Audited 05 Aug 2026·Last updated 28 Oct 2026·3 citations·Tier 2·0 uses

Ductwork Sizing Calculator

Size a duct from airflow in CFM and target velocity in FPM: cross-section in sq ft, the equal-area round diameter, and rectangular width at your ratio.

Ductwork Sizing Calculator

Required duct area
1.1429
The open cross-sectional area the duct needs, in square feet: airflow ÷ velocity. Multiply by 144 for square inches.
Equivalent round diameter
14.4755
Rectangular width at entered aspect ratio
18.1423

Background.

Air moving through a duct obeys a simple continuity rule: the volume of air per minute equals the duct's cross-sectional area times the speed of the air. Pick the airflow a room or system needs and the speed you are willing to push it at, and the area follows. 800 cubic feet per minute at 700 feet per minute needs 800 ÷ 700, about 1.14 square feet of open duct.

Velocity is the design choice. Faster air lets you use smaller, cheaper ducts that fit more easily between joists, but it costs you twice over: noise rises, and friction losses climb steeply with speed, so the blower has to work harder against more static pressure. Slower air is quiet and efficient but needs bigger ducts. At 600 FPM the same 800 CFM would need a 15.64 inch round duct; at 900 FPM, 12.77 inches.

From the required area the calculator gives two shapes. The round diameter is the circle with exactly that area. The rectangular width is the width of a rectangle with that same area at the width-to-height ratio you choose, and the height is the width divided by the ratio.

That equal-area conversion is a starting point, not a final size. A rectangle has more wall per square inch of opening than a circle, so at equal area it has more friction, and the gap grows as the shape gets flatter. Full residential design under ACCA Manual D sizes each run from the blower's available static pressure and the run's effective length, fittings included, then checks velocity against the manual's limits. Velocity sizing alone checks only the last of those steps.

What is ductwork sizing calculator?

Duct sizing by velocity finds the cross-sectional area a duct needs to carry a design airflow at a chosen air speed. Airflow is in cubic feet per minute (CFM), velocity in feet per minute (FPM), and the area in square feet. The area is then expressed as the diameter of a round duct, or the width of a rectangular one, with the same open area. It does not determine pressure loss, which depends on duct length, fittings, shape and lining as well as velocity.

How to use this calculator.

  1. Enter the design airflow in CFM for the duct section you are sizing: the whole system's blower airflow for the main trunk, or a single room's share for a branch. Room airflows come from a Manual J load calculation; a rough check for cooling is about 400 CFM per ton.
  2. Enter the target velocity in FPM. Use lower speeds near living spaces and for returns where noise matters, and check the maximum velocities your design standard sets for trunks, branches and grilles.
  3. Enter a width-to-height ratio for a rectangular duct, from 1 for square up to 10. Choose it from the space available, such as the depth of a joist bay, and keep it as low as the space allows.
  4. Round the results up to a size that is actually made, usually whole inches, then check the real velocity of the chosen size by dividing the CFM by its area.

The formula.

area = airflow ÷ velocity; round diameter = √(4A ÷ π); rectangular width = √(A × width-to-height ratio)

Area A = Q ÷ V, where Q is the airflow in CFM and V the velocity in FPM, so A is in square feet. The round diameter with that area is D = √(4A ÷ π) × 12, in inches. For a rectangle with width-to-height ratio r, width × height = A and width = r × height, so width = √(A × r) × 12 inches and height = width ÷ r. Area scales directly with airflow and inversely with velocity, while the diameter scales with the square root of both, so doubling the airflow at the same velocity widens a round duct by about 41%, not 100%. The round diameter is an equal-area equivalent. Friction charts and duct calculators use a different, equal-friction equivalent diameter, often from the Huebscher formula De = 1.30 (ab)^0.625 ÷ (a + b)^0.25, which for any rectangle comes out smaller than the equal-area diameter.

A worked example.

Example

A supply trunk must carry 800 CFM at a target of 700 FPM, in a rectangular duct twice as wide as it is tall. The required duct area is 800 ÷ 700 = 1.1429 square feet, or about 164.57 square inches. A round duct with that area has a diameter of √(4 × 1.1429 ÷ π) × 12 = 14.4755 inches. At a 2:1 ratio the rectangular width is √(1.1429 × 2) × 12 = 18.1423 inches, and the height is 18.1423 ÷ 2 = 9.0711 inches. No one buys a 14.48 inch duct. A 15 inch round duct has 1.2272 square feet of area, so the air actually moves at 800 ÷ 1.2272, about 652 FPM; a 14 inch duct would run at about 748 FPM. For the rectangle, the equal-friction diameter of the 18.14 × 9.07 inch section is only about 13.82 inches, so it would carry the air with more friction than the 14.48 inch round. An 18 × 10 inch duct, with an equal-friction diameter of about 14.51 inches, is the closer match.

airflow Cfm800
aspect Ratio2
target Velocity Fpm700

Frequently asked questions.

What velocity should I design residential ducts for?
It depends on the section and on how much noise you will accept. Trunks near the air handler tolerate more speed than branches and grilles in bedrooms, and returns are usually kept slower still. ACCA Manual D tabulates maximum velocities for each, and a velocity under those limits is a check, not the sizing method itself.
Why does a duct calculator give a different equivalent diameter for my rectangular duct?
Most duct calculators and friction charts use an equal-friction equivalent: the round duct with the same pressure loss per foot at the same airflow. This calculation gives the equal-area equivalent. The equal-friction value is always the smaller of the two, by more as the rectangle gets flatter, because the extra wall surface adds drag.
How tall should the rectangular duct be?
Divide the width by the ratio you entered. In the example, 18.1423 ÷ 2 gives 9.0711 inches. If the space fixes the height, say 8 inches between joists, work backwards: 164.57 square inches ÷ 8 is about 20.6 inches of width, a ratio of about 2.6.
Does the aspect ratio change anything besides the shape?
Yes. At the same area, a flatter duct has more perimeter: for 164.57 square inches, a square is 51.3 inches around, a 2:1 rectangle 54.4 inches and a 4:1 rectangle 64.1 inches. More perimeter means more sheet metal, more surface losing heat and more friction, which is why square-ish ducts are preferred where space allows.
Can I size flexible duct this way?
The area and diameter apply to the inner diameter of flex duct, but flex has much more friction than smooth metal, and far more again when it sags or is compressed rather than pulled taut. Velocity sizing does not see that difference, so flex runs sized this way should be kept short, straight and fully stretched.
Where does the design airflow come from?
Room by room, from a Manual J heating and cooling load calculation, and for the system from the equipment selected under Manual S and the blower setting. The figure of roughly 400 CFM per ton of cooling is a common check; on that basis, 800 CFM corresponds to about a 2-ton system.

How this page was produced

Published by
Quanta Calculator
Primary sources
3 cited below
Method
area = airflow ÷ velocity; round diameter = √(4A ÷ π); rectangular width = √(A × width-to-height ratio)