Audited 30 Jul 2026·Last updated 31 Jul 2026·6 citations·Tier 2·0 uses

Door Header Size Calculator

What size header a door or window opening needs. Runs the NDS 2018 bending, shear, sag and bearing checks and counts the jack studs at each end.

Door Header Size Calculator

Species and grade
Plies in the built-up header
The framed opening, not the door slab — about 38 in for a 3-0 door and 74 in for a 6-0 patio door. The design span adds 1.5 in of jack-stud bearing at each end.
in
Half the span of the joists, rafters or trusses bearing on this wall, plus any overhang they carry. For a 28 ft wide house with a ridge down the middle it is 14 ft — HALF the building width, not all of it.
ft
This is the ROOF snow load, not the ground snow load — ASCE 7 flat-roof snow is pf = 0.7 Ce Ct Is pg, so 30 psf on the ground is 21 psf on a warm unobstructed roof. Roof live load is 20 psf and a bedroom or living room floor is 40 psf under IRC Table R301.5.
lb/ft²
PLIB Technical Report No. 8 uses 20 lb/ft² for roof plus ceiling and 10 lb/ft² for a light-frame floor.
lb/ft²
Load that does not come through the tributary area — the wall above, most often. PLIB TR-8 allows 121 lb/ft for a wall. Enter 0 if the header carries no wall.
lb/ft
Any further live load per foot of header. Leave it at 0 if the tributary figures already cover everything.
lb/ft
Governing load combination
Live-load deflection limit
Used only when species is set to custom. Take the reference bending design value from NDS-2018 Supplement Table 4A or 4B for your exact species, grade and size classification.
psi
Used only when species is set to custom. Reference shear parallel to grain, same table.
psi
Used only when species is set to custom. E drives deflection and is never adjusted by the load duration factor.
psi
Used only when species is set to custom. Compression perpendicular to grain sets the required bearing length and therefore the jack stud count.
psi
Header to use
(2) 2x10 Douglas Fir-Larch No. 2
The shallowest built-up section at your chosen ply count that satisfies bending, horizontal shear and live-load deflection over the design span. This is an ANSI/AWC NDS-2018 engineering check, not a reproduction of a code span table — where your jurisdiction is on the prescriptive path, IRC Table R602.7(1) governs and its tabulated span and jack stud count are what an inspector checks. Adopted IRC editions differ (2018, 2021, 2024) and local amendments govern. A licensed structural engineer or architect must confirm this member and sign off before work proceeds.
Jack studs per end
1
Dressed depth
9.25in
Built-up width
3in
Design span
6.4167ft
Total uniform load
695lb/ft
Maximum moment
3,576.9575ft-lb
Reaction at each end
2,229.7917lb
Bending used
88.13%
Shear used
58.23%
Deflection used
11.04%
Live-load sag
0.0354in
Reading of the result
A 74 in rough opening gives a design span of 77 in (6.42 ft) once 1.5 in of jack-stud bearing is added at each end. The header carries 695 lb/ft in total, of which 294 lb/ft is live or snow, so the maximum moment is w L² / 8 = 3576.96 ft-lb and each end reaction is 2229.79 lb. The smallest 2-ply section in Douglas Fir-Larch No. 2 that passes all three checks is (2) 2x10 Douglas Fir-Larch No. 2: bending at 88.1 %, shear at 58.2 % and live-load deflection at 11 % of L/240 (0.0354 in). Bending governs. Bearing needs 1.189 in of length at 625 psi compression perpendicular to grain, so 1 jack stud per end. METHOD. This is an ANSI/AWC NDS-2018 check, not a reproduction of a code span table. No tabulated span is asserted anywhere on this page. Reference design values are NDS-2018 Supplement Table 4A for No. 2 visually graded dimension lumber; the size factor C_F comes from the same table's adjustment factors (1.3 / 1.2 / 1.1 / 1.0 at 6 / 8 / 10 / 12 in deep); the load duration factor C_D is 1.15; and the repetitive member factor C_r is 1 because NDS applies 1.15 only to members not less than three in number. Pacific Lumber Inspection Bureau Technical Report No. 8, whose criteria are stated to be consistent with IRC R602.7(1) and R602.7(2), uses C_r = 1.1 for a 2-ply header; this page uses the more conservative NDS text. Shear is taken without the NDS 3.4.3.1 allowance to neglect loads within d of the supports, so it errs high. Deflection uses the live or snow load only. SCOPE. Built-up sawn dimension lumber only, 2 to 4 plies of 2x6 through 2x12, on a simple span with a uniformly distributed load. It does not size engineered lumber (LVL, PSL, glulam) or steel; it does not handle point loads from a girder or a post landing on the header; and it assumes the compression edge is continuously laterally braced by the plate with the ends held in position, so the beam stability factor C_L is 1.0. Where the top of a header is not laterally braced, IRC R602.7(1) requires tabulated spans for 2x8, 2x10 and 2x12 to be multiplied by 0.70 or the member to be designed — this page will not size that condition. Dry service and normal temperature are assumed (C_M = C_t = 1.0). The jack stud count is a BEARING check under NDS 3.10.2 with the bearing area factor C_b ignored; it does not check the jack stud as a column, and it is not the prescriptive NJ value. CODE AND SIGN-OFF. Where your jurisdiction is on the prescriptive path, IRC Table R602.7(1) governs and its tabulated span and NJ jack stud count are the numbers an inspector will check — they can differ from these. The IRC edition adopted where you are may be 2018, 2021 or 2024, local amendments govern, and high-wind and high-seismic regions are pushed out of the prescriptive tables entirely and into AWC's Wood Frame Construction Manual or ICC 600. A licensed structural engineer or architect must confirm this member and sign off before any work proceeds, and nothing here replaces a permit, a plan review or an inspection. Removing or undersizing a header in a bearing wall is a collapse mechanism, not a finish defect.

Background.

A header is the beam over a door or window that picks up whatever the wall would have carried if the opening were not there and hands it sideways to the jack studs at each end. Get it right and nobody ever thinks about it again. Get it wrong and the first symptom is a door that binds in its frame, followed by cracked drywall above the corners, followed by a sagging line in the ceiling. In a bearing wall, an undersized header is a collapse mechanism rather than a finish defect, which is why this is one of the few residential framing decisions that a building inspector will actually measure.

This calculator answers the question the way a framer asks it: I have an opening this wide, carrying this much roof or floor, so what size header do I need and how many jack studs go under each end? It walks a 2x6, 2x8, 2x10 and 2x12 in turn at the ply count you choose, runs three checks on each one, and reports the shallowest section that passes all three — plus the bearing check that sets the jack stud count. That is a genuinely different question from "how far can this beam span", which is what a span calculator answers; if you already know the member and want its reach, use the wood beam span page instead.

The three checks are the ones the code's own span tables are derived from. Bending asks whether the extreme fibres of the header are overstressed at midspan, where the moment is w L² / 8. Horizontal shear asks whether the member will fail along the grain near the supports, where the vertical shear is w L / 2. Deflection asks whether the header will sag visibly, which is a serviceability question rather than a strength one, and is what the familiar L/240 and L/360 limits control. On a residential header, bending governs almost every time, deflection occasionally, and shear essentially never — which is worth knowing before you spend an afternoon worrying about the wrong one.

A fourth check has nothing to do with the header itself. Wood is far weaker across the grain than along it, so the real question at each end is whether the bearing surface is long enough to keep the plate from being crushed. That is why the answer is not just a size but a size and a jack stud count: each jack stud gives you 1.5 in of bearing length, and the required length is the end reaction divided by the compression perpendicular to grain value and the built-up width.

What this page is, precisely, is an ANSI/AWC NDS-2018 allowable-stress check on built-up sawn dimension lumber. What it is not is a reproduction of IRC Table R602.7(1). Those tabulated spans are copyrighted and are not reproduced anywhere here; instead this page runs the engineering check behind them, using the published design criteria of Pacific Lumber Inspection Bureau Technical Report No. 8, whose stated criteria are consistent with that table. The two can disagree by a size, and where your jurisdiction is on the prescriptive path the table governs.

So read the result as a sanity check and a shopping list, not as a permit. It covers sawn lumber only, on a simple span, under a uniformly distributed load, with the top of the header laterally braced. It will not size engineered lumber or steel, it does not accept a point load from a girder or post landing on the header, and it says nothing about the studs, plates and footings that carry the reaction down to the ground. Adopted code editions differ by jurisdiction and local amendments govern. A licensed structural engineer or architect has to confirm the member and sign off before work proceeds.

What is door header size calculator?

A door header — a lintel in British usage, a girder when it runs under a floor rather than over an opening — is a horizontal member spanning a framed opening in a wall. In North American light-frame construction it is normally built up from two, three or four plies of nominal 2x lumber nailed together, sometimes with a plywood spacer so the assembly finishes flush with the wall thickness. Each ply is 1.5 in thick dressed, so a two-ply header is 3 in wide and a three-ply is 4.5 in.

The header sits on jack studs (also trimmer studs) that are cut short to fit under it, and those in turn bear on the bottom plate, the floor framing and eventually the foundation. King studs run full height alongside, holding the assembly in position. The header's design span is measured between the faces of the jack studs, which is the rough opening plus 1.5 in at each end — 3 in more than the opening you measured.

Two numbers describe the shape of the member and do all the work. The section modulus S = b d² / 6 governs bending: because depth is squared, a 2x10 is roughly 1.6 times stronger in bending than a 2x8 of the same width, while a second ply only doubles it. The moment of inertia I = b d³ / 12 governs deflection, where depth is cubed, so depth is even more decisive for sag than for strength. This is why adding depth beats adding plies whenever the headroom exists, and why a header that fails is almost always too shallow rather than too narrow.

How to use this calculator.

  1. Measure the rough opening — the framed hole, not the door or window unit. A 3-0 door is usually about 38 in of rough opening and a 6-0 patio door about 74 in. The page adds 1.5 in of jack-stud bearing at each end for you.
  2. Work out the tributary width: half the span of the joists, rafters or trusses that land on this wall, plus any overhang they carry. For a 28 ft wide house with a ridge down the middle it is 14 ft. It is half the framing span, never the whole building width.
  3. Enter the live or snow load on that area. Use the ROOF snow load, not the ground snow load — ASCE 7 flat-roof snow is pf = 0.7 Ce Ct Is pg, so 30 psf on the ground is 21 psf on a warm unobstructed roof. Roof live load is 20 psf; a bedroom floor is 40 psf.
  4. Enter the dead load. TR-8 uses 20 psf for roof plus ceiling and 10 psf for a light-frame floor, and allows 121 lb/ft for the wall sitting on the header — that goes in the extra dead load field, because it does not come through the tributary area.
  5. Pick the governing load combination. It sets the load duration factor CD: 1.15 for snow, 1.25 for roof live, 1.00 for a floor. Then pick the deflection limit — L/240 for roof and ceiling only, L/360 once a floor is carried.
  6. Choose the species from the grade stamp and the number of plies your wall thickness allows. Read the answer, then read the note beside it: it tells you which of the three checks governed, how close to the limit you are, and what the page did not check.

The formula.

f_b = (w L² ⁄ 8) ⁄ S ≤ Fb·CD·CF·Cr f_v = 1.5(w L ⁄ 2) ⁄ A ≤ Fv·CD Δ = 5 w_LL L⁴ ⁄ (384 E I) ≤ L ⁄ n jacks = ⌈ (w L ⁄ 2) ⁄ (Fc⊥ b) ⁄ 1.5 ⌉

Everything starts from the design span. The header bears on the jack studs, so L = rough opening + 2 × 1.5 in. A 74 in opening gives a 77 in span, which is 6.4167 ft. The built-up width is b = plies × 1.5 in, so a two-ply header is 3 in wide, and the dressed depth d is 5.5, 7.25, 9.25 or 11.25 in for a nominal 2x6 through 2x12 (PS 20 dry surfaced sizes). From those two, S = b d² / 6 and I = b d³ / 12, which are NDS-2018 equations 3.3-4 and 3.3-3.

The load is w = tributary width × (dead psf + live psf) + the two per-foot terms. In the worked example that is 14 × (20 + 21) + 121 = 695 lb per foot, of which 294 lb/ft is snow. The moment is M = w L² / 8 = 3,576.96 ft-lb and each end reaction is R = w L / 2 = 2,229.79 lb.

Bending compares f_b = M / S against the adjusted design value F_b′ = Fb × CD × CF × Cr. Douglas Fir-Larch No. 2 has a reference Fb of 900 psi in NDS-2018 Supplement Table 4A. CD is the load duration factor from Table 2.3.2 — 1.15 for a snow combination. CF is the size factor from the same table's adjustment factors, and it is where depth pays twice: 1.3 at 6 in deep, 1.2 at 8 in, 1.1 at 10 in and 1.0 at 12 in. Cr is the repetitive member factor, which NDS grants as 1.15 only to members "not less than 3 in number", so a two-ply header gets 1.0. For the 2x10 that makes F_b′ = 900 × 1.15 × 1.1 = 1,138.5 psi against an actual 1,003.32 psi — 88.13 % used, and the section passes.

Shear compares f_v = 1.5 V / A against F_v′ = Fv × CD, which is NDS-2018 equation 3.4-2 written as 3V/2bd. With V = 2,229.79 lb and A = 27.75 in², f_v is 120.53 psi against 207 psi allowed: 58.23 % used. The page deliberately declines the NDS 3.4.3.1 allowance to ignore uniformly distributed load within a depth of the supports, so this figure errs high.

Deflection uses the live or snow load alone: Δ = 5 w L⁴ / (384 E I). With E = 1,600,000 psi and I = 197.86 in⁴, Δ = 0.0354 in against an allowable L/240 = 0.3208 in, which is 11.04 % used. Note that the load duration factor never appears here: NDS Table 2.3.2 footnote 1 says CD does not apply to E. A snow header and a floor header of the same section sag identically under the same live load.

Bearing is the last check and the one people skip. The required bearing length is R / (Fc⊥ × b) = 2,229.79 / (625 × 3) = 1.189 in, and since each jack stud provides 1.5 in, one jack stud per end is enough. CD does not apply to Fc⊥ either, so a longer-duration load does not buy you a shorter bearing. Hem-Fir, with Fc⊥ of 405 psi against Douglas Fir-Larch's 625, needs two jack studs at exactly the same reaction — a good illustration that the species matters at the ends as well as in the middle.

One recorded conflict, because it changes answers. TR-8's design criteria use Cr = 1.1 for a two-ply header; the NDS text grants 1.15 only at three members or more and offers no 1.1. This page follows the NDS text, which is about 4.65 % more conservative on span. Reproducing TR-8's own table with its 1.1 gives a two-ply 2x10 a 7 ft 2 in span at 695 lb/ft, exactly as tabulated; with the NDS 1.0 the same member reaches 6 ft 10 in. So this page will sometimes ask for one size more than the prescriptive table. That is the direction to err.

A worked example.

Example

A 6-0 patio door is going into the long exterior bearing wall of a 28 ft wide house in a region with a 30 psf ground snow load. The rough opening measures 74 in, so the header's design span is 77 in — 6.4167 ft — once 1.5 in of jack-stud bearing is added at each end. Trusses span the full 28 ft with no interior bearing wall, so the tributary width is 14 ft. Roof plus ceiling dead load is 20 psf and the roof snow load is 21 psf, which is 0.7 × 30 psf ground snow, and the wall above the opening adds 121 lb/ft. That is 695 lb per foot in total, 294 lb/ft of it snow. The moment is 3,576.96 ft-lb and each end carries 2,229.79 lb. Walking the ladder at two plies with CD = 1.15: a 2x6 wants 210.9 % of its bending capacity and a 2x8 wants 131.5 %, so both are out. The 2x10 comes in at 88.1 % of bending, 58.2 % of shear and 11.0 % of the L/240 deflection limit — 0.0354 in of sag, about the thickness of a business card over a 6 ft opening. So the answer is (2) 2x10 Douglas Fir-Larch No. 2, and bending is what governs it. At the ends, the required bearing length is 2,229.79 lb ÷ (625 psi × 3 in) = 1.189 in, and one jack stud gives 1.5 in, so one jack stud per end is enough — though the IRC table's prescriptive NJ figure for a comparable case is what an inspector on the prescriptive path will actually count. Two things are worth noticing. First, shear is not remotely close to governing, which is normal on a residential header. Second, the same header in Hem-Fir would still be a 2x10 but would need two jack studs, because Hem-Fir's compression perpendicular to grain is 405 psi against Douglas Fir-Larch's 625 — the ends, not the middle, are where the weaker species shows up. Widen the tributary to 20 ft, as it would be on a 40 ft wide house, and the 2x10 fails bending at 119.3 %: the answer becomes (2) 2x12 with two jack studs per end.

custom E Psi1,600,000
additional Live Load Plf0
dead Load Psf20
plies2
custom Fv Psi180
live Or Snow Load Psf21
deflection Limit Denominator240
additional Dead Load Plf121
load Durationsnow
rough Opening Width In74
speciesdouglasFirLarch
custom Fc Perp Psi625
custom Fb Psi900
tributary Width Ft14

Frequently asked questions.

What size header do I need for a 6 foot opening?
There is no single answer, which is why a chart is a trap: it depends on how much roof or floor lands on that wall. For the worked example above — a 74 in rough opening, 14 ft of tributary width, 21 psf roof snow, 20 psf dead and a wall above — a two-ply 2x10 in Douglas Fir-Larch No. 2 does it at 88 % of bending capacity. Double the tributary width to 20 ft and the same opening needs a two-ply 2x12. Put a floor on it instead of a roof, so the load duration factor drops from 1.15 to 1.00, and again you are at a 2x12. Same opening, three different answers.
Is this the same as the IRC header span table?
No, and the difference matters. IRC Table R602.7(1) is a prescriptive table: it lists spans you may use without engineering. This page runs the NDS-2018 engineering check that the table is derived from, using PLIB Technical Report No. 8's published design criteria, and asserts no tabulated span anywhere. The two agree closely — reproducing TR-8's loading and its own repetitive member factor reproduces five of its tabulated spans to within half an inch — but this page follows the NDS text on that factor and so runs about 4.65 % more conservative on a two-ply header, which is occasionally one size deeper. Where your jurisdiction is on the prescriptive path, the table governs and its span and jack stud count are what the inspector checks.
Why does the calculator add 3 inches to my rough opening?
Because the header does not span the hole, it spans between the jack studs that hold it up, and each of those is 1.5 in thick. A 74 in rough opening is a 77 in design span. Skipping that step understates the moment by about 8 % on a 6 ft opening and more on a small one, always in the unsafe direction. If you are comparing against a span table, check what its span means: reproducing TR-8's table only works if its tabulated value is used directly as the design span, so this page is slightly more conservative than the table for the same clear opening.
How many jack studs do I need under each end?
It is a bearing calculation, not a rule of thumb. Divide the end reaction by the compression perpendicular to grain value and the built-up width to get a required bearing length, then divide by 1.5 in per jack stud and round up. In the worked example, 2,229.79 lb ÷ (625 psi × 3 in) = 1.189 in of required bearing, so one jack stud suffices. Note that this is a bearing check on the header, not the prescriptive NJ value from the IRC table, and it does not check the jack stud itself as a column or the plates and floor framing below it. The IRC's own note allows a single required jack stud to be replaced by an approved framing anchor attached to the king stud.
Should I add plies or add depth?
Depth, whenever the headroom exists. Bending capacity goes with the section modulus b d² / 6, so depth is squared while width is only linear: going from a 2x8 to a 2x10 at the same two plies buys about 63 % more bending capacity, while adding a third ply buys 50 % — and 72 % once the repetitive member factor kicks in at three members. For deflection the case is even stronger, because the moment of inertia b d³ / 12 cubes the depth. A third ply also has to fit: two plies plus a spacer fill a 2x4 wall, three fill a 2x6.
Why doesn't a longer load duration help the sag or the bearing?
Because the load duration factor does not apply to either. NDS-2018 Table 2.3.2 footnote 1 says CD shall not apply to the reference modulus of elasticity, to Emin, or to compression perpendicular to grain based on a deformation limit. Wood carries a short-term load at a higher stress than a long-term one, but it does not become stiffer, and it does not resist crushing across the grain any better. You can see it on this page: switch the combination from snow to roof live and the bending and shear utilisations both fall by exactly 1.15/1.25, while the deflection and the jack stud count do not move at all.
What is this page not checking?
Quite a lot, deliberately. It sizes built-up sawn dimension lumber only — 2 to 4 plies of 2x6 through 2x12 — on a simple span under a uniformly distributed load. It does not size LVL, PSL, glulam or steel; those need the manufacturer's evaluation report. It does not accept a point load from a girder, a post or a beam landing on the header. It assumes the top of the header is laterally braced by perpendicular framing, so the beam stability factor is 1.0; where cripple studs bear on the header instead, the prescriptive rule is to multiply tabulated spans for 2x8 and deeper by 0.70 or design the member, and this page will not size that condition. It assumes dry service and normal temperature. And it stops at the header: the studs, plates, rim and footings that carry the reaction to the ground are somebody else's calculation.
Why is Southern Pine missing from the species list?
Because applying this page's size factor to Southern Pine would double-count it. Southern Pine is tabulated separately in NDS-2018 Supplement Table 4B, and that table's own adjustment factors say the reason plainly: "Appropriate size adjustment factors have already been incorporated in the tabulated design values for most thicknesses of Southern Pine and Mixed Southern Pine dimension lumber." Multiplying a Table 4B value by the Table 4A ladder would overstate a 2x6's bending capacity by 30 %. Rather than special-case it here, the page leaves it out and offers a custom mode: look your grade and size up in Table 4B and enter Fb, Fv, E and Fc⊥ directly. The custom mode is also how you use a species this page does not list, or a grade other than No. 2.

References& sources.

  1. [1]American Wood Council — ANSI/AWC NDS-2018 Supplement, Design Values for Wood Construction (2020-08-27 web printing). Table 4A reference design values for visually graded dimension lumber 2"–4" thick: Douglas Fir-Larch No. 2 Fb 900, Fv 180, Fc⊥ 625, E 1,600,000 psi; Hem-Fir No. 2 850 / 150 / 405 / 1,300,000; Spruce-Pine-Fir No.1/No.2 875 / 135 / 425 / 1,400,000. Table 4A Adjustment Factors: size factor CF for Fb of 1.3 / 1.2 / 1.1 / 1.0 at 6 / 8 / 10 / 12 in deep, and repetitive member factor Cr = 1.15 for members "not less than 3 in number". Table 4B Adjustment Factors, Size Factor: "Appropriate size adjustment factors have already been incorporated in the tabulated design values for most thicknesses of Southern Pine and Mixed Southern Pine dimension lumber" — which is why Southern Pine is not offered as a species here. Open access, retrieved 2026-07-30.
  2. [2]American Wood Council — ANSI/AWC NDS-2018 with Commentary, Chapter 2. Table 2.3.2 Frequently Used Load Duration Factors CD: 0.9 permanent, 1.0 ten years (occupancy live), 1.15 two months (snow), 1.25 seven days (construction), 1.6 ten minutes (wind/earthquake). Footnote 1: load duration factors shall not apply to E, Emin, or to Fc⊥ based on a deformation limit. Open access, retrieved 2026-07-30.
  3. [3]American Wood Council — ANSI/AWC NDS-2018 with Commentary, Chapter 3. Eq. 3.3-3 (I = bd³/12) and Eq. 3.3-4 (S = bd²/6); Eq. 3.4-2 (f_v = 3V/2bd for a rectangular bending member); 3.4.3.1(a), the allowance to ignore uniformly distributed load within a depth d of the supports, which this page declines; 3.3.3.3 (CL = 1.0 when the compression edge is supported throughout its length and the ends are held against rotation); 3.10.2 (bearing perpendicular to grain on the net bearing area, f_c⊥ ≤ F_c⊥′). Open access, retrieved 2026-07-30.
  4. [4]Pacific Lumber Inspection Bureau — Technical Report No. 8, Span Tables for Headers and Girders for Domestic Species, 1 July 2021. Its introduction states the design criteria, calculations and tabulated values are consistent with AWC's Wood Frame Construction Manual and ICC's 2018 IRC R602.7(1) and R602.7(2), and that basic wind speeds above 130 mph leave the prescriptive provisions for the WFCM or ICC 600. Design criteria: 20 psf roof dead, 121 plf wall dead, 10 psf floor dead, ΔLL = L/240 supporting only roof and ceiling and L/360 otherwise, CD 1.25 / 1.00 / 1.15 by combination, Cr 1.0 / 1.1 / 1.15 / 1.15 at 1 / 2 / 3 / 4 plies. Table 2 gives No. 2 Douglas Fir-Larch spans and jack stud counts; footnote e carries the 0.70 multiplier for an unbraced header top. This is the source of the independent check that reproduces five of its tabulated spans to within half an inch. Open access, retrieved 2026-07-30.
  5. [5]International Code Council — 2021 International Residential Code §R602.7 Headers and Table R602.7(1), Girder Spans and Header Spans for Exterior Bearing Walls. This is the prescriptive route that governs where it is adopted, and the table this page deliberately does not reproduce. Gated: ICC Digital Codes is free to read in a browser with an account but refused automated retrieval (HTTP 403) on 2026-07-30, so no value on this page is attributed to it. Adopted editions vary by jurisdiction — 2018, 2021 and 2024 are all in force somewhere — and local amendments govern.
  6. [6]American Lumber Standard Committee / US Department of Commerce — Voluntary Product Standard PS 20, American Softwood Lumber Standard. Dressed dry surfaced sizes used here: nominal 2x lumber is 1.5 in thick, and 2x6 / 2x8 / 2x10 / 2x12 are 5.5 / 7.25 / 9.25 / 11.25 in deep. Print standard, not retrieved online; the same dressed depths are confirmed indirectly by the PLIB TR-8 span reproduction above, which only matches to the inch if these depths are correct.

In this category

Embed

Quanta Pro

Paid features are coming later.

  • All 977 calculators remain free
  • No billing is enabled
Coming soon