and shear design values for the material you intend to use, Fb' and Fv'. The hints carry the NDS Table 4A and 4B reference values for the four common framing species.
  7. Read the uniform load in plf — that is the number span tables and deflection formulas want — then the moment, the reaction and the required section modulus.
  8. Carry the reaction downward: check the post, the bearing area, the foundation and the footing, and have a licensed engineer or architect sign off before work proceeds.

The formula.

w = (L_psf + D_psf) × trib · M = wL²⁄8 + PL⁄4 · S = 12M ⁄ Fb′

The uniform line load is w = (live psf + dead psf) × tributary width, giving pounds per lineal foot. The total load on the beam is w × L plus any concentrated load P. For a symmetric arrangement each end reaction is R = wL/2 + P/2, and because a simply supported beam's shear is greatest at the supports, that reaction is also the maximum shear. The maximum moment is M = wL²/8 + PL/4; both terms peak at midspan for a uniform load and a midspan point load, so they superpose directly with no cross term. The required section modulus is S = 12M ÷ Fb', with the factor of twelve converting foot-pounds to inch-pounds, and the required cross-sectional area for horizontal shear in a rectangular member is A = 3V ÷ (2Fv'), which follows from the parabolic shear stress distribution whose peak is 1.5 times the average. Working the example: 40 psf live plus 10 psf dead is 50 psf; times a tributary width of 8 ft gives 400 plf, of which 320 plf is live and 80 plf is dead. Over a 12 ft span the tributary area is 96 sq ft and the total load is 4,800 lb, so each end carries 2,400 lb. The moment is 400 × 12² ÷ 8 = 7,200 ft-lb, which is 86,400 in-lb, so at Fb' = 1,200 psi the required section modulus is 72 in³. The required shear area is 3 × 2,400 ÷ (2 × 180) = 20 in². For comparison, a two-ply 2x12 measures 3.0 by 11.25 in, giving S = 3.0 × 11.25² ÷ 6 = 63.28 in³ and an area of 33.75 in² — it clears the shear requirement but is 12 percent short in bending. A three-ply 2x12 gives S = 94.92 in³ and an area of 50.63 in², and clears both. All arithmetic is carried at twenty significant digits and rounded only at the final result.

A worked example.

Example

A basement girder runs twelve feet between two posts and carries floor joists that span eight feet to a bearing wall on each side. Because each joist gives half its load to each end, the girder's tributary width is eight feet — half of eight on the left plus half of eight on the right — and not the sixteen feet of floor that sits between the two walls. The floor above is living space, so IRC 2021 Table R301.5 sets the live load at 40 pounds per square foot, and a plain light-frame floor is taken at 10 psf dead. The calculator returns 400 pounds per lineal foot, made up of 320 plf live and 80 plf dead, over a tributary area of 96 square feet. The total load is 4,800 pounds and each post carries 2,400 of it, which is also the maximum shear. The maximum moment is 7,200 foot-pounds at midspan, and at an adjusted bending design value of 1,200 psi that calls for a section modulus of at least 72 cubic inches and a cross-sectional area of at least 20 square inches for horizontal shear. A two-ply 2x12 measures 3.0 by 11.25 inches, giving 63.28 cubic inches and 33.75 square inches: it clears shear comfortably but is twelve percent short in bending, even though that same beam under that same load over that same span passes an L/360 deflection check at 82 percent of its allowance. A three-ply 2x12 gives 94.92 cubic inches and 50.63 square inches and clears everything. Then keep going: 2,400 pounds arrives at each post, and the post, its bearing, the pad under it and the soil under that all have to carry it.

dead Load Psf10
occupancyroomsOtherThanSleeping
allowable Bending Stress Psi1,200
beam Span Ft12
allowable Shear Stress Psi180
point Load Lb0
custom Live Load Psf40
tributary Width Ft8

Frequently asked questions.

What exactly is tributary width, and why do people get it wrong?
It is the width of floor or roof whose weight ends up on the member you are analysing. A simply supported joist delivers half its load to each end, so a beam under joists collects half the joist span from the left plus half the joist span from the right. Joists spanning eight feet on each side of a central girder give that girder an eight-foot tributary width. The common mistake is to use the full sixteen feet of floor between the two outer walls, which doubles the moment and can make an adequate beam look failed — or, when the error runs the other way and only one side is counted, make an overloaded beam look fine. For a joist or rafter rather than a beam, the tributary width is simply the on-centre spacing.
Where do the live load numbers come from?
IRC 2021 Table R301.5, Minimum Uniformly Distributed Live Loads. Rooms other than sleeping rooms are 40 psf, sleeping rooms 30, exterior balconies and decks 40, stairs 40, passenger-vehicle garages 50, habitable attics and attics served with fixed stairs 30, uninhabitable attics with limited storage 20, and uninhabitable attics without storage 10. Commercial work uses IBC Table 1607.1 instead, which is why the Custom option exists. Confirm which code edition your jurisdiction has adopted, because local amendments govern and adopted editions differ.
Why are guards and handrails not in the list?
Because IRC Table R301.5 specifies them as concentrated loads rather than uniform ones — 200 pounds applied in any direction at any point along the top of a guard or handrail, and 50 pounds on a one-square-foot area for guard in-fill components. Feeding those into a uniform-load calculator would be a category error, not a conservative simplification. The same applies to the garage floor, which requires a separate concentrated-load check in addition to the 50 psf uniform value, and to the concentrated wheel loads that govern many commercial floors.
What dead load should I use?
It depends on the assembly, which is why the calculator asks instead of assuming. Ten pounds per square foot is the conventional allowance for a light-frame floor with subfloor, joists and a single finished ceiling, and it is the value the AWC span tables pair with a 40 psf living-area live load. Fifteen to twenty is more honest under ceramic tile, stone, gypcrete or a second ceiling below. Roughly fifteen covers a typical asphalt-shingled roof assembly with sheathing, felt and a ceiling; a concrete or clay tile roof can reach thirty or more. If you are near a limit, add it up from the actual materials rather than using a round number.
Why does the moment go up with the square of the span?
Because a longer beam collects more load and applies it with a longer lever at the same time. Both effects are linear in span, so their product is quadratic — M = wL²/8. Doubling a span from six feet to twelve quadruples the moment while only doubling the reaction. This is why halving a span with a mid-span post is such a dramatic intervention, and why long clear spans push builders towards steel and engineered lumber so quickly.
Does a point load at midspan really just add to the uniform moment?
Yes, in this arrangement, and it is worth understanding why. For a uniform load on a simply supported beam the maximum moment is at midspan. For a point load at midspan the maximum moment is also at midspan. Because the two maxima coincide, the moments superpose exactly and the total is wL²/8 + PL/4 with no interaction term. If the point load were off-centre this would no longer hold — the two peaks would occur at different places and the true maximum would have to be found by locating the point of zero shear. This page places the concentrated load at midspan for exactly that reason and says so.
The required section modulus is 72 in³. What size beam is that?
Section modulus for a rectangle is breadth times depth squared divided by six, using dressed dimensions. A two-ply 2x12 is 3.0 by 11.25 inches, giving 63.28 in³ — short. A three-ply 2x12 is 4.5 by 11.25, giving 94.92 in³. A solid 4x12 is 3.5 by 11.25, giving 73.83 in³. A 3.5 by 11.875 LVL gives 82.2 in³. Remember that the Fb' you divided by must already include every applicable NDS adjustment factor for the actual member, and that clearing bending is not the same as clearing shear, bearing or deflection.
Does passing this mean the beam works?
No. This page produces demands, not a verdict. The member still has to be checked in bending against its adjusted design value with the correct size and repetitive-member factors, in horizontal shear, in bearing at the supports, and against the deflection limit in IRC Table R301.7 or IBC Table 1604.3. Beyond the beam, the reaction has to be carried by a post or wall, a bearing plate, a foundation and a footing, each of which is its own calculation. A beam sitting on an inadequate footing fails just as completely as an undersized beam.
Which load combination is this?
Allowable-stress dead plus live, which is ASCE 7-16 §2.4.1 basic combination 2 and is the combination that governs an ordinary residential floor beam. It is not the whole set. A roof member must also be checked against the combinations that include roof live load, snow and rain, and lateral load cases bring wind and seismic into the picture with their own factors. If you need combination 4 with its 0.75 factors, or the strength-design combinations of §2.3, this page does not generate them — enter the governing combined load in the Custom field or use a load-combination tool.

References& sources.

  1. [1]International Code Council — IRC 2021 Table R301.5, Minimum Uniformly Distributed Live Loads. Source of every psf value in the occupancy list: attic without storage 10, attic with limited storage 20, habitable attic 30, sleeping rooms 30, rooms other than sleeping rooms 40, balconies and decks 40, stairs 40, passenger-vehicle garages 50. Guards and handrails are specified in the same table as 200 lb concentrated and are therefore excluded here.
  2. [2]IRC 2024 R301.5 commentary reproducing the same live-load rows (10 / 20 / 30 / 40 / 40 / 50 psf) and the L/360 live-load and L/240 total-load deflection thresholds, used as the independent confirmation of Table R301.5.
  3. [3]American Society of Civil Engineers — ASCE/SEI 7-16, Minimum Design Loads and Associated Criteria for Buildings and Other Structures, §2.4.1 basic allowable-stress load combinations. Combination 2 is D + L, the combination implemented here. Access is gated; the combination list is reproduced in IBC 2021 §1605.3.
  4. [4]American Wood Council — NDS 2018 Supplement, Tables 4A and 4B, Reference Design Values for Visually Graded Dimension Lumber. Source of the reference Fb and Fv values quoted in the field hints: Douglas Fir-Larch No.2 Fb 900 / Fv 180, Hem-Fir No.2 Fb 850 / Fv 150, Spruce-Pine-Fir No.1-No.2 Fb 875 / Fv 135, Southern Pine No.2 Fv 175 psi.
  5. [5]American Wood Council — Span Tables for Joists and Rafters, 2021 edition. "Explanation of Tables" section 3 gives the PS 20-20 dressed sizes used for the section modulus comparisons, and section 9 with Tables 9.1 and 9.2 gives the required compression-perpendicular-to-grain values for bearing at the reactions.
  6. [6]International Code Council — IBC 2021 Table 1607.1, Minimum Uniformly Distributed Live Loads and Minimum Concentrated Live Loads, the commercial equivalent referenced by the Custom option.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 977 calculators remain free
  • No billing is enabled
Coming soon