Audited 30 Jul 2026·Last updated 31 Jul 2026·7 citations·Tier 1·0 uses

Floor Joist Calculator

What size floor joist you need, from NDS design values with the repetitive member factor applied. Checks bending, deflection and shear, and counts the joists.

Floor Joist Calculator

What do you want to know
Species group
Grade
Joist size (used when checking a size)
Face to face of the supports, not wall to wall. A joist bearing on a 2x4 plate at each end in a 15 ft room has a clear span of about 14 ft 9 in.
ft
Joist spacing
IRC 2021 Table R301.5: 40 psf rooms other than sleeping rooms, 30 sleeping rooms, 30 habitable attics and attics with fixed stairs, 20 attics with limited storage, 10 attics without storage, 40 decks and balconies.
psf
The weight of the assembly itself. About 10 psf for a plain light-frame floor with subfloor and drywall below, 15–20 psf under ceramic tile, stone or gypcrete. No code tabulates this — it is a property of what you are building.
psf
Deflection limit
The dimension the joists are spaced along — perpendicular to the span. Used for the joist count and the lumber take-off, and to check the NDS condition that at least three members share the load.
ft
Joist size you need
2x10 at 16 in o.c.
The shallowest of 2x6, 2x8, 2x10 and 2x12 that satisfies bending, deflection and horizontal shear over your clear span at your spacing. Design values are NDS 2018 Supplement Table 4A or 4B with the load duration factor CD at 1.0 and the repetitive member factor Cr at 1.15 where the NDS conditions are met. The page assumes dry service, normal temperature, no incising and a compression edge held in line by the subfloor, and covers single-ply nominal 2-inch dimension lumber only — engineered lumber values come from the manufacturer's ICC-ES evaluation report. Prescriptive spans are set by the code your jurisdiction has adopted (IRC 2021 Tables R502.3.1(1) and R502.3.1(2)); local amendments govern, adopted editions differ, and a licensed structural engineer or architect must sign off before work proceeds.
Pass or fail, and by how much
A 2x10 in Douglas Fir-Larch No.2 at 16 in o.c. reaches 15 ft 7 in and you need 14 ft, so it PASSES — bending is the closest limit at 80.5 % of capacity.
Maximum span, feet and inches
15 ft 7 in
Maximum span
15.6055ft
Closest limit at your span
bending
Bending utilisation
80.48
Deflection utilisation
62.41
Horizontal shear utilisation
24.94
Live-load deflection
0.2912 in
Allowable deflection
0.4667 in
Joists needed
19
Repetitive member factor, Cr
1.15
Adjusted bending value, Fb'
1,138.5 psi
Load on one joist
66.6667 plf
Stock length to order
16ft
Board feet of joist lumber
506.6667
Design values, assumptions and code framing
Cr = 1.15 IS applied: the joists are 16 in o.c. (not more than 24), there are 19 of them (not fewer than 3), and the subfloor is the load-distributing element NDS Table 4A requires. DESIGN VALUES: NDS 2018 Supplement Table 4A, Douglas Fir-Larch No.2, adjusted to Fb' = 1138.5 psi and Fv' = 180 psi. CD is fixed at 1.0 — the ten-year occupancy live load is the shortest-duration load on a floor, so there is no choice to make. Deflection is checked against the LIVE load alone at L/360, which is the IRC and AWC span-table convention for floors. ASSUMPTIONS: dry service (moisture content 19 % or less), normal temperature, no incising, and a compression edge held in line by the subfloor. SCOPE: single-ply nominal 2-inch visually graded dimension lumber, 2x6 to 2x12, simply supported over one span. It does not cover cantilevers, notches or holes, point loads, bearing at the supports, floor vibration, or engineered lumber — LVL, LSL and I-joist values come from the manufacturer's ICC-ES evaluation report. CODE AND SIGN-OFF: prescriptive joist spans are set by the code your jurisdiction has adopted — IRC 2021 Table R502.3.1(1) for sleeping rooms and Table R502.3.1(2) for living areas, with deflection limits in Table R301.7 and live loads in Table R301.5. Spans here are truncated DOWN to the whole inch while the IRC tables round to the nearest inch, so this page can read one inch short of the table. Local amendments govern and adopted editions differ between jurisdictions. A licensed structural engineer or architect must confirm the design and sign off before work proceeds.

Background.

A floor joist is not a small beam, and the difference is worth about a foot of span. The National Design Specification lets you raise the bending design value of dimension lumber by 15 percent when the members are "in contact or spaced not more than 24 inches on center, are not less than 3 in number, and are joined by floor, roof or other load distributing elements adequate to support the design load". A sheathed row of floor joists meets all three of those conditions without argument. A built-up girder does not obviously meet the third, which is why the beam span page on this site deliberately leaves the factor out and this page applies it.

That single factor is what makes this page match the code tables. Take Douglas Fir-Larch No.2, a 2x10 at 16 inches on centre, carrying 40 pounds per square foot of living-area live load and 10 of dead load. Without the repetitive-member factor the bending limit lands at 14 ft 6 in. With it, the same joist reaches 15 ft 7 in — and IRC 2021 Table R502.3.1(2) publishes 15'-7". Six more cells of that table come out the same way: 2x6 at 9'-9", 2x8 at 12'-9", 2x12 at 18'-1", Hem-Fir No.2 2x10 at 15'-2", Spruce-Pine-Fir at 15'-5", Southern Pine at 14'-0". Every one is asserted by a test against the published value. If a joist calculator disagrees with the code table by a foot, the repetitive-member factor is usually why.

Three things can stop a joist and the answer is the smallest of them. It can break in bending, which depends on the section modulus — breadth times depth squared over six — and on the adjusted bending value of the wood. It can sag past what the finishes tolerate, which depends on the moment of inertia, breadth times depth cubed over twelve, and on the modulus of elasticity. Or it can split along the grain in horizontal shear, which depends on the cross-sectional area. Those three limits move in different directions when you change something, so knowing which one is binding is more useful than knowing the number. This page reports the utilisation of all three at the span you actually have, and names the one that is closest to its capacity.

The pattern is consistent once you see it. Under a living-area load a 2x10 at 16 inches on centre is bending-limited: at a 14-foot span it sits at 80.5 percent of its bending capacity, 62.4 percent of its deflection allowance and 24.9 percent of its shear. Drop the live load to 30 psf for a sleeping room and a 2x8 becomes adequate, but now deflection governs at 97.2 percent — the joist is strong enough and only just stiff enough. Tighten the deflection limit to L/480, which is common practice under ceramic tile and stone but is not a code requirement, and deflection takes over at the same 14-foot span. Buy Select Structural instead of No.2 and the bending value jumps 67 percent while stiffness rises only 19 percent, so the 2x10 goes from bending-governed at 80.5 percent to deflection-governed, reaching 17 ft 4 in. Grade buys strength; only depth and spacing buy stiffness.

Spacing is the lever most people underuse. At the same 14-foot span and load, a 2x12 is required at 24 inches on centre, a 2x10 at 19.2 inches, a 2x10 at 16 inches, and only a 2x8 at 12 inches. Halving the spacing halves the strip of floor each joist carries, and over this span that is worth two nominal sizes. It is not always cheaper — twenty-five 2x8s at 12 inches on centre is 533 board feet against nineteen 2x10s at 16 inches on centre at 507 — but it is often the move when headroom below is the constraint rather than money. The page gives you the joist count, the stock length to order and the board-foot total so you can price both.

The deflection number is the one to look at if you care how a floor feels. At L/360 a 14-foot span allows 0.467 inches of live-load sag; the 2x10 in the worked example actually deflects 0.291 inches. That is well inside the limit and the floor will still be perceptibly springy to some people, because L/360 was never a comfort criterion — it exists to keep plaster and drywall from cracking. Floor vibration is a separate problem with its own methods, and this page does not address it. If bounce is the concern, the honest advice is to go one size deeper than the calculation requires, add a row of blocking or bridging, or glue the subfloor down as well as screwing it.

The scope is narrow and stated on purpose. This page covers single-ply nominal 2-inch visually graded dimension lumber, 2x6 through 2x12, in four species and three grades, simply supported over a single span with a uniform load. It does not cover cantilevers, notches or holes, point loads from a partition or a bathtub, doubled joists, bearing at the supports, floor vibration, or fire-resistance ratings. It does not cover solid timbers 5 inches and thicker, which are NDS Table 4D, or glulam, which is Table 5A, or LVL, LSL and I-joists, whose design values are product-specific and come from the manufacturer's ICC-ES evaluation report — there is no generic number to look up for those, and using dimension-lumber values would be confidently wrong. The load duration factor is fixed at 1.0 because the ten-year occupancy live load is the shortest-duration load on a floor, so there is no choice to make; a roof member needs 1.15 for snow or 1.25 for roof live load and belongs on the beam page. Adopted code editions and local amendments differ between jurisdictions, and a licensed structural engineer or architect must confirm the design and sign off before work proceeds.

What is floor joist calculator?

A floor joist is one of a row of parallel bending members that carry a floor between supports. Sizing one means finding the shallowest member that satisfies every applicable limit state at once over the span you have, at the spacing you intend, under the load the code assigns to the occupancy.

There are three limit states for a simply supported, uniformly loaded sawn joist. Bending capacity is the adjusted bending design value Fb' times the section modulus S; setting the demand wL²/8 equal to that and solving gives the bending-limited span. Deflection capacity comes from the modulus of elasticity E and the moment of inertia I; setting 5wL⁴/(384EI) equal to the span divided by the code denominator and solving gives the deflection-limited span. Shear capacity comes from the adjusted shear value Fv' and the cross-section, with the peak stress in a rectangular member being 1.5 times the average, and NDS 3.4.3.1(a) permitting uniform load within a distance d of each support to be ignored.

What makes a joist a joist rather than a beam is the repetitive member factor. NDS Table 4A allows Cr = 1.15 on the bending value for members spaced not more than 24 inches on centre, at least three in number, joined by a load-distributing element. Sheathing is that element: it lets a stiffer joist take load from a weaker neighbour, and it braces the compression edge. The factor applies to bending only — never to the modulus of elasticity, because stiffness is not a design value and load sharing does not make wood stiffer. That is why Cr can lengthen a bending-governed span and can never lengthen a deflection-governed one.

The calculator handles single-ply nominal 2-inch dimension lumber from 2x6 to 2x12, at 12, 16, 19.2 or 24 inches on centre, simply supported over one span. It reports the shallowest size that works, the utilisation of all three limit states at your span, the live-load deflection in inches, the joist count and the lumber take-off. It does not size headers or girders, check bearing, handle cantilevers or point loads, or address floor vibration.

How to use this calculator.

  1. Choose whether you want to be told the size, or want to check a size you have already picked. The recommended size is shown either way.
  2. Read the species and grade off the grade stamp. Unstamped lumber has no published design value and cannot be used structurally.
  3. Enter the clear span — face to face of the supports, not wall to wall. Bearing on a 2x4 plate at each end takes about 3 inches off each end of the room dimension.
  4. Pick the spacing. Try 24, 19.2, 16 and 12 inches on centre in turn: closing the spacing often drops the required size by a nominal step or two, and the board-foot total tells you whether that is cheaper.
  5. Enter the live load from IRC Table R301.5 for the occupancy — 40 psf for living areas, 30 for sleeping rooms — and estimate the dead load from the actual assembly rather than accepting 10 psf under tile or stone.
  6. Leave the deflection limit at L/360 unless the floor is getting ceramic tile or stone, in which case L/480 is common practice and is not a code requirement.
  7. Enter the floor length along the joist run for the joist count and the take-off. If it comes out at fewer than three joists the repetitive member factor drops to 1.0, and the page will say so.
  8. Read the recommended size, then read which limit is closest at your span. If deflection is closest, go deeper or closer. If bending is closest, a better grade also helps. Compare the live-load deflection in inches against the allowance to judge how the floor will feel.
  9. Check what this page does not: bearing at the supports, notches and holes, point loads, doubled joists under partitions, cantilevers and floor vibration — and have a licensed engineer or architect sign off before work proceeds.

The formula.

L = min[ √(8·Fb′·S ⁄ w) , ∛(384·E·I ⁄ (5·w·n)) , 2(2·Fv′·b·d ⁄ 3w + d) ] · Fb′ = Fb × CD × CF × Cr

Three limits are computed independently, all in inches with the load converted to pounds per inch, and the smallest is the maximum span. Bending: wL²/8 must not exceed Fb'·S, so L = √(8·Fb'·S ⁄ w). Deflection: 5wL⁴/(384EI) must not exceed L divided by the denominator n, and one power of L cancels, leaving L = ∛(384·E·I ⁄ (5·w·n)) — a cube root, not a fourth root. Shear: the peak horizontal shear stress in a rectangular member is 3V/(2bd) and NDS 3.4.3.1(a) allows uniform load within a distance d of the supports to be neglected, so V = w(L/2 − d) and L = 2·(2·Fv'·b·d ⁄ (3w) + d). The adjusted bending value is Fb' = Fb × CD × CF × Cr, with CD fixed at 1.0 for a floor, CF the Table 4A size factor, and Cr = 1.15 where the Table 4A conditions on spacing and member count are met. Fv' = Fv × CD only — neither the size factor nor the repetitive member factor touches shear. Working the example: a 2x10 is 1.5 by 9.25 inches dressed, so S = 1.5 × 9.25² ⁄ 6 = 21.390625 in³ and I = 1.5 × 9.25³ ⁄ 12 = 98.931640625 in⁴. Douglas Fir-Larch No.2 has a reference Fb of 900 psi, an E of 1,600,000 psi and an Fv of 180 psi; at a 10-inch nominal depth CF is 1.1, and with Cr at 1.15 the adjusted value is Fb' = 900 × 1.0 × 1.1 × 1.15 = 1,138.5 psi. At 16 inches on centre each joist carries a strip 1.333 ft wide, so the load is (40 + 10) × 1.333 = 66.667 plf, or 5.5556 lb/in, of which 4.4444 lb/in is live. Bending gives √(8 × 1,138.5 × 21.390625 ⁄ 5.5556) = √35,068.7 = 187.27 in = 15.6055 ft. Deflection at L/360 on the live load gives ∛(384 × 1,600,000 × 98.931640625 ⁄ (5 × 4.4444 × 360)) = 196.6 in = 16.38 ft. Shear gives 2 × (2 × 180 × 1.5 × 9.25 ⁄ (3 × 5.5556) + 9.25) = 617.9 in = 51.5 ft. Bending is smallest, so the maximum span is 15.6055 ft, displayed as 15 ft 7 in — truncated downward to the whole inch, never rounded up. Utilisation is then computed at the span you actually asked for rather than at the maximum: at 14 ft the bending stress is 5.5556 × 168² ⁄ 8 ⁄ 21.390625 = 916.3 psi, which is 80.5 percent of 1,138.5; the live-load deflection is 5 × 4.4444 × 168⁴ ⁄ (384 × 1,600,000 × 98.931640625) = 0.2912 in against an allowance of 168 ⁄ 360 = 0.4667 in, or 62.4 percent; and the shear is 24.9 percent. Every intermediate value including the square and cube roots is carried at twenty significant digits and rounded only at the final result, and the pass/fail verdict classifies the unrounded utilisation, not the displayed percentage.

A worked example.

Example

A 24 ft by 14 ft addition needs a floor. The joists will run the 14 ft direction, bearing on the foundation wall at one end and a beam at the other, so the clear span is 14 ft and the 24 ft dimension is what they are spaced along. It is living space, so IRC Table R301.5 gives 40 pounds per square foot of live load, and a plain light-frame floor with subfloor and drywall below is taken at 10 psf dead. The lumberyard stocks Douglas Fir-Larch No.2. At 16 inches on centre each joist picks up a strip 1.333 ft wide and therefore carries 66.67 pounds per lineal foot. The answer is a 2x10. There are nineteen of them — 24 ft is eighteen bays of 16 inches, plus one — ordered in 16 ft stock lengths because 14 ft of span plus 3 inches of bearing at each end needs more than a 14-footer, which comes to 507 board feet of joist lumber before rim joists, blocking and waste. The 2x10 reaches 15 ft 7 in and you need 14 ft, so it passes with room to spare. Bending is the closest limit at 80.5 percent of capacity, deflection is at 62.4 percent and horizontal shear at 24.9 percent — shear is not remotely in play, which is normal for a slender joist. Under the live load alone the middle of the joist drops 0.291 inches against an allowance of 0.467 inches at L/360. A 2x8 will not do it: it reaches only 12 ft 9 in, and at a 14 ft span it is 120.1 percent overstressed in bending and 129.6 percent past its deflection allowance. A 2x12 reaches 18 ft 1 in and sits at 59.9 percent of bending capacity, which is a lot of extra lumber — 608 board feet — for span you do not need. Three things worth noticing. First, the repetitive member factor is doing real work: nineteen joists at 16 inches on centre under a subfloor meet the NDS Table 4A conditions, so Fb' is 900 × 1.1 × 1.15 = 1,138.5 psi rather than 990, and the maximum span is 15 ft 7 in rather than 14 ft 6 in. Second, IRC 2021 Table R502.3.1(2) publishes exactly 15'-7" for this species, grade, size and spacing, so the calculation and the code table agree. Third, if this floor were getting ceramic tile you would switch to L/480, the allowance would fall to 0.350 inches, and deflection rather than bending would become the closest limit at 83.2 percent — the same joist, still adequate, but for a different reason and with less margin.

spacing In16
sizing ModerecommendSize
live Load Psf40
dead Load Psf10
speciesdouglasFirLarch
floor Length Ft24
nominal Depth In10
gradeno2
clear Span Ft14
deflection Limit Denominator360

Frequently asked questions.

How far can a 2x10 floor joist span?
For Douglas Fir-Larch No.2 at 16 inches on centre carrying 40 psf of living-area live load and 10 psf dead, 15 ft 7 in — which is exactly what IRC 2021 Table R502.3.1(2) publishes. Change any one of five things and the answer moves: Hem-Fir No.2 gives 15 ft 1 in, Spruce-Pine-Fir 15 ft 4 in and Southern Pine No.2 only 14 ft 0 in; Select Structural Douglas Fir-Larch gives 17 ft 4 in; dropping to a 30 psf sleeping-room load lengthens it, and going to 24 inches on centre shortens it. Enter your actual conditions rather than trusting a remembered number.
What size floor joist do I need for a 14 foot span?
At 16 inches on centre in Douglas Fir-Larch No.2 under a 40 psf living-area load, a 2x10. But the spacing changes the answer by two nominal sizes: you need a 2x12 at 24 inches on centre, a 2x10 at 19.2 or 16 inches, and only a 2x8 at 12 inches. The board-foot totals are close enough — 416 for the 2x12s, 507 for the 2x10s, 533 for the 2x8s — that the decision usually comes down to headroom below and what the yard has in stock rather than cost.
Why does this give a longer span than a beam calculator for the same lumber?
Because a joist gets the repetitive member factor and a beam does not. NDS Table 4A permits Cr = 1.15 on the bending design value for members not more than 24 inches on centre, at least three in number, and joined by a load-distributing element — which is exactly what a row of joists under a subfloor is. A built-up girder satisfies the spacing and count conditions but not obviously the third, so the beam span page on this site leaves Cr out. For a 2x10 Douglas Fir-Larch No.2 at 16 inches on centre the difference is 15 ft 7 in against 14 ft 6 in. Cr applies to bending only and never to the modulus of elasticity, so it cannot lengthen a deflection-governed span.
Which limit usually governs a floor joist?
It flips depending on the load. Under a 40 psf living-area load a 2x10 at 16 inches on centre is bending-governed — 80.5 percent bending against 62.4 percent deflection at a 14-foot span. Under a lighter 30 psf sleeping-room load a 2x8 becomes adequate and deflection takes over at 97.2 percent. Shallow joists tend to be deflection-governed and deeper ones bending-governed, because deflection improves with the cube of depth while bending improves with the square. Horizontal shear is almost never close on anything slender. The page names the closest limit at your span, which is what tells you what to change.
Is L/360 enough to stop a floor feeling bouncy?
Not reliably, and it was never meant to. L/360 exists to keep plaster and gypsum board from cracking, not to control how a floor feels underfoot. At a 14-foot span it allows 0.467 inches of live-load sag; the 2x10 in the worked example deflects 0.291 inches and some people will still find that floor springy. Perceived bounce is a vibration problem driven by natural frequency and damping, with its own analysis methods that this page does not implement. The practical fixes are to go one size deeper than the calculation requires, tighten the spacing, add solid blocking or bridging, and glue as well as screw the subfloor down.
Does buying a better grade help?
It helps bending a lot and deflection barely. Douglas Fir-Larch No.2 to Select Structural raises the reference bending value from 900 to 1,500 psi, a 67 percent gain, while the modulus of elasticity only goes from 1,600,000 to 1,900,000, a 19 percent gain — and because deflection depends on E linearly while the deflection-limited span depends on its cube root, that 19 percent is worth about 6 percent of span. In the worked example the upgrade takes the 2x10 from bending-governed at 80.5 percent to deflection-governed, with a maximum span of 17 ft 4 in instead of 15 ft 7 in. If deflection is already the closest limit, a better grade is close to wasted money and a deeper joist is the answer.
What is 19.2 inches on centre for?
It puts five joist bays in every 8 feet, so every 4-foot and 8-foot sheet edge lands on a joist and nothing has to be cut to fit. It is a tabulated spacing in both the IRC and the AWC span tables, it is inside the 24-inch limit for the repetitive member factor, and it uses about 16 percent fewer joists than 16 inches on centre. In the worked example it needs the same 2x10 as 16 inches does, with sixteen joists instead of nineteen and 427 board feet instead of 507 — though the bending utilisation rises from 80.5 to 96.6 percent, which is a much thinner margin.
Does this cover LVL, I-joists or engineered lumber?
No, and that is a deliberate scope limit rather than a gap. LVL, LSL, PSL and I-joists have product-specific design values published in the manufacturer's ICC-ES evaluation report — there is no generic value to look up, and different mills genuinely differ, so a calculator that offered them would be guessing. Glulam is NDS Table 5A with its own volume factor. Solid sawn timbers 5 inches and thicker are NDS Table 4D, a separate table with different values and a different size-factor rule. This page covers single-ply visually graded nominal 2-inch dimension lumber, 2x6 to 2x12, in four species and three grades, and nothing else.
Why does the answer sometimes read one inch shorter than the code table?
Because the two round in different directions on purpose. The IRC tables round a computed span to the nearest inch; this page truncates downward to the whole inch, because rounding a span up is the one rounding direction that can be unsafe. A 2x6 Douglas Fir-Larch No.2 at 16 inches on centre computes to 9 ft 8.9 in: the IRC prints 9'-9" and this page shows 9 ft 8 in. The underlying number is the same, and the feet-and-inches figure is never longer than the calculation supports.
Can I use this to get a permit?
Not on its own. A building department will normally accept a span read directly from the code table your jurisdiction has adopted — IRC 2021 Table R502.3.1(1) for sleeping rooms and R502.3.1(2) for living areas — or a design stamped by a licensed engineer or architect. This page implements the same mechanics those tables are built on and reproduces seven of their cells exactly, but it does not check bearing, connections, notches, point loads, doubled joists or vibration, local amendments govern, adopted editions differ between jurisdictions, and a licensed structural engineer or architect must sign off before work proceeds.

References& sources.

  1. [1]American Wood Council — NDS 2018 Supplement, Table 4A, Reference Design Values for Visually Graded Dimension Lumber (2"–4" thick), all species except Southern Pine. Source of Fb, E and Fv for Douglas Fir-Larch (Fb 1500/1000/900 psi, E 1.9/1.7/1.6 million psi, Fv 180), Hem-Fir (1400/975/850; 1.6/1.5/1.3 million; Fv 150) and Spruce-Pine-Fir (1250 Select Structural, 875 for the combined No.1/No.2 row; 1.5/1.4 million; Fv 135).
  2. [2]American Wood Council — NDS 2018 Supplement, Table 4A adjustment factors. Source of the repetitive member factor Cr = 1.15 and its three conditions (in contact or spaced not more than 24 in on centre, not less than 3 in number, joined by floor, roof or other load distributing elements adequate to support the design load), and of the size factor CF for Fb at 2"–3" breadth: 1.3 at 6 in nominal depth, 1.2 at 8, 1.1 at 10, 1.0 at 12.
  3. [3]American Wood Council — NDS 2018 Supplement, Table 4B, Reference Design Values for Visually Graded Southern Pine Dimension Lumber, whose size factors are already incorporated so CF must not also be applied. Fb by nominal width for No.2: 1000 at 6", 925 at 8", 800 at 10", 750 at 12"; E 1,800,000 / 1,600,000 / 1,400,000 psi for Select Structural / No.1 / No.2; Fv 175.
  4. [4]American Wood Council — Span Tables for Joists and Rafters, 2021 edition. "Explanation of Tables" section 3 gives the PS 20-20 surfaced-dry dressed sizes used here (2x6 = 1.5 × 5.5 in, 2x8 = 1.5 × 7.25, 2x10 = 1.5 × 9.25, 2x12 = 1.5 × 11.25), and the tables establish the convention that a floor deflection limit is applied to the live load alone rather than to dead plus live.
  5. [5]International Code Council — IRC 2021 Table R502.3.1(2), Floor Joist Spans for Common Lumber Species, residential living areas, 40 psf live load, 10 psf dead load, deflection limited to L/360. Used as the independent check on this calculator: seven cells (Douglas Fir-Larch No.2 2x6 9'-9", 2x8 12'-9", 2x10 15'-7", 2x12 18'-1"; Hem-Fir No.2 2x10 15'-2"; Spruce-Pine-Fir No.2 2x10 15'-5"; Southern Pine No.2 2x10 14'-0", all at 16 in o.c.) are asserted by test. The ICC copy is gated to automated retrieval, so those cell values were confirmed against two independent published reproductions of the table.
  6. [6]International Code Council — IRC 2021 Table R301.5, Minimum Uniformly Distributed Live Loads: 40 psf rooms other than sleeping rooms, 30 psf sleeping rooms, 30 psf habitable attics and attics served by a fixed stair, 20 psf attics with limited storage, 10 psf attics without storage, 40 psf exterior balconies and decks. Source of the live-load figures in the field hint.
  7. [7]International Code Council — IRC 2021 Table R301.7, Allowable Deflection of Structural Members: L/360 for floors, L/240 for all other structural members. L/480 is offered on this page as common practice under rigid finishes and is explicitly labelled as not being a code requirement, because Table R301.7 does not contain it.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 977 calculators remain free
  • No billing is enabled
Coming soon