Radiant Floor Heating Calculator
Turn a heat-loss figure in Btu/h per square foot into the load a radiant floor must deliver and the boiler or electric input needed, in Btu/h and kW.
Radiant Floor Heating Calculator
Background.
A radiant floor is sized backwards from the building. The starting point is a heat-loss report: how many Btu per hour each room leaks to the outdoors on the design day, worked out room by room with a method such as ACCA Manual J. Divide a room's loss by the floor area that will carry tubing or heating cable and you have the design load in Btu per hour per square foot. Multiply back by the area for the heat the floor must give off, then divide by the efficiency of the source and its distribution for what the boiler, water heater or electric circuit has to supply.
That last step is the one that gets skipped. A floor that must put 25,000 Btu/h into the house, fed by a system that turns 90% of its energy into useful floor heat, needs a source rated for about 27,778 Btu/h of input, roughly 8.14 kW.
The per-square-foot figure is also a feasibility check. A floor can only run so warm before it feels uncomfortable underfoot: ASHRAE Standard 55 and the European standard EN 1264 both put the ceiling for areas where people stand at 29 °C, about 84 °F. Hydronic designers commonly reckon that a floor emits roughly 2 Btu/h per square foot for each °F it sits above room air, so in a 68 °F room a floor at 84 °F tops out near 32 Btu/h·ft². A sunroom walled in glass, or a kitchen where cabinets cover a third of the floor, can need more than that, and no boiler upgrade fixes it; the room needs a second heat emitter.
What the arithmetic leaves to the designer is the floor itself: tube or cable spacing, supply water temperature, the resistance of the rug or hardwood laid on top, insulation beneath the slab, and the controls.
What is radiant floor heating calculator?
The delivered design heat load is the rate, in Btu per hour, at which the heated area loses heat at the heating design temperature, which under Manual J is the outdoor temperature beaten on the cold side only about 1% of the hours in a year. The required heat-source input is that load divided by the share of the source's energy that actually reaches the room as heat. On a boiler, the comparable figure is the nameplate input rating. An electric cable or mat turns essentially all of its electricity into heat, so for an electric floor at 100% the input and the delivered load are the same quantity, and the kilowatt figure is the electrical load the circuits must carry.
How to use this calculator.
- Enter the heated floor area in square feet: the area that will actually have tubing or cable beneath it. Leave out cabinets, islands, tubs, shower bases and anywhere a fixed appliance will stand.
- Enter the design heat load in Btu per hour per square foot from a room-by-room heat-loss report, calculated as the room's loss divided by the area you just entered. A figure quoted in watts per square metre converts by dividing by 3.155.
- Enter the delivered-system efficiency as a percentage. Start from the source's rated efficiency (AFUE for a boiler, 100 for electric resistance) and reduce it if a meaningful share of the heat will escape downward into soil or an unheated space.
- Compare the required input with the input rating on the boiler or water heater you are considering, and the delivered load with its output rating. For an electric floor, take the kW figure to whoever is sizing the circuits.
The formula.
Delivered load Q = A × q, where A is the heated floor area in square feet and q the design load in Btu/h·ft². Required input = Q ÷ (η ÷ 100), where η is the delivered-system efficiency in percent. The kilowatt figure is the required input divided by 3,412.142, the number of Btu per hour in one kilowatt. Efficiency enters as a single combined factor, so if you know the losses separately, multiply them: a 95% boiler feeding a slab that loses a tenth of its heat to the ground works out to 0.95 × 0.90 = 85.5% overall, which lifts a 25,000 Btu/h load to about 29,240 Btu/h of input. Every term is linear, so doubling area or per-square-foot load doubles each output. Two limits follow from the structure. The model does not check whether the floor can physically emit q; that depends on the surface temperature that spacing, water temperature and covering produce. And efficiency cannot exceed 100%, so a heat pump's coefficient of performance has no place here.
A worked example.
A 1,000 sq ft slab-on-grade addition has a heat-loss report that works out to 25 Btu/h for every square foot of heated floor, and the boiler and piping together deliver 90% of their fuel energy to the slab. Delivered load: 1,000 × 25 = 25,000 Btu/h. Required input: 25,000 ÷ 0.90 = 27,777.78 Btu/h, so about 27,778 Btu/h. In kilowatts: 27,777.78 ÷ 3,412.142 = 8.1409 kW. A boiler with an input rating of at least 27,778 Btu/h, and an output rating of at least 25,000 Btu/h, covers the design day. Most of the season is far milder than that, which is why a modulating boiler that can throttle its firing rate suits a slab better than a single-rate unit that would cycle on and off. The 25 Btu/h·ft² is also within what the floor can emit. At roughly 2 Btu/h·ft² per °F, the surface needs to sit about 12.5 °F above room air: around 80.5 °F in a 68 °F room, under the 84 °F comfort ceiling.
Frequently asked questions.
How many Btu per square foot can a radiant floor actually give off?
Should I subtract cabinets and the bathtub from the heated area?
What efficiency should I enter for an electric heating mat or cable?
Can I size a heat pump for radiant floors with this?
Does putting carpet or hardwood on the floor mean a bigger boiler?
Do I need extra capacity for domestic hot water?
References& sources.
- [1]ASHRAE Handbook—Fundamentals, duct design and heat-transfer methods (PAYWALL). Retrieved 2026-08-07.
- [2]Air Conditioning Contractors of America. Manual J — residential load calculation. Retrieved 2026-08-07.
- [3]International Code Council. 2024 International Energy Conservation Code (IECC). Retrieved 2026-08-07.
How this page was produced
- Published by
- Quanta Calculator
- Overseen by
- Daniel, Quanta Calculator Researcher
- Primary sources
- 3 cited below
- Method
- delivered load = floor area × professional Btu/h·ft² load; required input = delivered load ÷ system efficiency
- Published
- Last verified
Built with AI assistance and verified by automated tests against the cited sources — every worked example on this page is computed by the same code that runs the calculator. How we build and check calculators.